Description Safety barriers limit the energy fed to an intrinsically safe circuit so that neither sparks nor thermal effects (hot surfaces) can cause an explosion. CEAG safety barriers can be used for all kinds of instrumentation applications. • Digital inputs • Digital outputs • Analog inputs • Analog outputs • Temperature sensors • Pressure transmitters etc.

■ Plug in barrier to be installed on a backplane ■ Backplane snaps on standard 35 mm DIN rail ■ Optional replaceable fuses ■ LEDs shows barrier status ■ Cage clamp connections need no screws ■ Easy installation ■ General purpose and customized backplanes for easy installation ■ Power supply modules to stabilize barrier voltages ■ Large tagging areas for easy circuit identification ■ Mounts horizontally or vertically ■ International approvals

Safety or zener barriers generally have to be connected to equipotential earth. Each barrier connects to this high intergrity ground. The new plug type barrier has a back plane for 10 modules with a single connection to equipotential earth. By plugging the barriers into the back plane, each of them will automatically be earthed. The back plane can also be fitted with a power supply which stabilizes the mains voltage. It is particularly suitable for supply barriers the auxiliary power connection of which is also fed to the back plane via the copper ducts of the PCB. The new safety barriers are fitted with replaceable upstream fuses. Should the polarity be confused or the operating voltage be inadmissibly high, the upstream fuse is there to protect the internal fuse and thus the valuable barrier from being destroyed. The upstream fuse may be replaced during operation. Supply barriers are fitted with an LED which indicates the proper state of the barrier. When installing the barrier, care has to be taken that the polarity of the chosen barrier matches the circuit. The rated voltage must not be exceeded in operation, since that would result in measuring faults. Account has to be taken of the voltage drop over the end to end resistor of the barrier. A correct transmission of voltage signals can only be achieved with purely ohmic end to end resistors. For safety reasons, the maximum values for current, voltage, inductance and capacitance of the barrier have to be checked to match the data of the connected intrinsically safe circuit.

CEAG Sicherheitstechnik GmbH

184

Safety Barriers

Product features Simple wiring

Simple mounting

• save wiring through backplane technology • the PCB connects all barriers to equipotential earth • a power supply module can feed supply barriers via the printed circuit board • 20-30 V DC stabilized to 24 V DC • the stabilized voltage simplifies the use of supply barriers with otherwise fluctuating power lines

• plug-in barriers • cage clamp wiring • replaceable fuses • large tagging area • dual ground

Terminology

Safety barrier

Operating data VN Rated maximum voltage < 2 µA for V < VN Rmax. End to end resistance Si Internal fuse Technical data: Leakage current at VN Temperature drift Operating temperature Storage temperature range Relative humidity Width Weigth Explosion protection: Approval

Safety parameters (in intrinsically safe ciruits) Voc Isc Ca La

Maximum open circuit voltage Maximum short circuit current Maximum permissible external capacitance Maximum permissible external inductance

6

< 2 mA ≤ -250 x 10 - 6 / K -40 °C ... +60 °C -40 °C ... +80 °C < 75 % (annual average) < 95 % (30 d/a) no condensation see dimensions page 193 approx. 70 g

TÜV 97 ATEX 1167 X

Ordering details

Single barrier socket

Description

Type

Order No.

Standard socket (backplane) for 1 barrier Standard socket (backplane) for 2 barriers Standard socket (backplane) for 10 barriers Supply backplane for 8 barriers replaceable fuse 63 mA replaceable fuse 100 mA replaceable fuse 125 mA replaceable fuse 160 mA replaceable fuse 250 mA

SB- 9101 SB- 9102 SB- 9100 SB- 9200 SB- 9201 SB- 9202 SB- 9203 SB- 9204 SB- 9205

GHG 110 0000 W9101 GHG 110 0000 W9102 GHG 110 0000 W9100 upon enquiry GHG 110 0000 W9201 GHG 110 0000 W9202 GHG 110 0000 W9203 GHG 110 0000 W9204 GHG 110 0000 W9205

Note 10 fold backplane segment

Barriers will be supplied without sockets. Please order socket separately. All barriers can be ordered using the type number or the full order no. GHG….

CEAG Sicherheitstechnik GmbH

185

Safety Barriers

Safety barriers Type

DC barrier

1

23

21

13

11

PA

positive

2

23

21

13

11

VN (V)

Rmax (Ω)

Fuse (mA)

VOC (V)

ISC (mA)

Drawing No.

LED

Order No.

