CARLO GAVAZZI A u t o m a t i o n
C o m p o n e n t s
SPD Switching Power Supplies CARLO GAVAZZI presents one of the most complete ranges of DIN rail mount power supplies for the automation industry. Most features that the other manufacturers provide as options are included as standard throughout the SPD product range. The selection of the required SPD Power Supply is very simple. Choose the output voltage, the output power, and you’re done. If you require PFC, parallel connection, or an output relay, most SPD models include those features as standard. Now, the SPD power supplies are also available with a 3-phase input and biphase input. These new products, as well as the existing SPD single phase power supplies, feature very compact design, high efficiencies and overall high specs. The three phase power supplies are specifically tailored for the automation industry: the input is three phase 400~500VAC but what makes them unique is the fact that they can also be powered with 380~575VAC single phase input voltage.
High Efficiency
On single phase models the rated input voltage is automatically selected by the Power supply (120~240). On the three phase models, the input voltage can be provided by either three phases, or only two, provided the two phase voltage is between 340-575VAC.When only 2 phases are connected the maximum output power is derated by 25%. They can also be powered with DC voltage.
Adjustable Output All SPD models provide a front potentiometer to adjust the output voltage, typically within a span of +/10% of the rated output voltage.
Diagnostic Warning
User Friendly
Minimizing Energy Cost
Long Term Reliability
Long Term Reliability
Visual and Electrical Indications
The SPD Series efficiency is quite high, up to 93%.
Universal Output
Space Optimization
“Bi-phase” Input A 100W power supply is available with high-voltage single phase input. The SPDxx1002 can be powered with 380~575VAC input.
Power Factor Correction Power factor correction is standard on all units 240W and higher.
Parallel Connection All SPD power supplies rated 120W and higher, which feature the parallel feature, can be connected with one identical unit to double the power. Some models can be connected to two or three identical units.
Specifications are subject to change without notice.
All the models are equipped with double LED indication: one for output voltage and one for power ready. They are also equipped, only on 24VDC output, with a free contact relay output providing a signal of power ready.
Approvals and Warranty All SPD power supplies are approved according to UL, cUL, TÜV and safety standards: NEC Class 2 compliant and Class B for the emissions according to European standards. All models feature a Two Year Warranty.
Switching Power Supplies
SP D
510 -1 SP 8W D 130 ph -6 as 0 SP W e D 190 ph W as SP 1e ph D as 10 e 0W SP D 112 p 0W h a se SP 1D ph 24 as 0W e SP 1 D -p 30 ha 0W se SP 1 -p D ha 48 se 0W SP 1D ph 10 as 0W e SP 2 -p D ha 12 se 0W SP 3D ph 24 as 0W e SP 3D p 48 ha 0W se SP 3D ph 96 as 0W e 3ph as e
Product Line
5V 12V 15V 24V 48V : UL1310 Class 2 compliant devices
Active Current Sharing Carlo Gavazzi’s power supplies rated above 120W can be connected in parallel to provide more power. LOAD INFORMATION
+
-
The 960W version offers the additional feature of Active Current Sharing. A simple connection of two wires from one power supply to the other results in a data exchange that automatically monitors and adapts each to assure equal distribution of their respective output power.
Redundant Module The redundant module allows for the connection of two or more power supplies, thus guaranteeing the supply of DC power, even if one of the other power supplies fails. DC output
LOAD
Temperature Derating
100
Power out (%)
75
80
All switching power supplies are subject to derating, based upon the ambient temperature.
60
The operating range of the SPD Series is -25°C to +60°C without derating. Most power supplies on the market have their derating begin at +50°C.
40 20 0 -25° -20° -15° -10° 50° 55° 60° 65° 70° 75° 61° Temperature (°C) 71°
Carlo Gavazzi’s SPD Series derating starts at +61°C, and the operation is possible up to +70°C with 25% derating.
To instantly view a data sheet and specify products, visit www.GavazziOnline.com
SPD 120W SPD 12OW “N” 1-Phase
SPD 90W/100W 1-Phase
SPD 30/60W 1-Phase
SPD 5/10/18W 1-Phase
Front Adjustments and LEDs An adjustment trimmer potentiometer serves to fine tune the output voltage within a span of approximately +/- 10% of the rated voltage. With the 120W+ models, a slide switch is provided to select between Single or Parallel operation There is a red LED which indicates if the power supply’s output is out of the specified output range. Additionally, on all models except the 30W and 60W models, there is a green LED which indicates the output voltage is on.
