SPD Switching Power Supplies

5. SPD242403. 3ph 240W, Screw terminals, PFC and parallel function, RDY out. 24. 10. SPD482403 3ph ..... Recognized, ISA 12.12.01. (Class 1, Division 2,.
3MB taille 177 téléchargements 536 vues
CARLO GAVAZZI A u t o m a t i o n

C o m p o n e n t s

SPD Switching Power Supplies CARLO GAVAZZI presents one of the most complete ranges of DIN rail mount power supplies for the automation industry. Most features that the other manufacturers provide as options are included as standard throughout the SPD product range. The selection of the required SPD Power Supply is very simple. Choose the output voltage, the output power, and you’re done. If you require PFC, parallel connection, or an output relay, most SPD models include those features as standard. Now, the SPD power supplies are also available with a 3-phase input and biphase input. These new products, as well as the existing SPD single phase power supplies, feature very compact design, high efficiencies and overall high specs. The three phase power supplies are specifically tailored for the automation industry: the input is three phase 400~500VAC but what makes them unique is the fact that they can also be powered with 380~575VAC single phase input voltage.

High Efficiency

On single phase models the rated input voltage is automatically selected by the Power supply (120~240). On the three phase models, the input voltage can be provided by either three phases, or only two, provided the two phase voltage is between 340-575VAC.When only 2 phases are connected the maximum output power is derated by 25%. They can also be powered with DC voltage.

Adjustable Output All SPD models provide a front potentiometer to adjust the output voltage, typically within a span of +/10% of the rated output voltage.

Diagnostic Warning

User Friendly

Minimizing Energy Cost

Long Term Reliability

Long Term Reliability

Visual and Electrical Indications

The SPD Series efficiency is quite high, up to 93%.

Universal Output

Space Optimization

“Bi-phase” Input A 100W power supply is available with high-voltage single phase input. The SPDxx1002 can be powered with 380~575VAC input.

Power Factor Correction Power factor correction is standard on all units 240W and higher.

Parallel Connection All SPD power supplies rated 120W and higher, which feature the parallel feature, can be connected with one identical unit to double the power. Some models can be connected to two or three identical units.

Specifications are subject to change without notice.

All the models are equipped with double LED indication: one for output voltage and one for power ready. They are also equipped, only on 24VDC output, with a free contact relay output providing a signal of power ready.

Approvals and Warranty All SPD power supplies are approved according to UL, cUL, TÜV and safety standards: NEC Class 2 compliant and Class B for the emissions according to European standards. All models feature a Two Year Warranty.

Switching Power Supplies

SP D

510 -1 SP 8W D 130 ph -6 as 0 SP W e D 190 ph W as SP 1e ph D as 10 e 0W SP D 112 p 0W h a se SP 1D ph 24 as 0W e SP 1 D -p 30 ha 0W se SP 1 -p D ha 48 se 0W SP 1D ph 10 as 0W e SP 2 -p D ha 12 se 0W SP 3D ph 24 as 0W e SP 3D p 48 ha 0W se SP 3D ph 96 as 0W e 3ph as e

Product Line

5V 12V 15V 24V 48V : UL1310 Class 2 compliant devices

Active Current Sharing Carlo Gavazzi’s power supplies rated above 120W can be connected in parallel to provide more power. LOAD INFORMATION

+

-

The 960W version offers the additional feature of Active Current Sharing. A simple connection of two wires from one power supply to the other results in a data exchange that automatically monitors and adapts each to assure equal distribution of their respective output power.

Redundant Module The redundant module allows for the connection of two or more power supplies, thus guaranteeing the supply of DC power, even if one of the other power supplies fails. DC output

LOAD

Temperature Derating

100

Power out (%)

75

80

All switching power supplies are subject to derating, based upon the ambient temperature.

60

The operating range of the SPD Series is -25°C to +60°C without derating. Most power supplies on the market have their derating begin at +50°C.

40 20 0 -25° -20° -15° -10° 50° 55° 60° 65° 70° 75° 61° Temperature (°C) 71°

Carlo Gavazzi’s SPD Series derating starts at +61°C, and the operation is possible up to +70°C with 25% derating.

To instantly view a data sheet and specify products, visit www.GavazziOnline.com

SPD 120W SPD 12OW “N” 1-Phase

SPD 90W/100W 1-Phase

SPD 30/60W 1-Phase

SPD 5/10/18W 1-Phase

Front Adjustments and LEDs An adjustment trimmer potentiometer serves to fine tune the output voltage within a span of approximately +/- 10% of the rated voltage. With the 120W+ models, a slide switch is provided to select between Single or Parallel operation There is a red LED which indicates if the power supply’s output is out of the specified output range. Additionally, on all models except the 30W and 60W models, there is a green LED which indicates the output voltage is on.

Spring Loaded Terminals On all models up to 60W, a choice between spring loaded terminals and screw terminals are offered. Spring loaded terminals allow fast and reliable connections, saving time and money. All power supplies from 30W and above, have dual terminals, for the connection of the “+” and the “-” outputs. This feature allows for the use of smaller conductors and also simplifies parallel connections.

To instantly view a data sheet and specify products, visit www.GavazziOnline.com

SPD 100W 2-Phase SPD Redundant Module 24V - 20A

SPD 480W 1-Phase

SPD 300W 1-Phase

SPD 240W 1-Phase

Switching Power Supplies

Terminals The screw terminals of the single phase power supplies with metal enclosure (120 to 480W) can be supplied with either fixed terminals or removable connectors. The DC output terminals are doubled or tripled (depending upon output current) in order to ease the parallel connection or to connect more devices to the same power supply.

The 24VDC Output devices have 2 terminals, identified by RDY, that provide an external electrical indication of the power status. In case of failure: low output voltage or no output, the internal contact opens indicating to remote devices the abnormal situation. The 5W, 10W and 18W devices do not offer this unique feature, whereas all the others SPDs do.

To instantly view a data sheet and specify products, visit www.GavazziOnline.com

SPD 960W 3-phase

SPD 480W 3-phase

SPD 120W 3-phase

SPD 240W 3-phase

To instantly view a data sheet and specify products, visit www.GavazziOnline.com

Item Number

SPD Single Phase Description

Vin Vin Vout Iout VAC VDC VDC A

Item Number

SPD Single Phase Description

SPD121001

100W, Screw terminals, Parallel function, Plastic enclosure

SPD241001

100W, Screw terminals, Parallel function, RDY out, Plastic enclosure

SPD481001

100W, Screw terminals, Parallel function, Plastic enclosure

SPD24901 SPD24901B

SPD05051

5W, Screw terminals

5

1

SPD05051B

5W, Spring terminals

5

1

SPD12051

5W, Screw terminals

12

0.42

SPD12051B

5W, Spring terminals

12

0.42

SPD15051

5W, Screw terminals

15

0.34

SPD15051B

5W, Spring terminals

15

0.34

SPD24051

5W, Screw terminals

24

0.21

SPD24051B

5W, Spring terminals

24

0.21

SPD05101

10W, Screw terminals

5

2

SPD05101B

10W, Spring terminals

5

2

12

0.84

12

0.84

15

0.67

SPD241201

120W, Screw terminals, RDY out

12

8.4

24

4.2

48

2.1

90W, Screw terminals, PFC, Parallel function. Metal enclosure

24

3.8

90W, Removable connector, PFC, parallel function. Metal enclosure

24

3.8

SPD121201

120W, Screw terminals

12

10

SPD121201B

120W, Removable connector

12

10

24

5

SPD12101

10W, Screw terminals

SPD12101B

10W, Spring terminals

SPD15101

10W, Screw terminals

SPD15101B

10W, Spring terminals

15

0.67

SPD241201B

120W, Removable connector, RDY out

SPD24101

10W, Screw terminals

24

0.42

SPD481201

SPD24101B

10W, Spring terminals

24

0.42

SPD481201B

SPD05181

18W, Screw terminals

5

3

SPD121201N 120W, Screw terminals, PFC, Parallel function

SPD05181B

18W, Spring terminals

5

3

SPD121201BN 120W, Removable connector, PFC, Parallel function

SPD12181

18W, Screw terminals

12

1.5

SPD12181B

18W, Spring terminals

12

1.5

SPD15181

18W, Screw terminals

15

1.2

SPD15181B

18W, Spring terminals

15

1.2

90265

120370

Vin Vin Vout Iout VAC VDC VDC A

SPD241201N SPD241201BN

120375 90264

93264

24

5

120W, Screw terminals

48

2.5

120W, Removable connector

48

2.5

12

10

12

10

24

10

24

10

120W, Screw terminals, PFC, Parallel function, RDY out 120W, Removable connector, PFC, Parallel function, RDY out

210370 90264

SPD24181

18W, Screw terminals

24

0.75

SPD481201N 120W, Screw terminals, PFC, Parallel function

48

10

SPD24181B

18W, Spring terminals

24

0.75

SPD481201BN 120W, Removable connector, PFC, Parallel function

48

10

SPD05301

30W, Screw terminals

5

6

SPD05301B

30W, Spring terminals

5

6

24

10

SPD12301

30W, Screw terminals

12

2.5

SPD12301B

30W, Spring terminals

12

2.5

24

10

SPD242401

240W, Screw terminals, PFC, Parallel function, RDY out

SPD242401B

240W, Removable connector, PFC, Parallel function, RDY out

93264

SPD24301

30W, Screw terminals, RDY out

24

1.25

SPD482401 240W, Screw terminals, PFC, Parallel function

48

5

SPD24301B

30W, Spring terminals, RDY out

24

1.25

SPD482401B 240W, Removable connector, PFC, Parallel function

48

5

SPD48301

30W, Screw terminals

48

0.625

SPD48301B

30W, Spring terminals

48

0.625

24

12.5

24

12.5

48

6.25

48

6.25

24

20

85264

90375

SPD05601

60W, Screw terminals

5

10

SPD05601B

60W, Spring terminals

5

10

SPD243001

300W, Screw terminals, PFC, Parallel function, RDY out

SPD243001B

300W, Removable connector, PFC, Parallel function, RDY out

SPD12601

60W, Screw terminals

12

5

SPD483001 300W, Screw terminals, PFC, Parallel function

SPD12601B

60W, Spring terminals

12

5

SPD483001B 300W, Removable connector, PFC, Parallel function

SPD24601

60W, Screw terminals, RDY out

24

2.5

SPD24601B

60W, Spring terminals, RDY out

24

2.5

SPD244801

210375 90264

480W, Screw terminals, PFC, Parallel function, RDY out 210370

SPD48601

60W, Screw terminals

48

1.25

SPD244801B 480W, Removable connector, PFC, Parallel function

24

20

SPD48601B

60W, Spring terminals

48

1.25

SPD484801 480W, Screw terminals, PFC, Parallel function

48

10

SPD24901L

90W, Screw terminals, Plastic enclosure, RDY out

3.8

SPD484801B 480W, Removable connector, PFC, Parallel function

48

10

Item Number

SPD Bi and Three Phase Description

SPD121002 SPD241002 SPD481002

90264

120375

24

Vin Vin Vout Iout VAC VDC VDC A

2ph 100W, Screw terminals, Parallel function, Plastic enclosure 2ph 100W, Screw terminals, Parallel function, RDY out, Plastic enclosure 2ph 100W, Screw terminals, Parallel function, Plastic enclosure

12

8.4

24

4.2

48

2.1

SPD121203

3ph. 120W, Screw terminals, PFC

12

10

SPD241203

3ph 120W, Screw terminals, PFC, RDY out

24

5

24

10

48

5

24

20

48

10

24

40

24

40

48

20

SPD242403

3ph 240W, Screw terminals, PFC and parallel function, RDY out

SPD482403 3ph 240W, Screw terminals, PFC and parallel function SPD244803

3ph 480W, Screw terminals, PFC and parallel function, RDY out

SPD484803 3ph 480W, Screw terminals, PFC and parallel function SPD249603 SPD249603L SPD489603

3ph 960W, Screw terminals, PFC, Active parallel function, RDY out 3ph 960W, Screw terminals, PFC 3ph 960W, Screw terminals, PFC, Active parallel function

340575

480820

SPD24RM20

Redundant Module 24Vin 20A max.

N/A

24

24

20

SPM2RM2410

Redundant Module 24Vin 10A max.

N/A

5-24

Vin

10

Specifications are subject to change without notice.

Switching Power Supply Type SPD 120W New DIN rail mounting • • • • • • • • • • •

Installation on DIN Rail 7.5 or 15mm Short circuit protection PFC standard High efficiency Power ready output LED indicator for DC power ON LED indicator for DC low Parallel versions standard Compact dimensions Specific model for UL 1310 class 2 UL, cUL listed and TUV/CE approved

Product Description

Ordering Key

The Switching power supplies SPD series are specially designed to be used in all automation application where the installation is on a DIN rail

Model Mounting ( D = Din rail ) Output voltage Output power Input type Optional features New Type

and compact dimensions and performance are a must. Then version features PFC and parallel function as standard.

Approvals

SP D 24120 1 B N

Input type: 1= single phase

Optional Features Description

code

Standard screw terminal Plug-in connectors

Nil B

Output performances Rated output Output Voltage Power (VDC) 12 120 SPD12120 24 92 SPD2490 24 120 SPD24120 48 120 SPD48120 Model

DC on LED (VDC) DC on LED (VDC) Output Voltage Trim Range Typical Thereshold at startup Thereshold after startup Current (A) Efficiency Min. VDC Max. VDC Min. Max. Min. Max. 10 11.4 14.5 10 11.2 10 11.2 84% 3.8 22.5 24.5 17.6 19.4 17.0 19.4 85% 5 22.5 28.5 17.6 19.4 17.6 19.4 86% 2.5 45.0 55.0 37.0 43.0 37.0 43.0 87%

Output data Output voltage accuracy adjusted Line regulation Load regulation Non parallel model Parallel model Temp. coefficient

-0 +1% max (factory ± 0.5% ± 1% ± 5% ± 0.3% / °C

Transient recovery time Ripple and noise Hold up Time Vi = 115Vac Hold up time Vi = 230Vac Minimum load Parallel Operation (Not available SPD2490)

300µs 50mVpp 25ms 30ms 0% 3 units max.

Specifications are subject to change without notice. Pictures are just an example. For special features and/or custumization, please ask to our sales network.

Switching Power Supply Type SPD 120W New DIN rail mounting

Input data 115/230 autoselect

Rated input voltage Voltage range AC in, 115 AC in, 230 DC in Rated input current Rated input current SPD2490

47- 63 Hz

Frequency range Inrush current Vi= 115Vac Vi= 230Vac P.F.C.

90 - 132 Vac 186 - 264 Vac 210 - 370 Vdc 2.8 / 1.4A 2.0 / 0.8A

24A 48A 0.7

Controls and Protections T3.15/250Vac internal* 125 – 145% 102 - 106% Current limited 110 - 145% 102 - 108%

Input Fuse Overvoltage Protection Overvoltage Protection SPD2490 Output Short Circuit Rated Overload Protection Rated Overload Prot. SPD2490

Power ready (only SPD 24) Threshold at start up (contact closed) Contact rating at 60Vdc insulation

17.6 - 19.4 0.3A 500Vdc

* Not replaceable by user.