SB-0728

24

340

50

28

93

1

X

GHG 111 9140 W0728

SB-1728

-24

340

50

28

93

2

X

GHG 111 9040 W0728

SB-1240

24

205

50

28

150*

1

X

GHG 111 9140 W2410

SB-1230

24

115

50

27.4

277*

1

X

GHG 111 9140 W2420

SB-0722

18

185

50

22

150

1

GHG 111 9140 W0722

SB-0715

12

155

100

15

150

1

GHG 111 9140 W0715

SB-1250

12

53

100

15

387

1

GHG 111 9140 W1211

SB-0758

6

32

100

7.6

500

1

GHG 111 9140 W0758

SB-0779

24/24

340/340

50/50

28/28

93/93

3

SB-1202

23/17

340/435

50/50

26/20

87/51

3

GHG 115 9140 W0796

SB-0767

12/12

155/155

100/100

15/15

150/150

3

GHG 115 9140 W0767

SB-2250

12/12

53/53

100/100

15/15

387/387

3

SB-1350

10/10

83/495

100/100

11.66/11.66

174/25

3

SB-1351

10/10

495/495

50/50

11.66/11.66

25/25

3

GHG 115 9140 W1351

SB-0764

10/10

1075/1075

50/50

12/12

12/12

3

GHG 115 9140 W0764

SB-1301

+6/-6

74

100/100

17.2

414

4

GHG 113 9140 W1202

PA

negative DC double

3

DC floating

4

X

GHG 115 9140 W0779

GHG 115 9140 W1250 X

GHG 115 9140 W1350

23

21

SB-1302

+9/-9

1145

50/50

25.2

25

4

GHG 113 9140 W1804

13

11

SB-1303

+12/-12

154

50/50

29.4

248

4

GHG 113 9140 W2405

SB-2427

24/24

268/13.5+0.9 V

50/50

26.6

120

5

X

GHG 114 9440 W2427

SB-1787

24/24

340/30+0.9 V

50/50

28

93

5

X

GHG 115 9440 W1787

SB-0707

24/24

280/30+0.9 V

50/50

28

171*

5

X

GHG 115 9440 W0707

PA

double with return

5

23

21

13

11

PA

Channel 2 (11-13)

* only group IB

Channel 1 (21-23)

Note Barriers will be supplied without sockets. Please order socket separately (Page 185). All barriers can be ordered using the type number or the full order no. GHG….

CEAG Sicherheitstechnik GmbH

186

Safety Barriers

Safety barriers

double return

6

23

21

13

11

Type

VN (V)

Rmax (Ω)

SB-0786

24/24

Fuse (mA)

30 Ω + 1.2 V

VOC (V)

ISC (mA)

Drawing No.

LED

Order No.

50/50

28/28

0/0

6

GHG 115 9440 W0786

30 Ω + 1.2 V

PA

7

23

21

13

11

SB-1502

12

30 Ω + 1.2 V

50

16.8

0

7

GHG 111 9440 W1201

SB-1602

12

59

100

16.8

390

8

GHG 111 9240 W0906

SB-0710

6

85

50

10

200

8

GHG 111 9240 W0710

SB-1604

6

195

100

8.8

55

8

GHG 111 9240 W0406

PA

AC standard

8

23

21

13

11

6

PA

SB-1701

AC double

9

23 13

21 11

10/10

185/185

50/50

12/12

80/80

9

GHG 115 9240 W0766

SB-0761

6/6

145/145

100/100

9/9

100/100

9

GHG 115 9240 W0761

SB-0201

1.8/1.8

40/40

150/150

5.3/5.3

178/178

9

GHG 113 9240 W0201

SB-0772

18/18

340/340

50/50

22/22

73/73

10

GHG 115 9240 W0772

SB-0765

12/12

135/135

50/50

15/15

150/150

10

GHG 115 9240 W0765

SB-0760

6/6

85/85

50/50

10/10

200/200

10

GHG 115 9240 W0760

PA

universal

10

23

21

13

11

PA

Channel 2 (11-13) Channel 1 (21-23)

Note Barriers will be supplied without sockets. Please order socket separately (Page 185). All barriers can be ordered using the type number or the full order no. GHG….

CEAG Sicherheitstechnik GmbH

187

Safety Barrier Applications

Digital input Floating circuit - 1 channel • Power supply voltage: 24 V DC • End-to-end resistance 282 Ω +0.9 V • Short circuit proof • Smallest IS barrier available • IS connections for: Zone 1, Group IIC Class I, II, III, Div. 1, Gr. A-G

Hazardous Area

Safe Area 23

21

+24 V

13

11

DI

PA

SB-2427 or SB-1787

Analog input (4 - 20 mA transmitters) Floating circuit - safety barrier circuit • Lowest possible barrier voltage drop: 6.6 V maximum (at 20 mA) • Power supply voltage: 24 V DC • No restrictions for programming SMART transmitters • Smallest IS barrier available • IS connections for: Zone 1, Group IIC Class I, II, III, Div. 1, Gr. A-G

Hazardous Area

+

Safe Area

23

21

13

11

+24 V

-

AI (Load)

PA

SB-2427 or SB-1787

-

CEAG Sicherheitstechnik GmbH

188

Safety Barrier Applications

Digital output (solenoid valves, LEDs or audible alarms) Grounded circuit - 1 channel • Power supply voltage: to 24 V DC • End-to-end resistance: 340 Ω • Short circuit • Smallest IS barrier available • IS connections for: Zone 1, Group IIC Class I, II, III, Div. 1, Gr. A-G Grounded circuit - 1 channel - groups C-G • Low resistance barrier • Power supply voltage: to 26 V DC • End-to-end resistance: 205 Ω • Smallest IS barrier available • IS connections for: Zone 1, Group IIB Class I, II, III, Div. 1, Gr. C-G