Spring Loaded Terminals On all models up to 60W, a choice between spring loaded terminals and screw terminals are offered. Spring loaded terminals allow fast and reliable connections, saving time and money. All power supplies from 30W and above, have dual terminals, for the connection of the “+” and the “-” outputs. This feature allows for the use of smaller conductors and also simplifies parallel connections.
To instantly view a data sheet and specify products, visit www.GavazziOnline.com
SPD 100W 2-Phase SPD Redundant Module 24V - 20A
SPD 480W 1-Phase
SPD 300W 1-Phase
SPD 240W 1-Phase
Switching Power Supplies
Terminals The screw terminals of the single phase power supplies with metal enclosure (120 to 480W) can be supplied with either fixed terminals or removable connectors. The DC output terminals are doubled or tripled (depending upon output current) in order to ease the parallel connection or to connect more devices to the same power supply.
The 24VDC Output devices have 2 terminals, identified by RDY, that provide an external electrical indication of the power status. In case of failure: low output voltage or no output, the internal contact opens indicating to remote devices the abnormal situation. The 5W, 10W and 18W devices do not offer this unique feature, whereas all the others SPDs do.
To instantly view a data sheet and specify products, visit www.GavazziOnline.com
SPD 960W 3-phase
SPD 480W 3-phase
SPD 120W 3-phase
SPD 240W 3-phase
To instantly view a data sheet and specify products, visit www.GavazziOnline.com
Item Number
SPD Single Phase Description
Vin Vin Vout Iout VAC VDC VDC A
Item Number
SPD Single Phase Description
SPD121001
100W, Screw terminals, Parallel function, Plastic enclosure
SPD241001
100W, Screw terminals, Parallel function, RDY out, Plastic enclosure
SPD481001
100W, Screw terminals, Parallel function, Plastic enclosure
SPD24901 SPD24901B
SPD05051
5W, Screw terminals
5
1
SPD05051B
5W, Spring terminals
5
1
SPD12051
5W, Screw terminals
12
0.42
SPD12051B
5W, Spring terminals
12
0.42
SPD15051
5W, Screw terminals
15
0.34
SPD15051B
5W, Spring terminals
15
0.34
SPD24051
5W, Screw terminals
24
0.21
SPD24051B
5W, Spring terminals
24
0.21
SPD05101
10W, Screw terminals
5
2
SPD05101B
10W, Spring terminals
5
2
12
0.84
12
0.84
15
0.67
SPD241201
120W, Screw terminals, RDY out
12
8.4
24
4.2
48
2.1
90W, Screw terminals, PFC, Parallel function. Metal enclosure
24
3.8
90W, Removable connector, PFC, parallel function. Metal enclosure
24
3.8
SPD121201
120W, Screw terminals
12
10
SPD121201B
120W, Removable connector
12
10
24
5
SPD12101
10W, Screw terminals
SPD12101B
10W, Spring terminals
SPD15101
10W, Screw terminals
SPD15101B
10W, Spring terminals
15
0.67
SPD241201B
120W, Removable connector, RDY out
SPD24101
10W, Screw terminals
24
0.42
SPD481201
SPD24101B
10W, Spring terminals
24
0.42
SPD481201B
SPD05181
18W, Screw terminals
5
3
SPD121201N 120W, Screw terminals, PFC, Parallel function
SPD05181B
18W, Spring terminals
5
3
SPD121201BN 120W, Removable connector, PFC, Parallel function
SPD12181
18W, Screw terminals
12
1.5
SPD12181B
18W, Spring terminals
12
1.5
SPD15181
18W, Screw terminals
15
1.2
SPD15181B
18W, Spring terminals
15
1.2
90265
120370
Vin Vin Vout Iout VAC VDC VDC A
SPD241201N SPD241201BN
120375 90264
93264
24
5
120W, Screw terminals
48
2.5
120W, Removable connector
48
2.5
12
10
12
10
24
10
24
10
120W, Screw terminals, PFC, Parallel function, RDY out 120W, Removable connector, PFC, Parallel function, RDY out
210370 90264
SPD24181
18W, Screw terminals
24
0.75
SPD481201N 120W, Screw terminals, PFC, Parallel function