General data (@ nominal line, full load, 25°C ) -10°C to 71°C 2.5% / °C 20 to 95%RH -25°C to +85°C IP20 Free air convection

Ambient temperature Derating (>60°C to +71°C) Ambient humidity Storage Protection degree Cooling

80kHz 480.000h Metal (powder painted aluminium) 125 x 63.5 x 126 920g

Switching frequency MTBF (MIL-HDBK-217F) Case material Dimensions L x W x D Weight

Approvals and EMC 3.000Vac min 100Mohm min UL508 listed, UL60950-1 Recognised UL1310 class 2 EN60950-1

Insulation voltage I / O Insulation resistance UL / cUL SPD2490 only TUV

EN50081-1 EN55022 class B EN61000-3-2 EN61000-3-3 EN61000-6-2 EN61000-6-3 EN55024

CE

Block diagrams

L

Vo +

Fuse Line Filter

P.F.C. Circuit

Inrush Current Limiter and Rectifier

Smoothing Circuit

Switching Device

Rectifier

N Y

PWM Controller

Current Detection

Vo Single/parallel selection 1)

Opto isolation

Reference & Error Amp.

Opto isolation

Over Voltage Detection

Output Level Detection

115V/230V selected 1) Not available on SPD2490 2) for 24VDC models

Vout ADJ.

DCON (Green LED) DCLOW (Red LED) RDY 2) (Relay Contact)

Specifications are subject to change without notice. Pictures are just an example. For special features and/or costumization, please ask to our sales network.

Switching Power Supply Type SPD 120W New DIN rail mounting

Pin assignement and front controls Pin No. 1 2 3 4 5 6 7 8 9

Designation RDY (only SPD 24) RDY (only SPD 24) + + GND L N DC ON DC LO Vout ADJ. S/P

Description DC OK, relay normally open contact DC OK, relay normally open contact Positive output terminal Positive output terminal Negative output terminal Negative output terminal Ground terminal to minimise High frequency emissions Phase input ( no polarity with DC input ) Neutral input ( no polarity with DC input ) DC output ready LED DC low indicator LED Trimmer for fine output voltage adjustment Single/parallel selection switch (Not available on SPD2490)

Installation

Derating Diagram

VENTILATION / COOLING: • Normal air convection • 25mm of free space along all sides to allow good cooling SCREW CONNECTIONS: • 10-24AWG Flexible or solid cable. 8mm stripping recommended PLUG IN CONNECTORS: • 10-24AWG Flexible or solid cable. 7mm stripping recommended

Mechanical Drawings 116 (4.57)

Power out (%) 100 90 80 70 60 50 40 30 20 10 0 -10 0 5 10 Temperature (°C)

55

60

65

70

75

80

mm (inches)

6

7.0 (0.3) 6

I

I DC INPUT S

f

d e

2 JF4 E25 835 5 IND.C ONT. EQ.

B

au

ar t g eprü

f

S&E Rheinland Product Safety

p

y

v

T

appro

t

T

e

d

ar t g eprü

S&E

p

123.6 (4.87)

au

t

B

Rheinland Product Safety

y

N.C.

P

e

v appro

e

2 JF4 E25 835 5 IND.C ONT. EQ.

143 (5.63)

N.C.

P

123.6 (4.87)

S

AC INPUT 63.2 (2.49) 7

9

63.2 (2.49) 7

9

Specifications are subject to change without notice. Pictures are just an example. For special features and/or costumization, please ask to our sales network.

Switching Power Supply Type SPD 5W DIN rail mounting • • • • • • • • •

Universal AC input full range Installation on DIN rail 7.5 or 15mm Short circuit protection Overload protection High efficiency LED indicator for DC power ON LED indication for DC low Internal input filter CE, TUV approved and cULus Listed

Product Description

Ordering Key

The Switching power supplies SPD series are specially designed to be used in all automation application where the installation is on a DIN rail

Model Mounting ( D = Din rail ) Output voltage Output power Input Type Optional features

and compact dimensions and performance are a must.

SP D 12 05 1 B

Input type: 1= single phase

Approvals au

art geprü

Description

f t

B

Optional Features

Rheinland Product Safety

Spring connectors

d

p

e

T

y

e

appro

Code

v

B

Output Performances INPUT VOLTAGE

MODEL NO.

SPD05 SPD12 SPD24 SPD48

90~264 90~264 90~264 90~264

OUTPUT WATTAGE

VAC VAC VAC VAC

5 5 5 5

WATTS WATTS WATTS WATTS

OUTPUT VOLTAGE

OUTPUT CURRENT

Single Output Models + 5 VDC 1000 mA +12 VDC 420 mA +15 VDC 340 mA +24 VDC 210 mA

EFF. (min.)

EFF. (typ.)

EFF. (avg.)

67% 70% 70% 70%

83% 86% 87% 87%

69% 72% 72% 72%

Output Data Line regulation Load regulation Minimum load Turn on time (full resistive load) Transient recovery time Ripple and noise Output voltage accuracy Temperature coefficient Hold up time Vi= 115VAC Vi= 230VAC Voltage fall time (I0nom)

1

± 1% ± 2% 0 1000ms max 2ms 50mVpp ± 1% ± 0.03%/°C 30ms 130ms 150ms max

Rated continuous loading 5V Model 12V Model 15V Model 24V Model

1.0A @ 5VDC/0.85A @ 5.75VDC 0.42A @ 12VDC/0.36A @ 13.8VDC 0.34A @ 15VDC/0.28A @ 17.25VDC 0.21A @ 24VDC/0.17A @28.8VDC

Reverse voltage 5V Model 12V Model 15V Model 24V Model Capacitor load Voltage rise time at full resistive load

VDC 7.5 VDC 18 VDC 22 VDC 35 7000µF 150ms max

Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12

Switching Power Supply Type SPD 5W DIN rail mounting

Input Data Rated input voltage Voltage range AC DC Rated input current (Vi : 115VAC, Io nom) Typ. Max. Inrush current Vi= 115VAC Vi= 230VAC

100 - 240VAC 90 - 265VAC 120 - 370VDC 115mA 200mA 10A 18A

Power dissipation (Vi : 230VAC, Io nom) 5V Model 12V Model 15V Model 24V Model Frequency range Leakage current Input-Output Input-FG

2.2W 1.9W 2.1W 1.8W 47- 63Hz 0.25mA 3.5mA

Controls and Protections Overload Input fuse Output short circuit

1)

110 – 135% T2A/250VAC internal1) Hiccup mode

Over voltage protection 125 - 145% Internal surge voltage protection Varistor (IEC 61000-4-5)

Fuse not replaceable by user

General Data (@ nominal line, full load, 25°C ) Ambient temperature Derating (>61°C to +71°C) Ambient humidity Storage Protection degree Cooling Insulation voltage Input-Output Input-FG Insulation resistance I/O

-20°C to 71°C 2.5%/°C 20 ~ 95%RH -25°C to +85°C IP20 Free air convection 3.000VAC/4242VDC min 1.500VAC/2121VDC min 100M1 min (@ 500VDC)

MTBF

(Bellcore issue 6 @ 40°C, GB)

5V Model 12V Model 15V Model 24V Model

802000 Hours 805000 Hours 808000 Hours 812000 Hours Case material Plastic: PC, UL94-V0 Pollution degree 2 Altitude 4850m Dimensions LxWxD mm(inch) 90(3.60)x22.5(0.89)x114(4.49) Weight 120g

Norms and Standards Vibration resistance

Shock resistance

UL / cUL

TUV CCC

meet IEC 60068-2-6 (Mounting by rail: 10-500Hz, 2G, along X, Y, Z each Axis, 60 min for each Axis) meet IEC 60068-2-27 (15G, 11ms, 3 Axis, 6 faces, 3 times for each face) UL508 listed, UL60950-1, UL1310 Class 2 Power (only 5V, 12V w/o Class 2) Recognized, ISA 12.12.01 (Class 1, Division 2, Groups A, B, C and D) EN 60950-1, CB scheme GB4943, GB9254, GB17625.1

CE

EN 61000-6-3, EN 55022 Class B, EN 61000-3-2, EN 61000-3-3, EN 61000-6-2, EN 55024, EN 61000-4-2 Level 4, EN 61000-4-3 Level 3, EN 61000-4-4 Level 4, EN 61000-4-5 L-Level 3, L/N-FG Level 4, EN 61000-4-6 Level 3, EN 61000-4-8 Level 4, EN 61000-4-11, ENV 50204 Level 2, EN 61204-3

Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12

2

Switching Power Supply Type SPD 5W DIN rail mounting

Block Diagrams

Pin Assignement and Front Controls Pin No.

Designation

Description

1

V+

Positive output terminal

2

V-

Negative output terminal Ground this terminal to minimize high-frequency emission

3 4

N

Input terminals (neutral conductor, no polarity at DC input)

5

L

Input terminals (phase conductor, no polarity at DC input)

ON

Operation indicator LED

LO

DC LOW indicator LED

Vout ADJ.

Trimmer-potentiometer for Vout adjustment

Derating Diagram

Output voltage (%)

100

75

0 -20

61

71

Temperature

3

Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12

Switching Power Supply Type SPD 5W DIN rail mounting

Typ. Current Limited Curve v

Output voltage (%)

Hiccup Mode 100

75

t Time

Mechanical Drawings 22.50 (0.89)

2

Typ. Efficiency Curve

mm (inches)

80 75 70

22.50 (0.89)

1

2

1

V-

V+

DC Output

Vout ADJ

LO

90.00 (3.60)

90.00 (3.60)

LO ON

ON

Vout ADJ

EFFICIENCY (%)

DC Output

65 60 55 50 45 230 VAC 115 VAC

40 35 30 25 10

N L

3 4 5

3 4 5

25

50 Power out (%)

75

100

Installation Ventilation and cooling

114.00 (4.49) Connector size range Spring terminal

Screw terminal

Max. torque for terminal Input terminals Output terminals General tolerances mm(in.) 0.00 (0.00) ÷ 30.00 (1.18) 30.00 (1.18) ÷ 120.00 (4.72)

Normal convection All sides 25mm free space for cooling is recommended AWG24-14 (0.2~2mm2) flexible/solid cable, 10mm stripping at cable and recommends use copper conductors only, 60/75°C AWG26-12 (0.2~2.5mm2) flexible/solid cable, connector can withstand torque at max 0,56Nm (5 lbs-in). 4~5 mm stripping at cable and recommends use copper conductors only, 60/75°C 0.56Nm (5.0lb-in) 0.56Nm (5.0lb-in) ±0.30 (0.01) ±0.50 (0.02)

Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12

4

Switching Power Supply Type SPD 10W DIN rail mounting • • • • • • • • • •

Product Description The Switching power supplies SPD series are specially designed to be used in all automation application where the

Universal AC input full range Installation on DIN rail 7.5 or 15mm Short circuit protection Overload protection High efficiency LED indicator for DC power ON LED indication for DC low Power Ok output Internal input filter CE, TUV approved and cULus Listed

Ordering Key

installation is on a DIN rail and compact dimensions and performance are a must.

SP D 24 10 1 B

Model Mounting ( D = Din rail ) Output voltage Output power Input Type Optional features Input type: 1= single phase

Optional Features

Approvals au

art geprü

f t

B

p

e

T

d

Rheinland Product Safety

y

e

appro

v

Description

Code

Spring connectors Class I, Div 2

UL 1310

B

UL 60950-1

Output Performances MODEL NO.

SPD05 SPD12 SPD15 SPD24

INPUT VOLTAGE 90~264 90~264 90~264 90~264

VAC VAC VAC VAC

OUTPUT WATTAGE 10 10 10 10

OUTPUT VOLTAGE

Single Output Models WATTS + 5 VDC WATTS +12 VDC WATTS +15 VDC WATTS +24 VDC

OUTPUT CURRENT

EFF. (min.)

EFF. (typ.)

2000 mA 840 mA 670 mA 420 mA

71% 73% 74% 74%

73% 75% 76% 76%

Output Data Line regulation Load regulation Minimum load Turn on time (full resistive load) Vi nom, Io nom with 3500µF Transient recovery time Ripple and noise Output voltage accuracy Temperature coefficient Hold up time Vi= 115VAC Vi= 230VAC Voltage fall time (I0nom)

1

± 1% ± 2% 0 1000ms 1500ms 2ms 50mVpp + 1% ± 0.03%/°C 25ms 100ms 150ms max

Rated continuous loading 5V Model 12V Model 15V Model 24V Model Reverse voltage 5V Model 12V Model 15V Model 24V Model Capacitor load Voltage rise time at

2A @ 5VDC/1.7A @ 5.75VDC 0.84A@12VDC/[email protected] 0.67A @ 15VDC/0.58A @ 17.25VDC 0.42A @ 24VDC/0.34A @ 28.8VDC 7.5VDC 18VDC 22VDC 35VDC 3500µF 500ms

(full resistive load)

Vi nom, Io nom with 3500µF

150ms

Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12

Switching Power Supply Type SPD 10W DIN rail mounting

Input Data Rated input voltage Voltage range AC DC Rated input current (Vi : 115VAC, Io nom) Typ. Max. Inrush current Vi= 115VAC Vi= 230VAC

100 - 240VAC 90 - 264VAC 120 - 375VDC 200mA 300mA 10A 18A

Power dissipation (Vi : 230VAC, Io nom) 5V Model 12V Model 15V Model 24V Model Frequency range Leakage current Input-Output Input-FG

4.0W 3.4W 3.3W 2.8W 47- 63Hz 0.25mA 3.5mA

Controls and Protections Overload Input fuse Output short circuit 1)

110 – 145% T2A/250VAC internal1) Hiccup mode

Over voltage protection 125-145% Internal surge voltage protection Varistor (IEC 61000-4-5)

Fuse not replaceable by user

General Data (@ nominal line, full load, 25°C ) Ambient temperature Derating (>61°C to +71°C) Ambient humidity Storage Protection degree Cooling Insulation voltage Input-Output Input-FG Insulation resistance I/O

-20°C to 71°C 2.5%/°C 20 ~ 95%RH -25°C to +85°C IP20 Free air convection 3.000VAC/4242VDC min 1.500VAC/2121VDC min 100M1 min (@ 500VDC)

MTBF

(Bellcore issue 6 @ 40°C, GB)

5V Model 12V Model 15V Model 24V Model

801000 Hours 803000 Hours 805000 Hours 808000 Hours Case material Plastic: PC, UL94-V0 Pollution degree 2 Altitude 2000m Dimensions LxWxD mm(inch) 90(3.60)x22.5(0,89)x114(4.49) Weight 120g

Norms and Standards Vibration resistance

Shock resistance

UL / cUL

TUV CCC

meet IEC 60068-2-6 (Mounting by rail: 10-500Hz, 2G, along X, Y, Z each Axis, 60 min for each Axis) meet IEC 60068-2-27 (15G, 11ms, 3 Axis, 6 faces, 3 times for each face) UL508 listed, UL60950-1, UL1310 Class 2 Power Recognized, ISA 12.12.01 (Class 1, Division 2, Groups A, B, C and D) EN 60950-1, CB scheme GB4943, GB9254, GB17625.1

CE

EN 61000-6-3, EN 55022 Class B, EN 61000-3-2, EN 61000-3-3, EN 61000-6-2, EN 55024, EN 61000-4-2 Level 4, EN 61000-4-3 Level 3, EN 61000-4-4 Level 4, EN 61000-4-5 L-Level 3, L/N-FG Level 4, EN 61000-4-6 Level 3, EN 61000-4-8 Level 4, EN 61000-4-11, ENV 50204 Level 2, EN 61204-3

Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12

2

Switching Power Supply Type SPD 10W DIN rail mounting

Block Diagrams

Pin Assignement and Front Controls Pin No.

Designation

Description

1

V+

Positive output terminal

2

V-

Negative output terminal Ground terminal to minimise High frequency emissions

3 4

N

Input terminals (neutral conductor, no polarity at DC input)

5

L

Input terminals (phase conductor, no polarity at DC input)

ON

Operation indicator LED

LO

DC LOW indicator LED

Vout ADJ.