6 Hazardous Area +

Safe Area 23 +

+ 21

13 -

- 11

-

+24 V DC

-

PA

SB-0728 or SB-1240

Grounded circuit - 2 channel • Power supply voltage: to 26 V DC • End-to-end resistance 340 Ω/channel • Short cirucit proof • Smallest IS barrier available • IS connections for: Zone 1, Group IIC Class I, II, III, Div. 1, Gr. A-G • Lowest cost solution

Hazardous Area +

Safe Area 23

21

13

11

+24 V DC

PA

+

-

SB-0779

0V

CEAG Sicherheitstechnik GmbH

189

Safety Barrier Applications

Analog output (4 - 20 mA transducers) Grounded circuit - 1 channel • Barrier end-to-end resistance: 155 Ω • Allows the connections of transducers with maximum 445 Ω input impedance • Short circuit proof • Smallest IS barrier available • IS connections for: Zone 1, Group IIC Class I, II, III, Div. 1, Gr. A-G

Hazardous Area 4 - 20 mA

I

+

P

-

Safe Area 23 +

4 - 20 mA

+

13 -

21

+

11

-

-

PA

SB 0715 or SB 0728

Grounded circuit - 2 channels • Barrier end-to-end resistance: 145 Ω • Allows the connections of transducers with maximum 445 Ω input impedance • Short circuit proof • Smallest IS barrier available • IS connections for: Zone 1, Group IIC Class I, II, III, Div. 1, Gr. A-G • Lowest cost solution

Hazardous Area

I

P

Safe Area

+

23 ~

~ 21

Ch 1

-

13 ~

~ 11

Ch 2

PA

I

+

P

SB-0201 or SB-0761

-

0V PA

CEAG Sicherheitstechnik GmbH

190

Safety Barrier Applications

Temperature sensors (thermocouples, RTDs) One safety barrier for all applications Thermocouple • Low resistance solution (85 Ω maximum) • Short circuit proof • Lowest cost solution for thermocouple available

Hazardous Area

• Smallest thermocouple IS barrier available • Suited for all thermocouples • IS connections for: Zone 1, Group IIC Class I, II, III, Div. 1, Gr. A-G

Safe Area 23 ~

~ 21

13 ~

~ 11

PA

SB-0201 or SB-0760 2-wire RTD • Lowest resistance solution (40 Ω maximal) • Short circuit proof • Lowest cost solution for RTD available

Hazardous Area

↑↑

6

• Smallest RTD IS barrier available • IS connections for: Zone 1, Group IIC, Class I, II, III, Div. 1, Gr. A-G

Safe Area 23 ~

~ 21

13 ~

~ 11

ϑ

PA

SB-0201 or SB-0761 3-wire RTD • Lowest resistance solution (40 Ω maximum) • Short circuit proof • Lowest temperature coefficient

Hazardous Area

↑↑

• Smallest RTD IS barrier available • IS connections for: Zone 1, Group IIC Class I, II, III, Div. 1, Gr. A-G

Safe Area 23 ~

~ 21

13 ~

~ 11

ϑ

PA

SB-0201 or SB-0761 23 ~

~ 21

13 ~

~ 11

PA

SB-0201 or SB-0761 CEAG Sicherheitstechnik GmbH

191

Safety Barrier Applications

Load cells 10 V DC supply - sense • Lowest resistance solution (155 Ω maximum) • Lowest temperature coefficient • Only two barriers required for complete system • Smallest IS barrier available • IS connections for: Zone 1, Group IIC Class I, II, III; Div. 1; Gr. A-G

Hazardous Area

Safe Area 23

21

13

11

+

Sense PA

Bridge

23

21

13

11

Signal

Signal

PA

SB 1350 or SB 0767 SB 1351 0V

12 V DC supply - without sense • Lowest resistance solution (53 Ω maximum) • Lowest temperature coefficient • Only two barriers required for complete system • Smallest IS barrier available • IS connections for: Zone 1, Group IIC Class I, II, III; Div. 1; Gr. A-G

Hazardous Area

Bridge

Safe Area 23

+

+

21

+

13

-

-

11

0V

PA 23

21

13

11

Signal

Signal

PA

SB 1250 or SB 0767 SB 1351

CEAG Sicherheitstechnik GmbH

192

Dimensions

Safety barriers

68.2 mm

9.7 mm

b

a

13 (1x) 125 mm

24.8 (2x)

6

119.5 (SB 9100)

119.5 mm

d

c

125 mm

98.2 mm

70.4 mm

Glossary a Barrier b Socket for 2 barriers c Socket for 10 barriers d Fast-on terminals e Backplane sockets f Fast-on IS terminals g Equipotential earth

e

f

g

g

CEAG Sicherheitstechnik GmbH

193