48
10
SPD24181B
18W, Spring terminals
24
0.75
SPD481201BN 120W, Removable connector, PFC, Parallel function
48
10
SPD05301
30W, Screw terminals
5
6
SPD05301B
30W, Spring terminals
5
6
24
10
SPD12301
30W, Screw terminals
12
2.5
SPD12301B
30W, Spring terminals
12
2.5
24
10
SPD242401
240W, Screw terminals, PFC, Parallel function, RDY out
SPD242401B
240W, Removable connector, PFC, Parallel function, RDY out
93264
SPD24301
30W, Screw terminals, RDY out
24
1.25
SPD482401 240W, Screw terminals, PFC, Parallel function
48
5
SPD24301B
30W, Spring terminals, RDY out
24
1.25
SPD482401B 240W, Removable connector, PFC, Parallel function
48
5
SPD48301
30W, Screw terminals
48
0.625
SPD48301B
30W, Spring terminals
48
0.625
24
12.5
24
12.5
48
6.25
48
6.25
24
20
85264
90375
SPD05601
60W, Screw terminals
5
10
SPD05601B
60W, Spring terminals
5
10
SPD243001
300W, Screw terminals, PFC, Parallel function, RDY out
SPD243001B
300W, Removable connector, PFC, Parallel function, RDY out
SPD12601
60W, Screw terminals
12
5
SPD483001 300W, Screw terminals, PFC, Parallel function
SPD12601B
60W, Spring terminals
12
5
SPD483001B 300W, Removable connector, PFC, Parallel function
SPD24601
60W, Screw terminals, RDY out
24
2.5
SPD24601B
60W, Spring terminals, RDY out
24
2.5
SPD244801
210375 90264
480W, Screw terminals, PFC, Parallel function, RDY out 210370
SPD48601
60W, Screw terminals
48
1.25
SPD244801B 480W, Removable connector, PFC, Parallel function
24
20
SPD48601B
60W, Spring terminals
48
1.25
SPD484801 480W, Screw terminals, PFC, Parallel function
48
10
SPD24901L
90W, Screw terminals, Plastic enclosure, RDY out
3.8
SPD484801B 480W, Removable connector, PFC, Parallel function
48
10
Item Number
SPD Bi and Three Phase Description
SPD121002 SPD241002 SPD481002
90264
120375
24
Vin Vin Vout Iout VAC VDC VDC A
2ph 100W, Screw terminals, Parallel function, Plastic enclosure 2ph 100W, Screw terminals, Parallel function, RDY out, Plastic enclosure 2ph 100W, Screw terminals, Parallel function, Plastic enclosure
12
8.4
24
4.2
48
2.1
SPD121203
3ph. 120W, Screw terminals, PFC
12
10
SPD241203
3ph 120W, Screw terminals, PFC, RDY out
24
5
24
10
48
5
24
20
48
10
24
40
24
40
48
20
SPD242403
3ph 240W, Screw terminals, PFC and parallel function, RDY out
SPD482403 3ph 240W, Screw terminals, PFC and parallel function SPD244803
3ph 480W, Screw terminals, PFC and parallel function, RDY out
SPD484803 3ph 480W, Screw terminals, PFC and parallel function SPD249603 SPD249603L SPD489603
3ph 960W, Screw terminals, PFC, Active parallel function, RDY out 3ph 960W, Screw terminals, PFC 3ph 960W, Screw terminals, PFC, Active parallel function
340575
480820
SPD24RM20
Redundant Module 24Vin 20A max.
N/A
24
24
20
SPM2RM2410
Redundant Module 24Vin 10A max.
N/A
5-24
Vin
10
Specifications are subject to change without notice.
Switching Power Supply Type SPD 120W New DIN rail mounting • • • • • • • • • • •
Installation on DIN Rail 7.5 or 15mm Short circuit protection PFC standard High efficiency Power ready output LED indicator for DC power ON LED indicator for DC low Parallel versions standard Compact dimensions Specific model for UL 1310 class 2 UL, cUL listed and TUV/CE approved
Product Description
Ordering Key
The Switching power supplies SPD series are specially designed to be used in all automation application where the installation is on a DIN rail
Model Mounting ( D = Din rail ) Output voltage Output power Input type Optional features New Type
and compact dimensions and performance are a must. Then version features PFC and parallel function as standard.