Trimmer-potentiometer for Vout adjustment

Derating Diagram

Output voltage (%)

100

75

0 -20

3

Temperature

61

71

Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12

Typ. Current Limited Curve v

Output voltage (%)

Hiccup Mode 100

75

t Time

Mechanical Drawings

22.50 (0.89)

2 1 V-

V+

2

1

V-

V+

DC Output

LO

LO

ON

ON

90.00 (3.60)

90.00 (3.60)

DC Output

Vout ADJ

Typ. Efficiency Curve

Vout ADJ

EFFICIENCY (%)

22.50 (0.89)

mm (inches)

85 80 75 70 65 60 55 50 45 40 35

230 VAC 115 VAC

10 N L

25

50 Power out (%)

75

100

N L

Installation 3 4 5 114.00 (4.49)

3 4 5

Ventilation and cooling

Connector size range Spring terminal

Screw terminal

Max. torque for terminal Input terminals Output terminals General tolerances mm(in.) 0.00 (0.00) ÷ 30.00 (1.18) 30.00 (1.18) ÷ 120.00 (4.72)

Normal convection All sides 25mm free space for cooling is recommended AWG24-14 (0.2~2mm2) flexible/solid cable, 10mm stripping at cable and recommends use copper conductors only, 60/75°C AWG26-12 (0.2~2.5mm2) flexible/solid cable, connector can withstand torque at max 0,56Nm (5 lbs-in). 4~5 mm stripping at cable and recommends use copper conductors only, 60/75°C 0.56Nm (5.0lb-in) 0.56Nm (5.0lb-in) ±0.30 (0.01) ±0.50 (0.02)

Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12

4

Switching Power Supply Type SPD 18W DIN rail mounting • • • • • • • • •

Universal AC input full range Installation on DIN rail 7.5 or 15mm Short circuit protection Overload protection High efficiency LED indicator for DC power ON LED indication for DC low Internal input filter CE, TUV approved and cULus Listed

Product Description

Ordering Key

The Switching power supplies SPD series are specially designed to be used in all automation application where the installation is on a DIN rail

Model Mounting ( D = Din rail ) Output voltage Output power Input Type Optional features

and compact dimensions and performance are a must.

SP D 24 18 1 B

Input type: 1= single phase

Approvals au

art geprü

Description

f t

B

Optional Features Code

y

Class I, Div 2

p

e

T

d

Rheinland Product Safety

e

appro

v

UL 1310

Spring connectors

B

UL 60950-1

Output performances MODEL NO.

SPD05 SPD12 SPD15 SPD24

INPUT VOLTAGE 90~264 90~264 90~264 90~264

VAC VAC VAC VAC

OUTPUT WATTAGE 15 18 18 18

OUTPUT VOLTAGE

Single Output Models WATTS + 5 VDC WATTS +12 VDC WATTS +15 VDC WATTS +24 VDC

OUTPUT CURRENT

EFF. (min.)

EFF. (typ.)

3000 mA 1500 mA 1200 mA 750 mA

73% 75% 75% 75%

75% 77% 77% 77%

Output data Line regulation Load regulation Minimum load Turn on time (full resistive load) Vi nom, Io nom with 7000µF CAP Transient recovery time Ripple and noise Output voltage accuracy Temperature coefficient Hold up time Vi= 115VAC Vi= 230VAC Voltage fall time (I0nom)

1

± 1% ± 2% 0 1000ms 1500ms 2ms 50mVpp ± 1% ± 0.03%/°C 20ms 75ms 150ms max

Rated continuous loading 5V Model 12V Model 15V Model 24V Model Reverse voltage 5V Model 12V Model 15V Model 24V Model Capacitor load Voltage rise time Vi nom Io nom Vi nom, Io nom with 7000µF CAP

3A @ 5VDC/2.6A @ 5.75VDC 1.5A @ 12VDC/1.3A @ 13.8VDC 1.2A @ 15VDC/1.0A @ 17.25VDC 0.75A @ 24VDC/0.6A @28.8VDC VDC 7.5 VDC 18 VDC 22 VDC 35 7000µF 150ms 500ms

Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12

Switching Power Supply Type SPD 18W DIN rail mounting

Input data Rated input voltage Voltage range AC DC Rated input current Vi: 115VAC, Io nom Inrush current Vi= 115VAC Vi= 230VAC

100 - 240VAC

Power dissipation 5V Model 12V Model 15V Model 24V Model Frequency range Leakage current Input-Output Input-FG (Vi : 230VAC, Io nom)

90 - 264VAC 120 - 375VDC 335-500mA 10A 18A

5.0W 4.65W 4.25W 4.45W 47- 63Hz 0.25mA 3.5mA

Controls and Protections Overload Input Fuse Overvoltage Protection 1)

110 – 140% T2A/250VAC internal1) 125 – 145%

Output Short Circuit Hiccup mode Internal surge voltage protection Varistor (IEC 61000-4-5)

Fuse not replaceable by user

General data (@ nominal line, full load, 25°C ) Ambient temperature Derating (>61°C to +71°C) Ambient humidity Storage Protection degree Cooling Insulation voltage Input-Output Input-FG Insulation resistance I/O

-20°C to 71°C 2.5%/°C 20 ~ 95%RH -25°C to +85°C IP20 Free air convection 3.000VAC/4242VDC min 1.500VAC/2121VDC min 100M1 min (@ 500VDC)

MTBF

(Bellcore issue 6 @ 40°C, GB)

5V Model 12V Model 15V Model 24V Model

795000 Hours 797000 Hours 796000 Hours 800000 Hours Case material Plastic: PC, UL94-V0 Pollution degree 2 Altitude 2000m Dimensions LxWxD mm(inch) 90(3.60)x22.5(0.89)x114(4.49) Weight 150g

Norms and Standards Vibration resistance

Shock resistance

UL / cUL

TUV CCC

meet IEC 60068-2-6 (Mounting by rail: 10-500Hz, 2G, along X, Y, Z each Axis, 60 min for each Axis) meet IEC 60068-2-27 (15G, 11ms, 3 Axis, 6 faces, 3 times for each face) UL508 listed, UL60950-1, UL1310 Class 2 Power (only 5V, 12V w/o Class 2) Recognized, ISA 12.12.01 (Class 1, Division 2, Groups A, B, C and D) EN 60950-1, CB scheme GB4943, GB9254, GB17625.1

CE

EN 61000-6-3, EN 55022 Class B, EN 61000-3-2, EN 61000-3-3, EN 61000-6-2, EN 55024, EN 61000-4-2 Level 4, EN 61000-4-3 Level 3, EN 61000-4-4 Level 4, EN 61000-4-5 L-N Level 3, L/N-FG Level 4, EN 61000-4-6 Level 3, EN 61000-4-8 Level 4, EN 61000-4-11, ENV 50204 Level 2, EN 61204-3

Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12

2

Switching Power Supply Type SPD 18W DIN rail mounting

Block diagrams

Pin Assignement and Front Controls Pin No.

Designation

Description

1

V+

Positive output terminal

2

V-

Negative output terminal Ground this terminal to minimize high-frequency emission

3 4

N

Input terminals (neutral conductor, no polarity at DC input)

5

L

Input terminals (phase conductor, no polarity at DC input)

ON

Operation indicator LED

LO

DC LOW indicator LED

Vout ADJ.

Trimmer-potentiometer for Vout adjustment

Derating Diagram

Output voltage (%)

100

75

0 -20

61

71

Temperature

3

Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12

Typ. Current Limited Curve v

Output voltage (%)

Hiccup Mode 100

50

t Time

Mechanical Drawings 22.50 (0.89)

Vout ADJ

1

85 80

V-

V+

75 70

DC Output

90.00 (3.60)

90.00 (3.60)

ON

2

LO ON

Vout ADJ

EFFICIENCY (%)

V+

DC Output LO

Typ. Efficiency Curve

22.50 (0.89)

2 1 V-

mm (inches)

65 60 55 50 45

230 VAC 115 VAC

40 35 N L

3 4 5 114.00 (4.49)

N L

3 4 5

10

25

50 Power out (%)

75

100

Installation Ventilation and cooling

Connector size range Spring terminal

Screw terminal

Max. torque for terminal Input terminals Output terminals General tolerances mm(in.) 0.00 (0.00) ÷ 30.00 (1.18) 30.00 (1.18) ÷ 120.00 (4.72)

Normal convection All sides 25mm free space for cooling is recommended AWG24-14 (0.2~2mm2) flexible/solid cable, 10mm stripping at cable and recommends use copper conductors only, 60/75°C AWG26-12 (0.2~2.5mm2) flexible/solid cable, connector can withstand torque at max 0,56Nm (5 lbs-in). 4~5 mm stripping at cable and recommends use copper conductors only, 60/75°C 0.56Nm (5.0lb-in) 0.56Nm (5.0lb-in) ±0.30 (0.01) ±0.50 (0.02)

Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12

4

Switching Power Supply Type SPD 30W DIN rail mounting • • • • • • • • •

Universal AC input full range Installation on DIN rail 7.5 or 15mm Short circuit protection Overload protection Class 2 output High efficiency LED indicator for DC power ON Power Ok output CE, TUV approved and cULus Listed

Product Description

Ordering Key

The Switching power supplies SPD series are specially designed to be used in all automation application where the

Model Mounting ( D = Din rail ) Output voltage Output power Input Type Optional features

installation is on a DIN rail and compact dimensions and performance are a must.

SP D 12 30 1 B

Input type: 1= single phase

Approvals a

Description

f t

B

Optional Features

rt gepr ua ü

Rheinland Product Safety

Class I, Div 2

Spring connectors

d

p

e

T

y

e

appro

v

UL 1310

Code B

UL 60950-1

Output performances MODEL NO.

SPD05 SPD12 SPD24 SPD48

INPUT VOLTAGE 85~264 85~264 85~264 85~264

VAC VAC VAC VAC

OUTPUT WATTAGE 30 30 30 30

OUTPUT VOLTAGE

Single Output Models WATTS + 5 VDC WATTS +12 VDC WATTS +24 VDC WATTS +48 VDC

OUTPUT CURRENT

EFF. (min.)

EFF. (typ.)

6000 mA 2500 mA 1250 mA 625 mA

77% 82% 83% 83%

79% 84% 86% 86%

Output Data Line regulation Load regulation Minimum load Turn on time (full resistive load) Vi nom, Io nom Vi nom, Io nom with 3500µF CAP Transient recovery time Ripple and noise Output voltage accuracy Temperature coefficient Hold up timeVi= 115VAC Vi= 230VAC Voltage fall time (I0nom)

1

± 0.5% ± 0.5% 0 1000ms 2000ms 2ms 50mVpp ± 1% ± 0.03%/°C 20ms 30ms 150ms max

Rated continuous loading 5V Model 12V Model 24V Model 48V Model Reverse voltage 5V Model 12V Model 24V Model 48V Model Capacitor load Voltage rise time Vi nom Io nom Vi nom, Io nom with 3500µF CAP

6A @ 5VDC/5.4A @ 5.5VDC 2.5A @ 12VDC/2.1A @ 14VDC 1.25A @ 24VDC/1.05A @ 28VDC 0.625A @ 48VDC/0.54A @ 55VDC 7.5VDC 18VDC 35VDC 63VDC 3500µF 150ms 500ms

Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12

Switching Power Supply Type SPD 30W DIN rail mounting

Input Data Rated input voltage Voltage range AC DC Rated input current (Vi : 115VAC, Io nom) Typ. Max. Inrush current Vi= 115VAC Vi= 230VAC

100 - 240VAC 85 - 264VAC 90 - 375VDC 560mA 800mA 20A 40A

Power dissipation (Vi : 230VAC, Io nom) 5V Model 12V Model 24V Model 48V Model Frequency range Leakage current Input-Output Input-FG

8.5W 5.6W 5.5W 4.9W 47- 63Hz 0.25mA 3.5mA

Controls and Protections Overload Input fuse Output short circuit Power ready output (only SPD 24) On threshold Off threshold 1)

110 – 140% T2A/250VAC internal1) Fold forward *19.2-19.4VDC )19.1-19.3VDC

Over voltage protection

VDC

Min. 5V Model 6 12V Model 15 24V Model 30 48V Model 60 Internal surge voltage protection Varistor

Max. 6.8 16.5 33 66

(IEC 61000-4-5)

Fuse not replaceable by user

General Data (@ nominal line, full load, 25°C ) Ambient temperature Derating (>61°C to +71°C) Ambient humidity Storage Protection degree Cooling Pollution degree

-40°C to 71°C 2.5%/°C 20 ~ 90%RH -40°C to +85°C IP20 Free air convection 2

MTBF

(Bellcore issue 6 @ 40°C, GB)

5V Model 12V Model 24V Model 48V Model

551000 Hours 582000 Hours 588000 Hours 609000 Hours Case material Plastic: PC, UL94-V0 Dimensions LxWxD mm(inch) 90(3.6) x 40.5(1.59) x 114(4.49) Weight 270g

Norms and Standards Vibration resistance

Shock resistance

UL / cUL

TUV

CCC

meet IEC 60068-2-6 (Mounting by rail: 10-500Hz, 2G, along X, Y, Z each Axis, 60 min for each Axis) meet IEC 60068-2-27 (15G, 11ms, 3 Axis, 6 faces, 3 times for each face) UL508 listed, UL60950-1, UL1310 Class 2 Power (only 5V, w/o Class 2) Recognized, ISA 12.12.01 (Class 1, Division 2, Groups A, B, C and D) EN 60950-1, CB scheme EN 61558-1, EN 61558-2-17 (meet EN 60204) GB4943, GB9254, GB17625.1

CE

EN 61000-6-3, EN 55022 Class B, EN 61000-3-2, EN 61000-3-3, EN 61000-6-2, EN 55024, EN 61000-4-2 Level 4, EN 61000-4-3 Level 3, EN 61000-4-4 Level 4, EN 61000-4-5 L-Level 3, L/N-FG Level 4, EN 61000-4-6 Level 3, EN 61000-4-8 Level 4, EN 61000-4-11, ENV 50204 Level 2, EN 61204-3

Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12

2

Switching Power Supply Type SPD 30W DIN rail mounting

Block Diagrams

Rdy connection RL >700ohm Rdy

L

Fuse

Vo+ Line Filter

Inrush Current Limiter and Rectifier

Switching Device

Vo-

N

-Vout

PWM Controller

a) Relay

Rdy

Rectifier

2.2k 0.5W

OptoIsolation

Reference & Error Amp.

OptoIsolation

Over Voltage Detection

5.1k 0.3w

Vout ADJ

Output Level Detection

-Vout b) 5V signal

DC ON (Green LED) RDY (Open Collector)

Pin Assignement and Front Controls Pin No.