Approvals
SP D 24120 1 B N
Input type: 1= single phase
Optional Features Description
code
Standard screw terminal Plug-in connectors
Nil B
Output performances Rated output Output Voltage Power (VDC) 12 120 SPD12120 24 92 SPD2490 24 120 SPD24120 48 120 SPD48120 Model
DC on LED (VDC) DC on LED (VDC) Output Voltage Trim Range Typical Thereshold at startup Thereshold after startup Current (A) Efficiency Min. VDC Max. VDC Min. Max. Min. Max. 10 11.4 14.5 10 11.2 10 11.2 84% 3.8 22.5 24.5 17.6 19.4 17.0 19.4 85% 5 22.5 28.5 17.6 19.4 17.6 19.4 86% 2.5 45.0 55.0 37.0 43.0 37.0 43.0 87%
Output data Output voltage accuracy adjusted Line regulation Load regulation Non parallel model Parallel model Temp. coefficient
-0 +1% max (factory ± 0.5% ± 1% ± 5% ± 0.3% / °C
Transient recovery time Ripple and noise Hold up Time Vi = 115Vac Hold up time Vi = 230Vac Minimum load Parallel Operation (Not available SPD2490)
300µs 50mVpp 25ms 30ms 0% 3 units max.
Specifications are subject to change without notice. Pictures are just an example. For special features and/or custumization, please ask to our sales network.
Switching Power Supply Type SPD 120W New DIN rail mounting
Input data 115/230 autoselect
Rated input voltage Voltage range AC in, 115 AC in, 230 DC in Rated input current Rated input current SPD2490
47- 63 Hz
Frequency range Inrush current Vi= 115Vac Vi= 230Vac P.F.C.
90 - 132 Vac 186 - 264 Vac 210 - 370 Vdc 2.8 / 1.4A 2.0 / 0.8A
24A 48A 0.7
Controls and Protections T3.15/250Vac internal* 125 – 145% 102 - 106% Current limited 110 - 145% 102 - 108%
Input Fuse Overvoltage Protection Overvoltage Protection SPD2490 Output Short Circuit Rated Overload Protection Rated Overload Prot. SPD2490
Power ready (only SPD 24) Threshold at start up (contact closed) Contact rating at 60Vdc insulation
17.6 - 19.4 0.3A 500Vdc
* Not replaceable by user.
General data (@ nominal line, full load, 25°C ) -10°C to 71°C 2.5% / °C 20 to 95%RH -25°C to +85°C IP20 Free air convection
Ambient temperature Derating (>60°C to +71°C) Ambient humidity Storage Protection degree Cooling
80kHz 480.000h Metal (powder painted aluminium) 125 x 63.5 x 126 920g
Switching frequency MTBF (MIL-HDBK-217F) Case material Dimensions L x W x D Weight
Approvals and EMC 3.000Vac min 100Mohm min UL508 listed, UL60950-1 Recognised UL1310 class 2 EN60950-1
Insulation voltage I / O Insulation resistance UL / cUL SPD2490 only TUV
EN50081-1 EN55022 class B EN61000-3-2 EN61000-3-3 EN61000-6-2 EN61000-6-3 EN55024
CE
Block diagrams
L
Vo +
Fuse Line Filter
P.F.C. Circuit
Inrush Current Limiter and Rectifier
Smoothing Circuit
Switching Device
Rectifier
N Y
PWM Controller
Current Detection
Vo Single/parallel selection 1)
Opto isolation
Reference & Error Amp.
Opto isolation
Over Voltage Detection
Output Level Detection
115V/230V selected 1) Not available on SPD2490 2) for 24VDC models
Vout ADJ.
DCON (Green LED) DCLOW (Red LED) RDY 2) (Relay Contact)
Specifications are subject to change without notice. Pictures are just an example. For special features and/or costumization, please ask to our sales network.
Switching Power Supply Type SPD 120W New DIN rail mounting
Pin assignement and front controls Pin No. 1 2 3 4 5 6 7 8 9
Designation RDY (only SPD 24) RDY (only SPD 24) + + GND L N DC ON DC LO Vout ADJ. S/P
Description DC OK, relay normally open contact DC OK, relay normally open contact Positive output terminal Positive output terminal Negative output terminal Negative output terminal Ground terminal to minimise High frequency emissions Phase input ( no polarity with DC input ) Neutral input ( no polarity with DC input ) DC output ready LED DC low indicator LED Trimmer for fine output voltage adjustment Single/parallel selection switch (Not available on SPD2490)
Installation
Derating Diagram
VENTILATION / COOLING: • Normal air convection • 25mm of free space along all sides to allow good cooling SCREW CONNECTIONS: • 10-24AWG Flexible or solid cable. 8mm stripping recommended PLUG IN CONNECTORS: • 10-24AWG Flexible or solid cable. 7mm stripping recommended
Mechanical Drawings 116 (4.57)
Power out (%) 100 90 80 70 60 50 40 30 20 10 0 -10 0 5 10 Temperature (°C)
55
60
65
70
75
80
mm (inches)
6
7.0 (0.3) 6
I
I DC INPUT S
f
d e
2 JF4 E25 835 5 IND.C ONT. EQ.
B
au
ar t g eprü
f
S&E Rheinland Product Safety
p
y
v
T
appro
t
T
e
d
ar t g eprü
S&E
p
123.6 (4.87)
au
t
B
Rheinland Product Safety
y
N.C.
P
e
v appro
e
2 JF4 E25 835 5 IND.C ONT. EQ.
143 (5.63)
N.C.
P
123.6 (4.87)
S
AC INPUT 63.2 (2.49) 7
9
63.2 (2.49) 7
9
Specifications are subject to change without notice. Pictures are just an example. For special features and/or costumization, please ask to our sales network.
Switching Power Supply Type SPD 5W DIN rail mounting • • • • • • • • •
Universal AC input full range Installation on DIN rail 7.5 or 15mm Short circuit protection Overload protection High efficiency LED indicator for DC power ON LED indication for DC low Internal input filter CE, TUV approved and cULus Listed
Product Description
Ordering Key
The Switching power supplies SPD series are specially designed to be used in all automation application where the installation is on a DIN rail
Model Mounting ( D = Din rail ) Output voltage Output power Input Type Optional features
and compact dimensions and performance are a must.
SP D 12 05 1 B
Input type: 1= single phase
Approvals au
art geprü
Description
f t
B
Optional Features
Rheinland Product Safety
Spring connectors
d
p
e
T
y
e
appro
Code
v
B
Output Performances INPUT VOLTAGE
MODEL NO.
SPD05 SPD12 SPD24 SPD48
90~264 90~264 90~264 90~264
OUTPUT WATTAGE
VAC VAC VAC VAC
5 5 5 5
WATTS WATTS WATTS WATTS
OUTPUT VOLTAGE
OUTPUT CURRENT
Single Output Models + 5 VDC 1000 mA +12 VDC 420 mA +15 VDC 340 mA +24 VDC 210 mA
EFF. (min.)
EFF. (typ.)
EFF. (avg.)
67% 70% 70% 70%
83% 86% 87% 87%
69% 72% 72% 72%
Output Data Line regulation Load regulation Minimum load Turn on time (full resistive load) Transient recovery time Ripple and noise Output voltage accuracy Temperature coefficient Hold up time Vi= 115VAC Vi= 230VAC Voltage fall time (I0nom)
1
± 1% ± 2% 0 1000ms max 2ms 50mVpp ± 1% ± 0.03%/°C 30ms 130ms 150ms max
Rated continuous loading 5V Model 12V Model 15V Model 24V Model
1.0A @ 5VDC/0.85A @ 5.75VDC 0.42A @ 12VDC/0.36A @ 13.8VDC 0.34A @ 15VDC/0.28A @ 17.25VDC 0.21A @ 24VDC/0.17A @28.8VDC
Reverse voltage 5V Model 12V Model 15V Model 24V Model Capacitor load Voltage rise time at full resistive load
VDC 7.5 VDC 18 VDC 22 VDC 35 7000µF 150ms max
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12
Switching Power Supply Type SPD 5W DIN rail mounting
Input Data Rated input voltage Voltage range AC DC Rated input current (Vi : 115VAC, Io nom) Typ. Max. Inrush current Vi= 115VAC Vi= 230VAC
100 - 240VAC 90 - 265VAC 120 - 370VDC 115mA 200mA 10A 18A
Power dissipation (Vi : 230VAC, Io nom) 5V Model 12V Model 15V Model 24V Model Frequency range Leakage current Input-Output Input-FG
2.2W 1.9W 2.1W 1.8W 47- 63Hz 0.25mA 3.5mA