Designation

Description

1

RDY

DC OK output for relay (not connect except 24V model)

2

+

Positive output terminal

3

+

Positive output terminal

4

-

Negative output terminal

5

-

Negative output terminal Ground this terminal to minimize high-frequency emissions

N

Input terminals (neutral conductor, no polarity at DC input)

L

Input terminals (phase conductor, no polarity at DC input)

Vout ADJ

Trimmer-potentiometer for Vout adjustment

DC ON

Operation indicator LED

Derating Diagram

Typ. Efficiency Curve 95 90 85 80 Efficiency (%)

Output voltage (%)

100

75

70 65 60 55 50

230 VAC 115 VAC

45 40

0 -25

61 Temperature (C°)

3

75

71

10

25

50

75

100

Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12

Switching Power Supply Type SPD 30W DIN rail mounting

Output Voltage (%)

Typ. Current Limited Curve

100 75 230 VAC 115 VAC

50 25 0 120

130

140

150

160

170

180

190

Output Current (%)

Mechanical Drawings

mm (inches)

Installation

40.50 (1.59)

40.50 (1.59)

543 2 1

543 2 1

- - + + Rdy

- - + + Rdy

Vout ADj

DC ON

90.00 (3.60)

90.00 (3.60)

Ventilation and cooling

N L

Vout ADj

Connector size range Spring terminal

Screw terminal

DC ON

N L

67 8

67 8 114.00 (4.49)

Max. torque for terminal Input terminals Output terminals General tolerances mm(in.) 0.00 (0.00) ÷ 30.00 (1.18) 30.00 (1.18) ÷ 120.00 (4.72)

Normal convection All sides 25mm free space for cooling is recommended AWG24-14 (0.2~2mm2) flexible/solid cable, 10mm stripping at cable and recommends use copper conductors only, 60/75°C AWG26-12 (0.2~2.5mm2) flexible/solid cable, connector can withstand torque at max 0,56Nm (5 lbs-in). 4~5 mm stripping at cable and recommends use copper conductors only, 60/75°C 0.56Nm (5.0lb-in) 0.56Nm (5.0lb-in) ±0.30 (0.01) ±0.50 (0.02)

Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12

4

Switching Power Supply Type SPD 60W DIN rail mounting • • • • • • • • •

Universal AC input full range Installation on DIN rail 7.5 or 15mm Short circuit protection Overload protection Class 2 output High efficiency LED indicator for DC power ON Power Ok output CE, TUV approved and cULus Listed

Product Description

Ordering Key

The Switching power supplies SPD series are specially designed to be used in all automation application where the installation is on a DIN rail

Model Mounting ( D = Din rail ) Output voltage Output power Input Type Optional features

and compact dimensions and performance are a must.

SP D 24 60 1 B

Input type: 1= single phase

Approvals au

art geprü

Description

f t

B

Optional Features

Rheinland Product Safety

Spring connectors

d

p

e

T

y

e

appro

Code

v

B

Output Performances Model

Rated output Voltage (VDC)

Output Power (W)

Output Current (A)

SPD05 SPD12 SPD24 SPD48

5 12 24 48

50 60 60 60

10.0 5.0 2.5 1.25

Voltage Trim Range Min. VDC 5 12 24 48

Max. VDC 5.5 14 28 55

DC ON green LED at start up DC LOW red LED after start up Min. VDC Max. VDC 3.5 4.5 9.0 10.8 18 21.6 37 43

Typical Efficiency 79% 86% 89% 89%

Output Data Line regulation Load regulation Minimum load (A) Turn on time (full resistive load) Transient recovery time Ripple and noise Output voltage accuracy Temperature coefficient Hold up time Vi= 115VAC Vi= 230VAC Voltage fall time (I0nom)

1

± 0.5% ± 0.5% 0 1000ms max 2ms 50mVpp ± 1% ± 0.03%/°C 20ms 30ms 150ms max

Rated continuous loading 5V Model 12V Model 24V Model 48V Model Reverse voltage 5V Model 12V Model 24V Model 48V Model Capacitor load Voltage rise time at full resistive load

10A @ 5VDC/9.0A @ 5.5VDC 5A @ 12VDC/4.25A @ 14VDC 2.5A @ 24VDC/2.1A @ 28VDC 1.25A @ 48VDC/1.08A @ 55VDC 7.5VDC 18VDC 35VDC 63VDC 7000µF 150ms max

Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12

Switching Power Supply Type SPD 60W DIN rail mounting

Input Data Rated input voltage Voltage range AC DC Rated input current (Vi : 115VAC, Io nom) Typ. Max. Inrush current Vi= 115VAC Vi= 230VAC

100 - 240VAC 85 - 264VAC 90 - 375VDC 1060mA 1500mA 20A 40A

Power dissipation (Vi : 230VAC, Io nom) 5V Model 12V Model 24V Model 48V Model Frequency range Leakage current Input-Output Input-FG

12.5W 9.0W 8.8W 7.8W 47- 63Hz 0.25mA 3.5mA

Controls and Protections Overload Input fuse Output short circuit Power ready output (Rdy) (only SPD 24) On threshold Off threshold 1)

110 – 150% T2A/250VAC internal1) Fold forward Vout > 19,2V ± 2% Vout < 19,1V ± 2%

Over voltage protection

VDC

Min. 5V Model 6.0 12V Model 15 24V Model 30 48V Model 60 Internal surge voltage protection Varistor

Max. 6.8 16.5 33 66

(IEC 61000-4-5)

Fuse not replaceable by user

General Data (@ nominal line, full load, 25°C ) Ambient temperature Derating (>61°C to +71°C) Ambient humidity Storage Protection degree Cooling Insulation voltage Input-Output Input-FG Insulation resistance I/O

-40°C to 71°C 2.5%/°C 20 ~ 95%RH -40°C to +85°C IP20 Free air convection 3.000VAC/4242VDC min 1.500VAC/2121VDC min 100M1 min (@ 500VDC)

MTBF

(Bellcore issue 6 @ 40°C, GB)

5V Model 12V Model 24V Model 48V Model

498000 Hours 504000 Hours 520000 Hours 531000 Hours Case material Plastic: PC, UL94-V0 Pollution degree 2 Altitude 2000m Dimensions LxWxD mm(inch) 90(3.60)x40.5(1.59)x114(4.49) Weight 340g

Norms and Standards Vibration resistance

Shock resistance

UL / cUL

TUV

CCC

meet IEC 60068-2-6 (Mounting by rail: 10-500Hz, 2G, along X, Y, Z each Axis, 60 min for each Axis) meet IEC 60068-2-27 (15G, 11ms, 3 Axis, 6 faces, 3 times for each face) UL508 listed, UL60950-1, UL1310 Class 2 Power (only 5V, 12V w/o Class 2) Recognized, ISA 12.12.01 (Class 1, Division 2, Groups A, B, C and D) EN 60950-1, CB scheme EN 61558-1, EN 61558-2-17 (meet EN 60204) GB4943, GB9254, GB17625.1

CE

EN 61000-6-3, EN 55022 Class B, EN 61000-3-2, EN 61000-3-3, EN 61000-6-2, EN 55024, EN 61000-4-2 Level 4, EN 61000-4-3 Level 3, EN 61000-4-4 Level 4, EN 61000-4-5 L-Level 3, L/N-FG Level 4, EN 61000-4-6 Level 3, EN 61000-4-8 Level 4, EN 61000-4-11, ENV 50204 Level 2, EN 61204-3

Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12

2

Switching Power Supply Type SPD 60W DIN rail mounting

Block Diagrams L

Fuse

Vo + Inrush Current Limiter and Rectifier

Line Filter

Switching Device

Rectifier

N

Vo -

PWM Controller Opto Isolation

Reference & Error Amp.

Opto Isolation

Over Voltage Detection

Vout ADj.

Y

Y Y Output Level Detection

DC ON (Green LED) RDY (Open Collector)

Pin Assignement and Front Controls Pin No.

Designation

Description

1

RDY

DC OK, output for relay (only on SPD 24)

2

+

Positive output terminal

3

+

Positive output terminal

4

-

Negative output terminal

5

-

Negative output terminal

6

GND

Ground terminal to minimise High frequency emissions

7

L

Phase input ( no polarity with DC input )

8

N

Neutral input ( no polarity with DC input )

Pot1

Vout ADJ.

Trimmer for fine output voltage adjustment

L1

DC ON

DC output ready LED

Output Rdy Wiring Diagram

Derating Diagram

RL > 700ohm Rdy

-Vout a ) Relay

Rdy

75

2.2K 0.5W 5.1K 0.3W

-Vout b ) 5V signal

3

Power out (%)

100

0 -40

61

71

Temperature (%)

Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12

Switching Power Supply Type SPD 60W DIN rail mounting

Typ. Current Limited Curve SPD 60W - 24V

mm (inches)

Typ. Efficiency Curve

EFFICIENCY (%)

Mechanical Drawings

95 90 85 80 75 70 65 60 55 50 45 40 10

230 VAC 115VAC

25

50 Power out (%)

75

100

Installation Ventilation and cooling

Connector size range Spring terminal

Screw terminal

Max. torque for terminal Input terminals Output terminals General tolerances mm(in.) 0.00 (0.00) ÷ 30.00 (1.18) 30.00 (1.18) ÷ 120.00 (4.72)

Normal convection All sides 25mm free space for cooling is recommended AWG24-14 (0.2~2mm2) flexible/solid cable, 10mm stripping at cable and recommends use copper conductors only, 60/75°C AWG26-12 (0.2~2.5mm2) flexible/solid cable, connector can withstand torque at max 0,56Nm (5 lbs-in). 4~5 mm stripping at cable and recommends use copper conductors only, 60/75°C 0.56Nm (5.0lb-in) 0.56Nm (5.0lb-in) ±0.30 (0.01) ±0.50 (0.02)

Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12

4

Alimentatori con tecnologia Switching Tipo SPD100W Montaggio da guida DIN • Installazione su guida DIN 7.5 o 15mm • Protezione da corto circuito • PFC standard • Controllo alimentazione in usciat a 24VCC • Indicatore LED per accensione DC ON • Indicatore LED di spegnimento DC LOW • Standard parallel function • Very compact dimensions • UL, cUL listed and TUV/CE approved • Class I div2 certification (in progress)

Product Description

Ordering Key

This SPD is the most compact 100W power supply on the market. Relay output for “power ready” parallel function and PFC are

Model Mounting ( D = Din rail ) Output voltage Output power Input type

included. Performances are unique with high efficiencies and the possibility of being used up to 70°C with a little derating.

Approvals au

Input type: 1= single phase

art geprü

f t

B

SP D 24 100 1

y

p

e

T

d

Rheinland Product Safety

e

appro

v

Output Performances MODEL NO.

INPUT VOLTAGE

OUTPUT WATTAGE

SPD12100

90~264 VAC

100.8 WATTS

SPD24100

90~264 VAC

SPD48100

90~264 VAC

OUTPUT VOLTAGE

OUTPUT CURRENT

EFF. (min.)

EFF. (typ.)

+12 VDC

8,4 A

82%

84%

100.8 WATTS

+24 VDC

4,2 A

84%

86%

100.8 WATTS

+48 VDC

2,1 A

86%

88%

Single Output Models

Output Data Line regulation Load regulation Non parallel model Parallel model Minimum load Turn on time (full resistive load) Vi nom, Io nom 12V/24V models with 7000µF CAP Vi nom, Io nom 48 V model with 3500µF CAP Transient recovery time Ripple and noise Output voltage accuracy Temperature coefficient Hold up timeVi= 115VAC Vi= 230VAC

1

± 1% ± 1% ± 5% 0

1000ms 2000ms 2ms 50mVpp ± 1% ± 0.03%/°C 15ms 30ms

Voltage fall time (I0nom) Rated continuous loading 12V Model 24V Model 48V Model Reverse voltage 12V Model 24V Model 48V Model Capacitor load 12V/24V models 48V model Voltage rise time Vi nom Io nom Vi nom, Io nom 12V/24V models with 7000µF CAP 48V model with 3500µF CAP

150ms max 8.4A @ 12VDC/6.9A @ 14.5VDC 4.2A @ 24VDC/3.5A @ 28.5VDC 2.1A @ 48VDC/1.8A @ 56VDC 18VDC 35VDC 63VDC 7000µF 3500µF 150ms 500ms 500 ms

Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 0811

Switching Power Supply Type SPD 100W DIN rail mounting

Input Data Rated input voltage Voltage range AC DC Rated input current (Vi : 90VAC, Io nom) Typ. Inrush current Vi= 115VAC Vi= 230VAC

100 - 240VAC

Power dissipation 12V Model 24V Model 48V Model Frequency range Leakage current Input-Output Input-FG (Vi : 230VAC, Io nom)

90- 264VAC 120 - 375VDC 2.4A 30A 60A

18.5W 15W 14W 47- 63Hz 0.25mA 3.5mA

Controls and Protections Over voltage protection

Overload 12V model 24V model 48V model Input fuse Output short circuit Power ready output threshold at start up Elettrical isolation Contact rating at 60VDC 1)

14.5V to 17.4V 30.0V to 33.0V 60.0V to 66.0V T3.15A/250VAC internal1) Fold forward

VDC

Min. 12V Model 14.5 24V Model 30 48V Model 60 Internal surge voltage protection Varistor

Max. 17.4 33 66

(IEC 61000-4-5)

≥17.6-19.4VDC 500VDC 0.3A

Fuse not replaceable by user

General Data (@ nominal line, full load, 25°C ) Ambient temperature Derating (>61°C to +71°C) Ambient humidity Storage Protection degree Cooling Pollution degree

-35°C to 71°C 2.5%/°C 22 ~ 95%RH -40°C to +85°C IP20 Free air convection 2

MTBF

(Bellcore issue 6 @ 40°C, GB)

12V Model 24V Model 48V Model

448000 Hours 456000 Hours 490000 Hours Case material Plastic: PC, UL94-V0 Dimensions LxWxD mm(inch) 90(3.6) x 54(2.13) x 114(4.49) Weight 430g

Norms and Standards Vibration resistance

Shock resistance

UL / cUL

TUV

meet IEC 60068-2-6 (Mounting by rail: 10-500Hz, 2G, along X, Y, Z each Axis, 60 min for each Axis) meet IEC 60068-2-27 (15G, 11ms, 3 Axis, 6 faces, 3 times for each face) UL508 listed, UL60950-1, UL1310 Class 2 Power Recognized EN 60950-1, CB scheme EN 61558-1, EN 61558-2-17 (meet EN 60204)

CE

EN 61000-6-3, EN 55022 Class B, EN 61000-3-2, EN 61000-3-3, EN 61000-6-2, EN 55024, EN 61000-4-2 Level 4, EN 61000-4-3 Level 3, EN 61000-4-4 Level 4, EN 61000-4-5 L-N Level 3, L/N-FG Level 4, EN 61000-4-6 Level 3, EN 61000-4-8 Level 4, EN 61000-4-11, ENV 50204 Level 2, EN 61204-3

Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 0811

2

Switching Power Supply Type SPD 100W DIN rail mounting

Block Diagrams L

Vo+

Fuse

π

Bridge Rectifier

Filter

Filter

Switching Device

Rectifier Current Detection

N

VoSingle/Paralle Select

PWM Controller OptoIsolation

Reference & Error Amp

OptoIsolation

Over Voltage Detection

Vout ADJ

Output Level Detection

DC ON (Green LED) DC LOW (Red LED) RDY (Relay Contact)

Pin Assignement and Front Controls Pin No.