Controls and Protections Overload Input fuse Output short circuit
1)
110 – 135% T2A/250VAC internal1) Hiccup mode
Over voltage protection 125 - 145% Internal surge voltage protection Varistor (IEC 61000-4-5)
Fuse not replaceable by user
General Data (@ nominal line, full load, 25°C ) Ambient temperature Derating (>61°C to +71°C) Ambient humidity Storage Protection degree Cooling Insulation voltage Input-Output Input-FG Insulation resistance I/O
-20°C to 71°C 2.5%/°C 20 ~ 95%RH -25°C to +85°C IP20 Free air convection 3.000VAC/4242VDC min 1.500VAC/2121VDC min 100M1 min (@ 500VDC)
MTBF
(Bellcore issue 6 @ 40°C, GB)
5V Model 12V Model 15V Model 24V Model
802000 Hours 805000 Hours 808000 Hours 812000 Hours Case material Plastic: PC, UL94-V0 Pollution degree 2 Altitude 4850m Dimensions LxWxD mm(inch) 90(3.60)x22.5(0.89)x114(4.49) Weight 120g
Norms and Standards Vibration resistance
Shock resistance
UL / cUL
TUV CCC
meet IEC 60068-2-6 (Mounting by rail: 10-500Hz, 2G, along X, Y, Z each Axis, 60 min for each Axis) meet IEC 60068-2-27 (15G, 11ms, 3 Axis, 6 faces, 3 times for each face) UL508 listed, UL60950-1, UL1310 Class 2 Power (only 5V, 12V w/o Class 2) Recognized, ISA 12.12.01 (Class 1, Division 2, Groups A, B, C and D) EN 60950-1, CB scheme GB4943, GB9254, GB17625.1
CE
EN 61000-6-3, EN 55022 Class B, EN 61000-3-2, EN 61000-3-3, EN 61000-6-2, EN 55024, EN 61000-4-2 Level 4, EN 61000-4-3 Level 3, EN 61000-4-4 Level 4, EN 61000-4-5 L-Level 3, L/N-FG Level 4, EN 61000-4-6 Level 3, EN 61000-4-8 Level 4, EN 61000-4-11, ENV 50204 Level 2, EN 61204-3
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12
2
Switching Power Supply Type SPD 5W DIN rail mounting
Block Diagrams
Pin Assignement and Front Controls Pin No.
Designation
Description
1
V+
Positive output terminal
2
V-
Negative output terminal Ground this terminal to minimize high-frequency emission
3 4
N
Input terminals (neutral conductor, no polarity at DC input)
5
L
Input terminals (phase conductor, no polarity at DC input)
ON
Operation indicator LED
LO
DC LOW indicator LED
Vout ADJ.
Trimmer-potentiometer for Vout adjustment
Derating Diagram
Output voltage (%)
100
75
0 -20
61
71
Temperature
3
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12
Switching Power Supply Type SPD 5W DIN rail mounting
Typ. Current Limited Curve v
Output voltage (%)
Hiccup Mode 100
75
t Time
Mechanical Drawings 22.50 (0.89)
2
Typ. Efficiency Curve
mm (inches)
80 75 70
22.50 (0.89)
1
2
1
V-
V+
DC Output
Vout ADJ
LO
90.00 (3.60)
90.00 (3.60)
LO ON
ON
Vout ADJ
EFFICIENCY (%)
DC Output
65 60 55 50 45 230 VAC 115 VAC
40 35 30 25 10
N L
3 4 5
3 4 5
25
50 Power out (%)
75
100
Installation Ventilation and cooling
114.00 (4.49) Connector size range Spring terminal
Screw terminal
Max. torque for terminal Input terminals Output terminals General tolerances mm(in.) 0.00 (0.00) ÷ 30.00 (1.18) 30.00 (1.18) ÷ 120.00 (4.72)
Normal convection All sides 25mm free space for cooling is recommended AWG24-14 (0.2~2mm2) flexible/solid cable, 10mm stripping at cable and recommends use copper conductors only, 60/75°C AWG26-12 (0.2~2.5mm2) flexible/solid cable, connector can withstand torque at max 0,56Nm (5 lbs-in). 4~5 mm stripping at cable and recommends use copper conductors only, 60/75°C 0.56Nm (5.0lb-in) 0.56Nm (5.0lb-in) ±0.30 (0.01) ±0.50 (0.02)
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12
4
Switching Power Supply Type SPD 10W DIN rail mounting • • • • • • • • • •
Product Description The Switching power supplies SPD series are specially designed to be used in all automation application where the
Universal AC input full range Installation on DIN rail 7.5 or 15mm Short circuit protection Overload protection High efficiency LED indicator for DC power ON LED indication for DC low Power Ok output Internal input filter CE, TUV approved and cULus Listed
Ordering Key
installation is on a DIN rail and compact dimensions and performance are a must.