Designation

Description

1

RDY

A normal open relay contact for DC ON level control Never connect

2 3, 4

V+

Positive output terminal

5, 6

V-

Negative output terminal Ground this terminal to minimize high-frequency emissions

7 8

N

Input terminals (neutral conductor, no polarity at DC input)

9

L

Input terminals (phase conductor, no polarity at DC input)

DC ON

Operation indicator LED

DC LO

DC LOW voltage indicator LED

Vout ADJ

Trimmer-potentiometer for Vout adjustment

Typ. Efficiency Curve

Derating Diagram

90

100

85

Output voltage (%)

Output voltage (%)

80 75 70 65 60 55 50

230 VAC 115 VAC

45

75

40 0

35

-35 10

25

50

75

100

61

71

Temperature (C°)

Temperature (C°)

3

Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 0811

Switching Power Supply Type SPD 100W DIN rail mounting

Output Voltage (%)

Typ. Current Limited Curve

100 75 50

230 VAC 115 VAC

25 0 110

120

130

140

150

160

170

180

190

200

210

Output Current (%)

Mechanical Drawings

mm (inches)

Installation Ventilation and cooling

Screw terminals

Normal convection All sides 25mm free space for cooling is recommended 10-24AWG flexible or solid cable 8mm stripping recommend

Max. torque for screws terminals Input terminals 1.008Nm (9.0lb-in) Output terminals 0.616Nm (5.5lb-in) Plug-in connectors 10-24AWG flexible or solid cable 7mm stripping recommend Max. torque for plug-in terminals Input terminals 0.784Nm (7.0lb-in) Output terminals 0.784Nm (7.0lb-in) Recommended circuit breaker 5A / 6A / 10A B, D characteristics Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network.0811

4

Switching Power Supply Type SPD 120W DIN rail mounting t*OTUBMMBUJPOPO%*/3BJMPSNN t4IPSUDJSDVJUQSPUFDUJPO t1'$BWBJMBCMF t)JHIFGGJDJFODZ t1PXFSSFBEZPVUQVU t-&%JOEJDBUPSGPS%$QPXFS0/ t-&%JOEJDBUPSGPS%$MPX t1BSBMMFMWFSTJPOTBWBJMBCMF t$PNQBDUEJNFOTJPOT t6- D6-MJTUFEBOE567$&BQQSPWFE

Product Description

Ordering Key

The Switching power supplies SPD series are specially designed to be used in all automation

Model Mounting (D= Din rail) Output voltage Output power Input Type Optional features

where the application installation is on a DIN rail and compact dimensions and performance are a must.

SP D 24 120 1 BFP

Input type: 1= single phase

Approvals au

art geprü

f

t

B

Optional Features

y

p

e

T

d

Rheinland Product Safety y

e

appro

v

Description

Code

Plug-in connectors

Bxx

With P.F.C.

xFx

With Parallel function

xxP

Output Performances */165 70-5"(&

.0%&-/0

065165 8"55"(&

065165 70-5"(&

065165 $633&/5

&'' NJO

&'' UZQ

4JOHMF0VUQVU.PEFMT 41%

1ø 90~264 VAC

120 WATTS

+12 VDC

10 A

85%

87%

41%

1ø 90~264 VAC

120 WATTS

+24 VDC

5A

87%

94%

Output Data Line regulation Load regulation Minimum load Turn on time (full resistive load) VI nom, Io nom VI nom, Io nom 12V model with 3500 μF CAP VI nom, Io nom 24V models with 7000 μF CAP Transient recovery time Ripple and noise Output voltage accuracy Temperature coefficient Hold up time Vi Voltage fall time (I0nom Vi nom) 1

± 1% ±1% 0A 1000ms 1500ms 1500ms 2ms 100mVpp ±1% ±0.03%/°C 20ms 150ms max

Voltage fall time (I0nom Vi nom) Rated continuous loading 12V Model 24V Model Reverse voltage 12V Model 24V Model Capacitor load Vi nom Io nom 12V model Vi nom Io nom 24V model Voltage rise time Vi nom Io nom Vi nom, Io nom 12V model with 7000μF CAP 24V model with 3500μF CAP

150ms max 10A @ 12VDC/8.2A @ 14.5VDC 5A @ 24VDC/4.2A @ 28.5VDC VDC 18 VDC 35 7000μF 3500μF 500ms 500ms 500ms

Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 20/03/14

Switching Power Supply Type SPD 120W DIN rail mounting

Input Data Rated input voltage Voltage range AC 115V selected AC 220V selected DC Rated input current (Vi:90VAC, Io nom) 5ZQ .BY Inrush current Vi= 115VAC

115/230 (auto selected) 90 - 132VAC 180 - 264VCA 210 - 315VDC 0.36A 0.5A

Power dissipation 12V Model 24V Model Frequency range Leakage current Input-Output Input-FG

20W 16W 47-63Hz 0.25mA 3.5mA

10A

Controls and Protections Overload Input fuse Output short circuit Power ready output on threshold &MFDUSJDBMJTPMBUJPO Contact rating at 60VDC

110-145% T2A/600VAC internal1) Hiccup mode ≥17.6-19.4VDC 500VDC 0.3A

Over voltage protection

VDC

.JO 12V Model 14.5 24V Model 30 Internal surge voltage protection Varistor

.BY 17.4 33

(IEC 61000-4-5)

1) Fuse not replaceable by user

General Data (@ nominal line, full load, 25°C) "NCJFOUUFNQFSBUVSF Derating (>61°C to +71°C) "NCJFOUIVNJEJUZ 4UPSBHF Protection degree Cooling Pollution degree

-35°C to +71°C 2.5%/C 20 - 90% RH -40°C to +85°C IP20 Free air convection 2

MTB (Bellcore issue 6 @ 40°C, GB) 12V Model 24V Model Case material Dimensions LxWxD mm(inch) Weight

527000 Hours 559000 Hours Metal 124(4.88) x 64.4(2.53) x 118.8(4.68) 800 g

Norms and Standards 7JCSBUJPOSFTJTUBODF

4IPDLSFTJTUBODF

6-D6-

567

2

meet IEC 60068-2-6 (Mounting by rail: 10-500Hz, 2G, along X, Y, Z each Axis, 60 min for each Axis) meet IEC 60068-2-27 (15G,11ms, 3 Axis, 6 faces, 3 times for each face) UL508 listed, UL60950-1, Recognized, ISA 12.12.01 (Class 1, Division 2, Groups A, B, C and D) EN 60950-1, CB scheme EN 61558-1, EN 61558-217 (meet EN 60204)

CCC $&

GB4943, GB9254, GB17625.1 EN 61000-6-3, EN 55022 Class B, EN 61000-3-2, EN 61000-3-3, EN 61000-6-2, EN 55024, EN 61000-4-2 Level 4, EN 61000-4-3 Level 3, EN 61000-4-4 Level 4, EN 61000-4-5 Level 3, L/N-FG Level 4, EN 61000-4-6 Level 3, EN 61000-4-8 Level 4, EN 61000-4-11, ENV 50204 Level 2, EN 61204-3

Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 20/03/2014

Switching Power Supply Type SPD 120W DIN rail mounting

Block Diagram

Vo+

L1 L2

Vo-

L3

Vo ADJ

DC ON (Green LED) DC LOW (Red LED) RDY 1 (Relay contact)

Pin Assignement and Front Controls 1JO/P

Designation

Description

1, 2

V-

Negative output terminal

3, 4

V+

Positive output terminal

5

RDY

A normal open relay contact for DC ON level control

6

RDY

(Never connect except 24V model)

7

Grounf this terminal to minimize high-frequency emissions

8

L1

Input terminals

9

L2

Input terminals

10

L3

Input terminals

%$0/

Operation indicator LED

DC LO

DC LOW voltage indicator LED

Vout ADJ

Trimmer-potentiometer for Vout adjustment

Derating Diagram

Typ. Efficiency Curve

Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 20/03/2014

3

Switching Power Supply Type SPD 120 W DIN rail mounting

Typ. Current Limited Curve

Mechanical Drawings mm (inches)

Installation Ventilation and cooling

4DSFXUFSNJOBM

.BYUPSRVFGPSUFSNJOBM Input terminal Output terminal Plug-in terminals

.BYUPSRVFGPS plug-in terminals Input terminal Output terminal

Normal convection All sides 25mm free space for cooling is recommended. 10-24AWG flexible or solid cable 8mm stripping recommend. 1.008Nm (9.0lb-in) 0.616Nm (5.5lb-in) 10-24AWG flexible or solid cable 7mm stripping recommend.

0.784Nm (7.0lb-in) 0.784Nm (7.0lb-in)

(0.27)

4

Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 20/03/2014

Switching Power Supply Type SPD 240W DIN rail mounting • • • • • • • • • • •

Universal AC input full range Installation on DIN rail 7.5 or 15mm Short circuit protection PFC as standard High efficiency Power ready output LED indicator for DC power ON LED indicator for DC low Parallel connection feature Compact dimensions UL, cUL listed and TUV/CE approved

Product Description

Ordering Key

The Switching power supplies SPD series are specially designed to be used in all automation application where the installation is on a DIN rail

Model Mounting ( D = Din rail ) Output voltage Output power Input Type Optional features

and compact dimensions and performance are a must.

Approvals au

Input type: 1= single phase

art geprü

f t

B

SP D 24 240 1 B

p

e

T

d

Rheinland Product Safety

y

e

appro

v

Optional Features Description

Class I, Div 2

Code

UL 60950-1

Plug-in connectors

B

Output performances INPUT VOLTAGE

MODEL NO.

OUTPUT WATTAGE

OUTPUT VOLTAGE

OUTPUT CURRENT

EFF. (min.)

EFF. (typ.)

Single Output Models SPD24

115~230 VAC

240 WATTS

+ 24 VDC

10 A

87%

89%

SPD48

115~230 VAC

240 WATTS

+48 VDC

5A

88%

90%

Output data Line regulation Load regulation Vi nom, Single mode Io min, Io nom parallel mode Minimum load Turn on time (full resistive load) Vi nom, Io nom Vi nom, Io nom with 7000µF CAP Transient recovery time Ripple and noise Output voltage accuracy Temperature coefficient

1

± 0.5% ±1 ±5 0 1000ms 1500ms 2ms 100mVpp ± 1% ± 0.03%/°C

Hold up timeVi= 115VAC Vi= 230VAC Voltage fall time (I0nom) Rated continuous loading 24V Model 48V Model Reverse voltage 24V Model 48V Model Capacitor load Voltage rise time Vi nom Io nom Vi nom, Io nom with 7000µF CAP

25ms 30ms 150ms max 10A @ 24VDC/8.4A @ 28.5VDC 5A @ 48VDC/4.2A @ 56VDC 35VDC 63VDC 7000µF 150ms 500ms

Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network . 18/04/12

Switching Power Supply Type SPD 240W DIN rail mounting

Input data Rated input voltage Voltage range AC in 115V AC in 230V DC in Rated input current (Vi : 115VAC, Io nom) Typ. Max. Inrush current Vi= 115VAC Vi= 230VAC

115 - 230

Power dissipation 24V Model 48V Model Frequency range Leakage current Input-Output Input-FG (Vi : 230VAC, Io nom)

90 - 132VAC 180 - 264VDC 210 - 375VDC 4.4/1.6mA 5.4/2.2mA

35W 32W 47- 63Hz 0.25mA 3.5mA

30A 60A

Controls and Protections Overload Input fuse Output short circuit Power ready output (only SPD 24) Threshold voltages

1)

120 – 140% T6.3/250VAC internal1) Fold forward

Over voltage protection 125-140% Internal surge voltage protection Varistor (IEC 61000-4-5)

17.6 - 19.4VDC

Fuse not replaceable by user

General Data (@ nominal line, full load, 25°C ) Ambient temperature Derating (>61°C to +71°C) Ambient humidity Storage Protection degree Cooling Pollution degree

-40°C to 71°C 2.5%/°C 20 ~ 90%RH -40°C to +85°C IP20 Free air convection 2

MTBF

(Bellcore issue 6 @ 40°C, GB)

24V Model 48V Model

423000 Hours 437000 Hours Metal

Case material Dimensions LxWxD mm(inch) Screw terminal type 124.5(4.9) x 83.5(3.29) x 123.6(4.87) Detachable connector type 143.5(5.65) x 83.5(3.29) x123.6(4.87) Weight 1380g

Norms and Standards Vibration resistance

Shock resistance

UL / cUL

TUV

CCC

meet IEC 60068-2-6 (Mounting by rail: 10-500Hz, 2G, along X, Y, Z each Axis, 60 min for each Axis) meet IEC 60068-2-27 (15G, 11ms, 3 Axis, 6 faces, 3 times for each face) UL508 listed, UL60950-1, recognized, ISA 12.12.01 (Class1, Division 2, Groups A, B, C and D) EN 60950-1, CB scheme EN 61558-1, EN 61558-2-17 (meet EN 60204) GB4943, GB9254, GB17625.1

CE

EN 61000-6-3, EN 55022 Class B, EN 61000-3-2 ClassD, EN 61000-3-3, EN 61000-6-2, EN 55024, EN 61000-4-2 Level 4, EN 61000-4-3 Level 3, EN 61000-4-4 Level 4, EN 61000-4-5 LLevel 3, L/N-FG Level 4, EN 61000-4-6 Level 3, EN 61000-4-8 Level 4, EN 61000-4-11, ENV 50204 Level 2, EN 61204-3

Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12

2

Switching Power Supply Type SPD 240W DIN rail mounting

Block diagrams Vo+

Fuse

L

Inruh Current Limiter, Rectifier and Auto Select 115/230VAC

Filter

Smoothing Circuit

P.F.C Circuit

Switching Device

Rectifier Current Detection

N

VoSingle/Parallel Select

PWM Controller

Y

OptoIsolation

Reference & Error Amp.

OptoIsolation

Over Voltage Detection

Vout ADj

DC ON (Green LED)

Output Level Detection

DC LOW (Red LED) RDY (Relay Contact)

Pin Assignement and Front Controls Pin No.

Designation

Description

1

RDY

A Normal open realay contact for DC ON level control (Never connect except 24V model)

2 3, 4

V+

Positive output terminal

5, 6

V-

Negative output terminal Ground this terminal to minimize high-frquency emission

7 8

L

Input terminals (phase conductor, no polarity at DC input)

9

N

Input terminals (neutral conductor, no polarity at DC input)

DC ON

Operation indicator LED

Vout ADJ

Trimmer-potentiometer for Vout adjustment

S/P

Single/Parallel select switch

Derating Diagram

Typ. Efficiency Curve

89

75

Efficiency (%)

Output voltage (%)

100

88 87 86 85 84 83 82

230 VAC 115 VAC

81 80 0 -25

61

71

10

25

50

75

100

Temperature (C°)

3

Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12

Typ. Current Limited Curve

Output Voltage (%)

100 75

230 VAC 115 VAC

50 25 0 100

110

120

130

140

150

160

Output Current (%)

Mechanical Drawings

Installation

mm (inches)

Ventilation and cooling 83.50 (3.29)

83.50 (3.29) Screw connections

Vout ADj DC LO DC ON

L N

143.50 (5.65)

Vout ADj DC LO DC ON

DC OUTPUT - - + + Rdy

124.50 (4.90)

S P

- - + + Rdy

124.50 (4.90)

S P

Normal convection All sides 25mm free space for cooling is recommended 10-24AWG flexible or solid cable 8mm stripping recommend

Max. torque for screws terminals Input terminals 1.008Nm (9.0lb-in) Output terminals 0.616Nm (5.5lb-in) 10-24AWG flexible or solid cable Plug-in connectors 7mm stripping recommend Max. torque for plug-in terminals Input terminals 0.784Nm (7.0lb-in) Output terminals 0.784Nm (7.0lb-in)

L N AC INPUT

7

9

7 116.60 (4.59)

9 7.00 (0.30)

Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12

4

Switching Power Supply Type SPD 300W DIN rail mounting • Installation on DIN Rail 7.5 or 15mm • Short circuit protection • Passive PFC • Power ready relay output on 24VDC • LED indicator for DC power ON • LED indicator for DC low • Parallel function by switch • Very compact dimensions • UL, cUL listed and TUV/CE approved • Class I division 2 certification • Selv design

Product Description This SPD is the most compact 300W power supply on the market. Relay output for “power ready” parallel function and PFC are included. Performances are unique with high

Ordering Key

efficiencies and the possibility of being used up to 70°C with a little derating. Thanks to the Class I Div 2 design is suitable for installation in potentially explosive environments.

au

art geprü

1= single phase Nil= screw terminals B= Detachable connectors

f t

B

Model Mounting (D= Din rail) Output voltage Output power Input type Connection Input type: Connection:

Approvals

SP D 24 300 1 B

y

p

e

T

d

Rheinland Product Safety

e

appro

v

Output performances MODEL NO.

INPUT VOLTAGE

OUTPUT WATTAGE

OUTPUT VOLTAGE

OUTPUT CURRENT

EFF. (min.)

EFF. (typ.)

Single Output Models SPD24300

115~230 VAC

300 WATTS

+ 24 VDC

12.5 A

87%

89%

SPD48300

115~230 VAC

300 WATTS

+ 48 VDC

6.25 A

88%

90%

Output data Line regulation Load regulation Minimum load Single mode Parallel mode Turn on time (full resistive load) Vi nom, Io nom Vi nom, Io nom with 7000µF CAP Transient recovery time Ripple and noise Output voltage accuracy Temperature coefficient

1

± 0.5% ± 1% ± 1% ± 5% 1000ms 1500ms 2ms 100mVpp ± 1% ± 0.03%/°C

Hold up time Vi115/230 VAC Voltage fall time (I0nom) Rated continuous loading 24V Model 48V Model Reverse voltage 24V Model 48V Model Capacitor load Vi nom Io nom Voltage rise time Vi nom Io nom Vi nom, Io nom 12v model with 7000µF CAP

25/30 ms 150ms max 12.5A @ 24VDC/10.5A @ 28.5VDC 6.25A @ 48VDC/5.35A @ 56VDC 35VDC 63VDC 7000µF 150ms 500ms

Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12

Switching Power Supply Type SPD 300W DIN rail mounting

Input data Rated input voltage Voltage range AC in 115V selected AC in 230V selected DC in Rated input current (Vi : 90/180VAC, Io nom) Typ. Max. Inrush current Vi= 115/230VAC

115 - 230VAC 90 - 132VAC 180 - 264VAC 210 - 375VDC 6.0A 3.0A

Power dissipation 24V Model 48V Model Frequency range Leakage current Input-Output Input-FG

42W 40W 47- 63Hz 0.25mA 3.5mA

35 - 65A

Controls and Protections Overload Input fuse Output short circuit Power ready output (only 24V model) On threshold Elettrical isolation Contact rating at 60vdc 1)

120-145% T8A/250VAC internal1) Fold forward

Over voltage protection 125 - 140% Internal surge voltage protection Varistor (IEC 61000-4-5)

≥17.6 -19.4VDC 500VDC 0.3A

Fuse not replaceable by user

General data (@ nominal line, full load, 25°C ) Ambient temperature Derating (>56°C to +71°C) Ambient humidity Storage Protection degree Cooling Pollution degree

-30°C to 71°C 2.5%/°C 20 ~ 90%RH -40°C to +85°C IP20 Free air convection 2

MTBF

(Bellcore issue 6 @ 40°C, GB)

24V Model 48V Model

415000 Hours 431000 Hours Case material Metal Dimensions LxWxD mm(inch) 124(4.88) x 83.5(3.29) x 123.6(4.87) Weight 1400g

Norms and Standards Vibration resistance

Shock resistance

UL / cUL

TUV

meet IEC 60068-2-6 (Mounting by rail: 10-500Hz, 2G, along X, Y, Z each Axis, 60 min for each Axis) meet IEC 60068-2-27 (15G, 11ms, 3 Axis, 6 faces, 3 times for each face) UL508 listed, UL60950-1, Recognized, ISA 12.12.01 (Class 1, Division 2, Groups A, B, C and D) EN 60950-1, CB scheme EN 61558-1, EN 61558-2-17 (meet EN 60204)

CE

EN 61000-6-3, EN 55022 Class B, EN 61000-3-2 Class D, EN 61000-3-3, EN 61000-6-2, EN 55024, EN 61000-4-2 Level 4, EN 61000-4-3 Level 3, EN 61000-4-4 Level 4, EN 61000-4-5 L-N Level 3, L/N-FG Level 4, EN 61000-4-6 Level 3, EN 61000-4-8 Level 4, EN 61000-4-11, ENV 50204 Level 2, EN 61204-3

Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12

2

Switching Power Supply Type SPD 300W DIN rail mounting

Block Diagrams

Fuse

L

Inrush Current Limiter, Rectifie and Auto Select 115/230VAC

Filter N

Vo+

P. F. C. Circuit

Smoothing Circuit

Switching Device

Rectifier Current Detection

Single/Parallel Select

PWM Controller

Y

Vo-

OptoIsolation

Reference & Error Amp.

OptoIsolation

Over Voltage Detection

Vout ADJ

Output Level Detection

DC ON (Green LED) DC LOW (Red LED) RDY (Relay Contact)

Pin Assignement and Front Controls Pin No.

Designation

Description

1

RDY

A normal open relay contact for DC ON level control (Never connect except 24V model)

2 3, 4

V+

Positive output terminal

5, 6

V-

Negative output terminal Ground this terminal to minimize high-frequency emissions

7 8

L

Input terminals (phase conductor, no polarity at DC input)

9

N

Input terminals (neutral conductor, no polarity at DC input)

DC ON

Operation indicator LED

DC LO

DC LOW voltage indicator LED

Vout ADj

Trimmer-potentiometer for Vout adjustment

S/P

Single / Parallel select switch

Derating Diagram

Typ. Efficiency Curve

100

89

62,5

86 85 84 83 82

230 VAC 115 VAC

81 80 0 -30

3

Efficiency (%)

Output voltage (%)

88 87

Temperature (C°)

56

71

25

50

75

100

Power out (%)

Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12

Switching Power Supply Type SPD 300W DIN rail mounting

Output voltage (%)

100

Output Voltage [%]

Typ. Current Limited Curve 100 75 50

230VAC 115VAC

25 0 110

120

130

140

150

75

160 Power Out [%]

170

180

190

200

210

230 VAC 115 VAC

50 25 0 110

100

120

130

140

150

160

Output Current (%)

Mechanical Drawings

Installation

mm (inches)

Ventilation and cooling 83.50 (3.29)

83.50 (3.29)

Rdy

124.50 (4.90)

Vout ADj.

L

DC LO DC ON

N

L

N

AC INPUT

7

9

7

116.60 (4.59)

9

143.50 (5.65)

--

DC LO DC ON

Rdy

124.50 (4.90)

++

Vout ADj.

--

S P

++

S P

Screw terminals

1

6 1

6

Max. torque for screws terminals Input terminals Output terminals Max. torque for detachable connections Input terminals Output terminals Plug-in connectors

Normal convection All sides 25mm free space for cooling is recommended 10-24AWG flexible or solid cable 8mm stripping recommend 1.008Nm (9.0lb-in) 0.616Nm (5.5lb-in)

1.008Nm (9.0lb-in) 0.616Nm (5.5lb-in) 10-24AWG flexible or solid cable 7mm stripping recommend

Max. torque for plug-in terminals Input terminals 0.784Nm (7.0lb-in) Output terminals 0.784Nm (7.0lb-in) Recommended circuit breaker 15A / 16A B, D characteristics

7.00 (0.30)

Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12

4

Switching Power Supply Type SPD 480W DIN rail mounting • • • • • • • • •

Universal AC single phase input full range Can also be used as bi-phase 400VAC Installation on DIN rail 7.5 or 15mm PFC as standard High efficiency up to 90% Power ready output Parallel connection feature Compact dimensions CE, TÜV, CCC approved and cULus listed

Product Description

Ordering Key

The Switching power supplies SPD series are specially designed to be used in all automation application where the

Model Mounting (D= Din rail) Output voltage Output power Input Type Optional features

installation is on a DIN rail and compact dimensions and performance are a must.

Approvals au

Input type: 1= single phase

art geprü

f t

B

SP D 24 480 1 B

p

e

T

d

Rheinland Product Safety

y

e

appro

v

Optional Features Description

Code

Plug-in connectors

B

Output performances MODEL NO.

INPUT VOLTAGE

OUTPUT WATTAGE

OUTPUT VOLTAGE

OUTPUT CURRENT

EFF. (min.)

EFF. (typ.)

Single Output Models

1)

SPD24

90~264 VAC

480 WATTS

+ 24 VDC

20 A

86%

89%

SPD48

90~264 VAC

480 WATTS

+48 VDC

10 A

87%

90%

When S/P switch is set to parallel, it is not possible to trim output voltage.

Output data Line regulation Load regulation Single mode Parallel mode Minimum load Turn on time (full resistive load) Vi nom, Io nom Vi nom, Io nom with 7000µF CAP Transient recovery time Ripple and noise Output voltage accuracy Temperature coefficient

1

± 0.5% ± 1% ± 5% 0 1000ms 1500ms 2ms 100mVpp + 1% ± 0.03%/°C

Hold up timeVi= 115/230VAC Voltage fall time (I0nom) Rated continuous loading 24V Model 48V Model Reverse voltage 24V Model 48V Model Capacitor load Voltage rise time Vi nom Io nom Vi nom, Io nom with 7000µF CAP

25-30ms 150ms max 20A @ 24VDC/16.8A @ 28.5VDC 10A @ 48VDC/8.5A @ 56VDC 35VDC 63VDC 7000µF 150ms 500ms

Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 11/09/12

Switching Power Supply Type SPD 480W DIN rail mounting

Input data Rated input voltage Voltage range AC DC Rated input current (Vi : 115/230VAC, Io nom) Typ. Max. Inrush current Vi= 115/230VAC Io nom

115 - 230VAC

Power dissipation 24V Model 48V Model Frequency range Leakage current Input-Output Input-FG P.F.C Vi=115/230VAC, Ionom (Vi : 400VAC, Io nom)

90 - 264VAC 120 - 375VDC 4.9/2.5A 7/3.5A

63W 560W 47- 63Hz 0.25mA 3.5mA 0.99/0.97

25/50A

Controls and Protections Overload Input fuse Output short circuit Power ready output (only SPD 24) On threshold elettrical isolation Contact Rating at 60VDC

110 – 1405% T10A/250VAC internal Fold forward

Over voltage protection 125/140% Internal surge voltage protection Varistor (IEC 61000-4-5)

≥17.6-19.4VDC 500VDC 0.3A

General data (@ nominal line, full load, 25°C ) Ambient temperature Derating (>61°C to +71°C) Ambient humidity Storage Protection degree Cooling Pollution degree

-40°C to 71°C 2.5%/°C 20 ~ 95%RH -40°C to +85°C IP20 Free air convection 2

MTBF

(Bellcore issue 6 @ 40°C, GB)

24V Model 48V Model

403000 Hours 416000 Hours Case material Metal Dimensions LxWxD mm (inch) 124.5 (4.9) x 175.5 (6.91) x 123.6 (4.87) Weight 1920g

Norms and Standards Vibration resistance

Shock resistance

UL / cUL

TUV

meet IEC 60068-2-6 (Mounting by rail: 10500Hz, 2G, along X, Y, Z each Axis, 60 min for each Axis). meet IEC 60068-2-27 (15G, 11ms, 3 Axis, 6 faces, 3 times for each face). UL508 listed, UL60950-1 Recognized, ISA 12.12.01 (Class 1, Division 2, Groups A, B, C and D). EN 60950-1, CB scheme EN 61558-1, EN 61558-2-17 (meet EN 60204).

CCC CE

GB4943, GB9254, GB17625.1. EN 61000-6-3, EN 55022 Class B, EN 61000-3-2 Class D, EN 61000-3-3, EN 61000-6-2, EN 55024, EN 61000-4-2 Level 4, EN 61000-4-3 Level 3, EN 61000-4-4 Level 4, EN 61000-4-5 L-N Level 3, L/N-FG Level 4, EN 61000-4-6 Level 3, EN 61000-4-8 Level 4, EN 61000-4-11, ENV 50204 Level 2, EN 61204-3.

Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 11/09/12

2

Switching Power Supply Type SPD 480W DIN rail mounting

Block diagrams

L1

Fuse1

L2

Fuse2

L3

Fuse3

Vo+

x Filter

Bridge Rectifier

x

π Filter

P.F.C Circuit

Switchong Device

Rectifier Current Detection

x

π Filter Vo+ Single / Parallel Select

PWM Controller

Y

OptoIsolation

Reference & Error Amp. Vout ADj

Over Voltage Detection

OptoIsolation

Continuos / Discontinuos DC ON

M.C.U

DC LOW RDY

Pin Assignement and Front Controls Pin No.

Designation

Description

1, 2

V-

Negative output teminal

3, 4

V+

Positive output terminal

5

RDY

A normal open relay contact for DC ON level control (Never connect except 24V model)

6 7

L

Input terminals (phase conductor, no polarity at DC input)

8

N

Input terminal (neutral conductor, no polarity at DC input) Ground this terminal to minimize high-frequency emissions

9 DC ON

Operation indicator LED

DC LO

DC LOW voltage indicator LED

Vout ADJ

Trimmer-potentiometer for Vout adjustment

S/P

Single / Paralle select switch

Typ. Efficiency Curve

Derating Diagram

90 100 Efficiency (%)

Output voltage (%)

85 75

75 230 VAC 115 VAC

70 65

0 -25

3

80

61 Temperature (C°)

71

10

25

50

75

100

Power Out (%)

Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 11/09/12

Switching Power Supply Type SPD 480W DIN rail mounting

Output Voltage (%)

Typ. Current Limited Curve

100 75

230 VAC 115 VAC

50 25 0 100

110

120

140

150

160

Output Current (%)

Mechanical Drawings

mm (inches)

Installation Ventilation and cooling

Connector

Input Connector

Normal convection All sides 25mm free space for cooling is recommended. Size range AWG 24-10 (0.2~4mm²) flexible/solid cable. can withstand torque at maximum 9 pound-inches.

Output Connector

Max. torque for screws terminals Input terminals Output terminals

can withstand torque at maximum 5.5 poundinches. 8 mm strip ping at cable end recom mends, use copper conductors only, 60/75°C.

0.784Nm (7.0lb-in) 0.784Nm (7.0lb-in)

Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 11/09/12

4

Switching Power Supply Type SPD 100W Bi-Phase DIN rail mounting · Installation on DIN Rail 7.5 or 15mm · Short circuit protection · Input single phase 340 to 575VAC · Passive PFC · Power ready output on 24VDC · LED indicator for DC power ON · LED indicator for DC low · Standard parallel function · Very compact dimensions · UL, cUL listed and TUV/CE approved · Class I div2 certification (in progress)

Product Description

Ordering Key

This particular SPD is the most compact 100W power supply on the market. Relay output for “power ready” parallel function and PFC are included. Performances are unique with high efficiencies

Model Mounting ( D = Din rail ) Output voltage Output power Input type

and the possibility of being used up to 70°C with a little derating. Furthermore it can be powered with 2 phases of a 3 phase grid system due to its high voltage input.

SP D 24 100 2

Input type: 2= single phase high voltage (bi-phase)

Approvals au B

art geprü

f

Rheinland P r o d u c t

S a f e t y

yp e

v appro

Output Performances Model SPD12100 SPD24100 SPD48100

Rated output Voltage (VDC) 12 24 48

Output Power (W) 100.8 100.8 100.8

Voltage Trim Range DC ON LED (VDC) Output 0.8 Io nom Threshold at startup Current (A) Min. VDC Max. VDC Min. Max. 8.4 11.4 14.5 10 11.2 4.2 22.5 28.5 17.6 19.4 2.1 47.0 56.0 37.0 43.0

DC LO LED (VDC) Threshold after startup Min. Max. 10 11.2 17.6 19.4 37.0 43.0

Typical Efficiency 86% 87% 89%

Output Data Output voltage accuracy Line regulation Load regulation Non parallel model Parallel model Temp. coefficient Ripple and noise Vi nom, Io nom, BW=20MHz Rated continuous Loading

-0 +1% max (factory adjusted) ± 1% ± 1% ± 5% ± 0.03% / °C 50mV 8.4A @ 12VDC / 6.9A @14.5VDC 4.2A @ 24VDC / 3.5A @ 28.5VDC 2.1A @ 48VDC / 1.8A @ 56VDC 150ms

Fall Time Transient recovery time 2ms Vi nom , Io= 0.5 x Inom Turn On Time Vi nom, I o nom 1.0s Vi nom, I o nom with Capacitor load 1.5s

1

Rise Time Vi nom, I o nom V i nom, Io nom with Capacitor load Capacitor Load 12V, 24V versions 48V version Reverse Voltage Immunity 12V 24V 48V Hold up Time Vi nom Io max Minimum load Vi nom Parallel Operation 0.1 Io min~0.9 Io max

150ms 500ms 7000µF 3500µF 18V 35V 63V 20ms 0% 2 units max.

Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. - 0940

Switching Power Supply Type SPD 100W Bi-phase DIN rail mounting

Input Data Rated input voltage Voltage range AC in DC in Rated input current Power dissipation 12V 24V 48V

400/500VAC

Frequency range 47 - 63Hz Internal Voltage Surge Protection Varistor

340 - 575VAC 480 - 820VDC 0.48A / 0.75A

(acc. to IEC61000-4-5)

Leakage Current Input / Output Input / FG Inrush current P.F.C.

15.0W 13.0W 10.5W

0.25mA 3.5mA 10A 0.55

Controls and Protections Input Fuse Output Short Circuit Rated Overload Protection Over voltage protection (auto recovery) 12V model 24V model 48V model

2A/600VAC internal1) current limit

Input Voltage Surge Protection Varistor Power ready (only SPD241002) Threshold at start up Min. 17.6VDC - Max.19.4VDC

115 - 135%

(contact closed)

Contact rating at 60VDC Insulation

14.5V to 17.4V 30.0V to 33.0V 60.0V to 66.0V

0.3A 500VDC

Fuse not replaceable by user

General Data (@ nominal line, full load, 25°C ) Ambient temperature Derating (>61°C to +71°C) Ambient humidity Storage Pollution degree Protection degree Cooling Switching frequency

-25°C to 71°C 2.5% / °C 20 to 95%RH -25°C to +85°C 2 IP20 Free air convection 45kHz

MTBF (Bellcore Issue 6@40°C), GB 12V model 622.000h 24V model 661.000h 48V model 672.000h Altitude during operation 3.000m Case material Plastic Dimensions L x W x D 90 x 54 x 114mm Weight 500g

Approvals and EMC Insulation voltage Input / Output Input / FG Insulation resistance

CE

EN 61000-6-3, EN 55022 Class B, EN 61000-3-2, EN 61000-3-3 EN 61000-6-2, EN 55024, EN 61000-4-2 Level 4, EN 61000-4-3 Level 3 EN 61000-4-4 Level 4, EN 61000-4-5 L-N Level 3, L / N-FG Level 4 EN 61000-4-6 Level 3, EN 61000-4-8 Level 4, EN 61000-4-11 ENV 50204 Level 2, EN 61204-3

3.000VAC / 4242VDC 1500VAC / 2121VDC 100M∧ min acc. to IEC 60068-2-27

Shock resistance

(15G, 11ms, 3 Axis, 6 Faces, 3 times for each Face)

acc. to IEC 60068-2-6

Vibration resistance

(Mounting by rail: 10-500 Hz, 2G, along X, Y, Z each Axis, 60 min for each Axis)

UL / cUL

UL 508 Listed UL 60950-1, Recognized ISA 12.12.01 (Class I, Division 2, Groups A, B, C and D in progress) EN 60950-1, CB scheme EN 61558-1, EN 61558-2-17 (acc.to EN 60204)

TUV

0940 S

ifi ti

bj t t

h

ith t

ti

Pi t

j t

l F

i lf t

d/

t

i ti

l

kt

l

t

k

2

Switching Power Supply Type SPD 100W Bi-phase DIN rail mounting

Block Diagrams

L1

Fuse1

Vo +

X

N ( L2)

Bridge Rectifier

Filter

Filter

P.F.C Circuit

Switching

Device

Rectifier

Current Detection

X

PWM Controller Y

Vo -

Opto Isolation

Reference & Error Amp.

Opto Isolation

Over Voltage Detection

Single / Parallel Select Vout ADJ.

Output Level Detection

DC ON ( Green LED) DC LOW ( Red LED) RDY 1) ( Relay Contact)

1) only for SPD241002

Pin Assignment and Front Controls Pin No.

Designation

1 2 3 4 5 6 7 8 9

RDY RDY V+ V+ VVGND N or L2 L1

NO relay contact for DC OK (only SPD241002) NO relay contact for DC OK (only SPD241002) Positive output terminal Positive output terminal Negative output terminal Negative output terminal Ground terminal to minimise High frequency emissions Neutral or phase 2 (no polarity with DC input) Phase 1 (no polarity with DC input)

L1 L2 POT1 SW1

DC ON DC LO Vout ADJ. S/P

DC output ready LED DC low indicator LED Trimmer for fine output voltage adjustment Single / Parallel select switch

Description

Typ. Current Limited Curve SPD241002 / 400VAC

SPD241002 / 500VAC

Hiccup mode

Hiccup mode

100

Output Voltage (%)

Output Voltage (%)

100

75

50

25

0

50

25

0 110

120

130

140

150

Power Out (%)

3

75

160

170

110

120

130

140

150

160

170

Power Out (%)

Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. - 0940

Switching Power Supply Type SPD 100W Bi-phase DIN rail mounting

Derating Diagram

100 90 80 70 60 50 40 30 20 10 0

95 90 85 80

Power out (%)

Efficiency [%]

Typ. Efficiency Curve

75 70 65 60 55 50 45 40 10

500 Vac 400 Vac

25

50

75

-25/ -13

100

Power Out [%]

-20/ -4

-15/ -5

-10/ 14

+55/ +60/ +65/ +70/ +75/ +80/ 131 140 149 158 167 176

Temperature °C / °F

Mechanical Drawings

mm (inches)

54.00 [2.13]

SW1

+71/ 159.8

114 [4.49]

654321

Rdy

POT1

S/P Vout A D J. DC LO DC O N

90.0 [3.6]

L2

L1

7

N

L

8

9

Installation Ventilation and cooling

Screw terminals

Normal convection All sides 25mm free space for cooling is recommended 10-24AWG flexible or solid cable 8mm stripping recommend

Max. torque for screws terminals Input terminals 1.008Nm (9.0lb-in) Output terminals 0.616Nm (5.5lb-in) Plug-in connectors 10-24AWG flexible or solid cable 7mm stripping recommend Max. torque for plug-in terminals Input terminals 0.784Nm (7.0lb-in) Output terminals 0.784Nm (7.0lb-in) Recommended circuit breaker 3A / 5A / 6A B, D characteristics

0940 - Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network.

4

Switching Power Supply Type SPD 120W 3 phases DIN rail mounting · · · · · · · ·

Universal AC 3 phases input full range Can also be used as single phase 480VAC Installation on DIN rail 7.5 or 15mm PFC as standard High efficiency up to 88% Power ready output Compact dimensions UL, cUL listed and TUV/CE

Product Description

Ordering Key

The Switching power supplies SPD series are specially designed to be used in all automation application where the

Model Mounting ( D = Din rail ) Output voltage Output power Input Type

installation is on a DIN rail and compact dimensions and performance are a must.

Approvals

Input type:

SP D 24 120 3

3 = three phase (or single phase 400/500VAC 3))

aua r t g e p r ü f B

Rheinland P r o d u c t

S a f e t y

yp e

v appro

Output performances

1)

Model

Rated output Voltage (VDC)

Output Power (W)

SPD12 SPD24

12 24

120 120

Output Voltage Trim Range Current (A)1) Min. VDC Max. VDC 10 (7.5) 11.4 14.5 5 (3.75) 22.5 28.5

DC OK Thereshold at startup (VDC) Min. Max. 10.0 11.2 17.6 19.4

DC low LED Thereshold after startup(VDC) Min. Max. 10.0 11.2 17.6 19.4

Typical Efficiency 87% 88%

When powered with three phases input; with biphase input value is in the brackets.

Output data Line regulation Load regulation Ouput Voltage accuracy Ripple and Noise

± 1% ± 1% from 0 to +1% (factory adjusted) 100mV

Temperature Coefficient Hold up time Vi = 230VAC Minimum load Parallel Operation

+0.02% / °C 20ms 0% NO

Frequency range Inrush current P.F.C. Vi= 500VAC, Io nom.

47- 63 Hz 10A 0.6

Input data Rated input voltage Voltage range AC in DC in Rated input current (380/500) 3)

1

400/500VAC 340 - 575VAC 3) 480 - 820VDC 0.5A / 0.35A

Biphase or triphase input (biphase can be: L1 L2, L2 L3 or L1 L3. Note: when used as biphase, the maximum output power is 75% of rated power.

Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. - 0841

Switching Power Supply Type SPD 120W 3 phases DIN rail mounting

Controls and Protections Input Fuse 1.0A/600VAC internal/phase4) Overvoltage ProtectionSPD12 14.5 – 17.4VDC SPD24 30 – 33VDC Output Short Circuit Current limit Continous Rated Overload Protection 115 - 135% 4)

Power ready output (only SPD 24) 17.6 - 19.4VDC Threshold voltages 0.3A Contact rating at 60VDC 500VDC insulation Overtemperature 100 - 110°C (shutdown with auto-restart when temperature is back to normal)

Not replaceable by user.

General data (@ nominal line, full load, 25°C ) Ambient temperature Derating (>61°C to +71°C) Ambient humidity Storage temperature Dimensions L x W x D Screw terminal type

-25°C to 71°C 2.5%/°C 20 - 95%RH -25°C to +85°C

Cooling MTBF (MIL-HDBK-217F) Case material Weight Protection degree

Free air convection n.a. Metal (powder painted aluminium) 800g / 28.22oz IP20

123.6 x 74.3 x 112 mm 4.87 x 2.93 x 4.41 inches

Approvals and EMC Insulation voltage I/O Insulation resistance I/O @ 500VDC UL / cUL

3.000VAC

CE

EN61000-6-3 EN55022 class B EN61000-3-2 EN61000-3-3 EN61000-6-2 EN55024

100M∧ UL508 listed, UL60950-1, Recognized EN60950-1

TUV

Block diagrams L1

Fuse1

L2

Fuse2

L3

Vo+

X Filter

Bridge Rectifier

X

Fuse3

Filter

P.F.C. Circuit

Switching Device

Rectifier Current Detection

X

VoSingle/Parallel Select

PWM

Y

Controller

OptoIsolation

Reference & Error Amp.

Opto-

OverVoltage

Isolation

Detection

Vout Adj.

Output

DCON (Green LED)

Level Detection

DCLOW (Red LED) RDY 1) (Relay Contact)

Note: 1) For 24V Model only

0841 - Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network.

2

Switching Power Supply Type SPD 120W 3 phases DIN rail mounting

Pin assignement and front controls Pin No.

Designation

1 2 3 4 5 6 7 8 9 10

V+ V+ VVGND L1 L2 L3 RDY RDY DC ON DC LO Vout ADJ.

Description Positive output terminal Positive output terminal Negative output terminal Negative output terminal Ground terminal to minimise High frequency emissions Input terminals Input terminals Input terminals A normal open relay contact for DC ON level control A normal open relay contact for DC ON level control DC output ready LED DC low indicator LED Trimmer for fine output voltage adjustment

Installation

Derating Diagram

Ventilation and cooling

Normal convection All sides 25mm free space for cooling is recommended 10-24AWG flexible or solid cable 8mm stripping recommend

Screw connections

Max. torque for screws terminals Input terminals 1.008Nm (9.0lb-in) Output terminals 0.616Nm (5.5lb-in)

Power out (%) 100 90 80 75 70 60 50 40 30 20 10 0 -25/ -13

-20/ -4

-15/ -5

-10/ 14

+50/ +55/ +60/ +65/ +70/ +75/ 122 131 140 149 158

Temperature °C / °F

+61/ 141.8

+71/ 159.8

Mechanical Drawings mm/inches 112.0 74.3

106.6

9 10 1

6.8

4

123.6

++

L1 L2 L3

5 8

3

Specifications are subject to change without notice Pictures are just an example For special features and/or customization please ask to our sales network - 0841

167

Switching Power Supply Type SPD 240W 3 phases DIN rail mounting · · · · · · · ·

Universal AC 3 phases input full range Installation on DIN rail 7.5 or 15mm PFC as standard High efficiency up to 90% Power ready output Parallel connection feature Compact dimensions UL, cUL listed and TUV/CE

Product Description

Ordering Key

The Switching power supplies SPD series are specially designed to be used in all automation application where the

Model Mounting ( D = Din rail ) Output voltage Output power Input Type

installation is on a DIN rail and compact dimensions and performance are a must.

Approvals

Input type:

SP D 24 240 3

3 = three phase (or single phase 400/500VAC 3))

aua r t g e p r ü f B

Rheinland P r o d u c t

yp

e

S a f e t y

v appro

Output performances

1) 2)

Model

Rated output Voltage (VDC)

Output Power (W)

SPD24 SPD48

24 48

240 240

Output Voltage Trim Current Range 2) 1) (A) Min. VDC Max. VDC 10 (7.5) 22.5 28.5 5 (3.75) 47.0 56.0

DC OK Thereshold at startup (VDC) Min. Max. 17.6 19.4 37.0 43.0

DC low LED Thereshold after startup(VDC) Min. Max. 17.6 19.4 37.0 43.0

Typical Efficiency 89% 90%

When powered with three phases input; with biphase input value is in the brackets. When S/P switch is set to parallel, it is not possible to trim output voltage.

Output data Line regulation Load regulation Parallel mode Non parallel mode Ouput Voltage accuracy Ripple and Noise

± 1% ± 5% ± 1% from 0 to +1% (factory adjusted) 100mV

Temperature Coefficient Hold up time Vi = 230VAC Minimum load Parallel Operation (only with S/P switch on “P” position)

+0.02% / °C 20ms 0% 2 units max.

Frequency range Inrush current P.F.C. (Vi= 500VAC, Io nom.)

47- 63 Hz 10A 0.6

Input data Rated input voltage Voltage range AC in DC in Rated input current (380/500) 3)

1

400/500VAC 340 - 575VAC 3) 480 - 820VDC 0.85A / 0.7A

Biphase or triphase input (biphase can be: L1 L2, L2 L3 or L1 L3. Note: when used as biphase, the maximum output power is 75% of rated power.

Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. - 0819

Switching Power Supply Type SPD 240W 3 phases DIN rail mounting

Controls and Protections Input Fuse 2.0A/600VAC internal/phase4) Overvoltage ProtectionSPD24 30 – 33VDC SPD48 60 – 68VDC Output Short Circuit Current limit Continous Rated Overload Protection 115 - 135% 4)

Power ready output (only SPD 24) Threshold voltages 17.6 - 19.4VDC Contact rating at 60VDC 0.3A insulation 500VDC Overtemperature 100 - 110°C (shutdown with auto-restart when temperature is back to normal)

Not replaceable by user.

General data (@ nominal line, full load, 25°C ) Ambient temperature Derating (>61°C to +71°C) Ambient humidity Storage temperature Dimensions L x W x D Screw terminal type

-25°C to 71°C 2.5%/°C 20 - 95%RH -25°C to +85°C

Cooling MTBF (MIL-HDBK-217F) Case material Weight Protection degree

Free air convection n.a. Metal (powder painted aluminium) 1.1Kg / 38,80oz IP20

123.6 x 89.0 x 110.7 mm 4.87 x 3.50 x 4.36 inches

Approvals and EMC Insulation voltage I/O Insulation resistance I/O @ 500VDC UL / cUL

CE

3.000VAC

EN61000-6-3 EN55022 class B EN61000-3-2 EN61000-3-3 EN61000-6-2 EN55024

100M& UL508 listed, UL60950-1, Recognized EN60950-1

TUV

Block diagrams L1

Fuse1

L2

Fuse2

L3

Fuse3

Vo+

X Filter

Bridge Rectifier

X

Filter

P.F.C. Circuit

Switching Device

Rectifier Current Detection

X

Vo Single/Parallel

PWM

Y

Controller

Select Opto Isolation

Reference & Error Amp.

Opto -

OverVoltage

Vout Adj.

Isolation

Detection Output

DCON (Green LED)

Level Detection

DCLOW (Red LED) RDY 1) (Relay Contact)

Note: 1) For 24V Model only

0819 - Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network.

2

Switching Power Supply Type SPD 240W 3 phases DIN rail mounting

Pin assignement and front controls Pin No.

Designation

1 2 3 4 5 6 7 8 9 10

V+ V+ VVGND L1 L2 L3 RDY RDY DC ON DC LO Vout ADJ. S/P

Description Positive output terminal Positive output terminal Negative output terminal Negative output terminal Ground terminal to minimise High frequency emissions Input terminals Input terminals Input terminals A normal open relay contact for DC ON level control A normal open relay contact for DC ON level control DC output ready LED DC low indicator LED Trimmer for fine output voltage adjustment Single / Parallel select switch

Installation

Derating Diagram

Ventilation and cooling

Normal convection All sides 25mm free space for cooling is recommended 10-24AWG flexible or solid cable 8mm stripping recommend

Screw connections Max. torque for screws terminals Input terminals Output terminals

1.008Nm (9.0lb-in) 0.616Nm (5.5lb-in)

Power out (%) 100 90 80 75 70 60 50 40 30 20 10 0 -25/ -13

-20/ -4

-15/ -5

-10/ 14

+50/ +55/ +60/ +65/ +70/ +75/ 122 131 140 149 158

Temperature °C / °F

+61/ 141.8

167

+71/ 159.8

Mechanical Drawings mm/inches 110.7 105.3

L1 L2 L3

5

3

8

++

1 89.0

112.0

123.6

9 10

Rdy

4

Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. - 0819

Switching Power Supply Type SPD 480W 3 phases DIN rail mounting · · · · · · · · ·

Universal AC 3 phases input full range Can also be used as single phase 480VAC Installation on DIN rail 7.5 or 15mm PFC as standard High efficiency up to 91% Power ready output Parallel connection feature Compact dimensions UL, cUL listed and TUV/CE

Product Description

Ordering Key

The Switching power supplies SPD series are specially designed to be used in all automation application where the

Model Mounting ( D = Din rail ) Output voltage Output power Input Type

installation is on a DIN rail and compact dimensions and performance are a must.

Approvals

Input type:

SP D 24 480 3

3 = three phase (or single phase 400/500VAC 3))

aua r t g e p r ü f B

Rheinland P r o d u c t

yp

e

S a f e t y

v appro

Output performances Model

Rated output Voltage (VDC)

Output Power (W)

SPD24 SPD48 1) 2)

Output Voltage Trim Current Range 1) 1) (A) Min. VDC Max. VDC 20 (15) 22.5 28.5 10 (7.5) 47.0 56.0

DC OK Thereshold at startup (VDC) Min. Max. 17.6 19.4 37.0 43.0

DC low LED Thereshold after startup(VDC) Min. Max. 17.6 19.4 37.0 43.0

Typical Efficiency 90% 91%

When powered with three phases input; with biphase input value is in the brackets. When S/P switch is set to parallel, it is not possible to trim output voltage.

Output data Line regulation Load regulation Non parallel mode Parallel mode Ouput Voltage accuracy Ripple and Noise

± 1% ± 1% ± 5% from 0 to +1% (factory adjusted) 100mV

Temperature Coefficient Hold up time Vi = 230Vac Minimum load Parallel Operation (only with S/P switch on “P” position)

+0.02% / °C 20ms 0% 2 units max.

Frequency range Inrush current P.F.C. Vi= 500VAC, Io nom.

47- 63 Hz 15A 0.7

Input data Rated input voltage Voltage range AC in DC in Rated input current (380/500) 3)

1

400/500VAC 340 - 575VAC 3) 480 - 820VDC 1.4A / 1.0A

Biphase or triphase input (biphase can be: L1 L2, L2 L3 or L1 L3. Note: when used as biphase, the maximum output power is 75% of rated power.

Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. - 0819

Switching Power Supply Type SPD 480W 3 phases DIN rail mounting

Controls and Protections Input Fuse 3.15A/250VAC internal/phase4) Overvoltage ProtectionSPD24 30 – 33VDC SPD48 60 – 68VDC Output Short Circuit Continous Current limit Discontinous Delay 3s shut-down, after 30s Auto-restart 115 - 135% Rated Overload Protection

Power ready output (only SPD 24) Threshold voltages 17.6 - 19.4VDC Contact rating at 60Vdc 0.3A insulation 500VDC Overtemperature 100 - 110°C (shutdown with auto-restart when temperature is back to normal)

Not replaceable by user.

General data (@ nominal line, full load, 25°C ) Ambient temperature Derating (>61°C to +71°C) Ambient humidity Storage Dimensions L x W x D Screw terminal type

-25°C to 71°C 2.5%/°C 20 - 95%RH -25°C to +95°C

Cooling MTBF (MIL-HDBK-217F) Case material Weight Protection degree

Free air convection n.a. Metal (powder painted aluminium) 1750g / 61.73oz IP20

124 x 150 x 118 mm 1.88 x 5.91 x 4.65 inches

Approvals and EMC Insulation voltage I/O Insulation resistance I/O @ 500VDC UL / cUL

CE

3.000VAC

EN61000-6-3 EN55022 class B EN61000-3-2 EN61000-3-3 EN61000-6-2 EN55024

100M& UL508 listed, UL60950-1, Recognized EN60950-1

TUV

Block diagrams

L1

Fuse1

L2

Fuse2

L3

Fuse3

Vo +

X Filt e r

Br idge Rectifier

X

Filt e r

P.F.C Circuit

Sw it ching D e v i ce

Rect ifier

Filter

C ur r ent

X

Vo -

D etection PW M C o nt r o lle r

Y

Si n gl e / Par al l e l O pto I so l at i o n

Se l e ct

Refer ence & Er r or A m p.

O pto -

V o u t A D J.

O ver Voltage D etection

I so l at i o n

C ontinuous / D iscontinuous M .C .U

0819 S

ifi ti

bj t t

h

ith t

ti

Pi t

j t

l F

i lf t

d/

t

i ti

DC ON D C LO W RD Y

l

kt

l

t

k

2

Switching Power Supply Type SPD 480W 3 phases DIN rail mounting

Pin assignement and front controls Pin No.

Designation

1 2 3 4 5 6 7 8 9 10

+ + GND L1 L2 L3 RDY RDY DC ON DC LO Vout ADJ. S/P C/D

Description Positive output terminal Positive output terminal Negative output terminal Negative output terminal Ground terminal to minimise High frequency emissions Input terminals Input terminals Input terminals A normal open relay contact for DC ON level control A normal open relay contact for DC ON level control DC output ready LED DC low indicator LED Trimmer for fine output voltage adjustment Single / parallel selection switch Continous / Discontinous

Installation

Derating Diagram

Ventilation and cooling

Normal convection All sides 25mm free space for cooling is recommended 10-24AWG flexible or solid cable 8mm stripping recommend

Screw connections Max. torque for screws terminals Input terminals Output terminals

1.008Nm (9.0lb-in) 0.616Nm (5.5lb-in)

Power out (%) 100 90 80 75 70 60 50 40 30 20 10 0 -25/ -13

-20/ -4

-15/ -5

-10/ 14

+50/ +55/ +60/ +65/ +70/ +75/ 122 131 140 149 158

Temperature °C / °F

+61/ 141.8

167

+71/ 159.8

Mechanical Drawings mm/inches 10 9 P 111.3 (4.38) 150 (5.91)

6.9 (0.27)

RDY

106.6 (4.2)

S/P

RDY

123.6 (4.87)

C/D

++

L1 L2 L3

5

3

8

1

4

Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. - 0819

Switching Power Supply Type SPD 960W 3 phases DIN rail mounting · · · · · · · · ·

Universal AC 3 phases input full range Can also be used as bi-phase 960VAC Installation on DIN rail 7.5 or 15mm PFC as standard High efficiency up to 93% Power ready output Parallel connection feature (except “L” version) Compact dimensions UL, cUL listed and TUV/CE

Product Description

Ordering Key

The Switching power supplies SPD XX9603 series are suitable for those applications where high DC power is required. Besides

Model Mounting (D= Din rail) Output voltage Output power Input Type Option Input type:

the PFC as standard, it also features the parallel connection with active current sharing on the high end versions.

Approvals

Option:

aua r t g e p r ü f B

SP D 24 960 3 L

3 = three phase (or single phase 400/500VAC 3)) Nil = standard version L = without active current sharing feature

Rheinland P r o d u c t

S a f e t y

yp e

v appro

Output performances MODEL NO.

INPUT VOLTAGE

OUTPUT WATTAGE

SPD24

3ø 340~575 VAC

960 WATTS

SPD24...L

3ø 340~575 VAC

SPD48

3ø 340~575 VAC

OUTPUT VOLTAGE

OUTPUT CURRENT

EFF. (min.)

EFF. (typ.)

+ 24 VDC

40 A

90%

92%

960 WATTS

+ 24 VDC

40 A

90%

92%

960 WATTS

+ 48 VDC

20 A

91%

93%

Single Output Models

Output data Line regulation Load regulation Single mode Parallel mode Minimum load Turn on time (full resistive load) Vi nom, Io nom Vi nom, Io nom with 7000µF CAP Transient recovery time Ripple and noise Output voltage accuracy Temperature coefficient

1

± 0.5% ± 1% ± 5% 0 1000ms 1500ms 2ms 80mVpp + 1% ± 0.03%/°C

Hold up time Vi nom ,Io nom Voltage fall time (I0nom) Rated continuous loading 24V Model 48V Model Reverse voltage 24V Model 48V Model Capacitor load Voltage rise time Vi nom Io nom Vi nom, Io nom with 7000µF CAP

15ms 150ms max 40A @ 24VDC/33.8A @ 28.5VDC 20A @ 48VDC/17A @ 56VDC 35VDC 63VDC 7000µF 150ms 500ms

Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 0811

Switching Power Supply Type SPD 960W 3 phases DIN rail mounting

Input data Rated input voltage Voltage range AC DC Rated input current (Vi: 340VAC, Io nom) Typ. Inrush current Vi nom, Io nom 24V/48V models Cold start 24L model

400 - 500VAC 340 - 575VAC 480 - 820VDC 2.4A

Power dissipation Vi: 400 VAC, Io nom 24V Model 48V Model Frequency range Leakage current Input-Output Input-FG

98W 55W 47- 63Hz 0.25mA 3.5mA

30 - 35A 50 - 60A

Controls and Protections Overload Input fuse Output short circuit Power ready output (only 24V model) On threshold Elettrical isolation

120-140% T5A/500VAC internal/phase Hiccup mode ε17.6 -19.4VDC 500VDC

Contact rating at 60vdc Over voltage protection

0.3A

VDC Min. Max. 24V Model 30 33 48V Model 60 68 Internal surge voltage protection Varistor (IEC 61000-4-5)

General data (@ nominal line, full load, 25°C ) Ambient temperature Derating (>61°C to +71°C) Ambient humidity Storage Protection degree Cooling Pollution degree

-40°C to 71°C 3.5%/°C 20 ~ 90%RH -40°C to +85°C IP20 Free air convection 2

MTBF

(Bellcore issue 6 @ 40°C, GB)

24V Model 24L Model 48V Model

352000 Hours 381000 Hours 390000 Metal Case material Dimensions LxWxD mm(inch) 126.2(4.97)x275.8(10.86)x118.8(4.68) Weight 3400g

Norms and Standards Vibration resistance

Shock resistance

UL / cUL

TUV

meet IEC 60068-2-6 (Mounting by rail: 10-500Hz, 2G, along X, Y, Z each Axis, 60 min for each Axis) meet IEC 60068-2-27 (15G, 11ms, 3 Axis, 6 faces, 3 times for each face) UL508 listed, UL60950-1, Recognized, ISA 12.12.01 (Class 1, Division 2, Groups A, B, C and D) EN 60950-1, CB scheme EN 61558-1, EN 61558-2-17 (meet EN 60204)

CCC CE

Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 0811

GB4943, GB9254, GB17625.1 EN 61000-6-3, EN 55022 Class B, EN 61000-3-2, EN 61000-3-3, EN 61000-6-2, EN 55024, EN 61000-4-2 Level 4, EN 61000-4-3 Level 3, EN 61000-4-4 Level 4, EN 61000-4-5 L-N Level 3, L/N-FG Level 4, EN 61000-4-6 Level 3, EN 61000-4-8 Level 4, EN 61000-4-11, ENV 50204 Level 2, EN 61204-3

2

Switching Power Supply Type SPD 960W 3 phases DIN rail mounting

Block diagrams

L1

Fuse 1

L2

Fuse 2

Filter

L3

Vo+

Filter

Bridge Rectifier

P.F.C Circuit

Filter

Switching Device

Rectifier

Fuse 3

PWm Controller

Current Detection

Vo-

Reference & Error Amp. Vout ADj.

Bias Power

Parallel Controller

Output Level Detection

Pin Assignement and Front Controls Pin No.

Designation

Description

1, 2

V-

Negative output teminal

3, 4

V+

Positive output terminal

5

G

Parallel GND PIN for current share

6

P

Parallel PIN for current share

7

RDY

A normal open relay contact for DC ON level control

8

(Never connect except 24V model)

9

L3

Input terminals

10

L2

Input terminals

11

L1

Input terminal

12

3

Ground this terminal to minimize high-frequency emission DC ON

Operation indicator LED

DC LO

DC LOW voltage indicator LED

Vout ADj

Trimmer-potentiometer for Vout adjustment

Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 0811

Parallel

DC ON (Green LED) DC LOW (Red LED) RDy 1) (Relay Contact)

Parallel Connection

Derating Diagram

Typ. Efficiency Curve 95

100

EFFICIENCY (%)

Power out (%)

90 65

85 80 75 70

0 -40

61

71

10

25

Output Current (%)

50 Power out (%)

75

100

Typ. Current Limited Curve 125

Output Voltage (%)

100

75

50

Hiccup mode

entering hiccup mode after 5~10 sec of output overload

Continuos

25

0 20

40

60

80

100 120 135 Output Current (%)

150

170

190

Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 0811

4

Mechanical Drawings mm/inches

Installation Ventilation and cooling

275.80 (10.86)

126.20 (4.97)

Conductors sections From Pin1 to Pin4

L1 L2 L3

DC DC LO ON

Rdy

Vout ADj

12 11 10 9

87654

32

From Pin9 to Pin12

10-24AWG (0.2-4mm2) flexible or solid cable 8mm stripping recommend 6-20AWG (0.5-10mm2) flexible or solid cable 8mm stripping recommend 10-24AWG (0.2-4mm2) flexible or solid cable 8mm stripping recommend

Max. torque for screws terminals From Pin1 to Pin4 1.008Nm (9.0lb-in) From Pin5 to Pin8 1.763Nm (15.6lb-in) From Pin9 to Pin12 0.616Nm (5.5lb-in)

Vout ADj

111.90 (4.41)

1

From Pin5 to Pin8

Normal convection All sides 25mm free space for cooling is recommended

6.90 (0.27)

106.50 (4.20)

6