SP D 24 10 1 B
Model Mounting ( D = Din rail ) Output voltage Output power Input Type Optional features Input type: 1= single phase
Optional Features
Approvals au
art geprü
f t
B
p
e
T
d
Rheinland Product Safety
y
e
appro
v
Description
Code
Spring connectors Class I, Div 2
UL 1310
B
UL 60950-1
Output Performances MODEL NO.
SPD05 SPD12 SPD15 SPD24
INPUT VOLTAGE 90~264 90~264 90~264 90~264
VAC VAC VAC VAC
OUTPUT WATTAGE 10 10 10 10
OUTPUT VOLTAGE
Single Output Models WATTS + 5 VDC WATTS +12 VDC WATTS +15 VDC WATTS +24 VDC
OUTPUT CURRENT
EFF. (min.)
EFF. (typ.)
2000 mA 840 mA 670 mA 420 mA
71% 73% 74% 74%
73% 75% 76% 76%
Output Data Line regulation Load regulation Minimum load Turn on time (full resistive load) Vi nom, Io nom with 3500µF Transient recovery time Ripple and noise Output voltage accuracy Temperature coefficient Hold up time Vi= 115VAC Vi= 230VAC Voltage fall time (I0nom)
1
± 1% ± 2% 0 1000ms 1500ms 2ms 50mVpp + 1% ± 0.03%/°C 25ms 100ms 150ms max
Rated continuous loading 5V Model 12V Model 15V Model 24V Model Reverse voltage 5V Model 12V Model 15V Model 24V Model Capacitor load Voltage rise time at
2A @ 5VDC/1.7A @ 5.75VDC 0.84A@12VDC/
[email protected] 0.67A @ 15VDC/0.58A @ 17.25VDC 0.42A @ 24VDC/0.34A @ 28.8VDC 7.5VDC 18VDC 22VDC 35VDC 3500µF 500ms
(full resistive load)
Vi nom, Io nom with 3500µF
150ms
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12
Switching Power Supply Type SPD 10W DIN rail mounting
Input Data Rated input voltage Voltage range AC DC Rated input current (Vi : 115VAC, Io nom) Typ. Max. Inrush current Vi= 115VAC Vi= 230VAC
100 - 240VAC 90 - 264VAC 120 - 375VDC 200mA 300mA 10A 18A
Power dissipation (Vi : 230VAC, Io nom) 5V Model 12V Model 15V Model 24V Model Frequency range Leakage current Input-Output Input-FG
4.0W 3.4W 3.3W 2.8W 47- 63Hz 0.25mA 3.5mA
Controls and Protections Overload Input fuse Output short circuit 1)
110 – 145% T2A/250VAC internal1) Hiccup mode
Over voltage protection 125-145% Internal surge voltage protection Varistor (IEC 61000-4-5)
Fuse not replaceable by user
General Data (@ nominal line, full load, 25°C ) Ambient temperature Derating (>61°C to +71°C) Ambient humidity Storage Protection degree Cooling Insulation voltage Input-Output Input-FG Insulation resistance I/O
-20°C to 71°C 2.5%/°C 20 ~ 95%RH -25°C to +85°C IP20 Free air convection 3.000VAC/4242VDC min 1.500VAC/2121VDC min 100M1 min (@ 500VDC)
MTBF
(Bellcore issue 6 @ 40°C, GB)
5V Model 12V Model 15V Model 24V Model
801000 Hours 803000 Hours 805000 Hours 808000 Hours Case material Plastic: PC, UL94-V0 Pollution degree 2 Altitude 2000m Dimensions LxWxD mm(inch) 90(3.60)x22.5(0,89)x114(4.49) Weight 120g
Norms and Standards Vibration resistance
Shock resistance
UL / cUL
TUV CCC
meet IEC 60068-2-6 (Mounting by rail: 10-500Hz, 2G, along X, Y, Z each Axis, 60 min for each Axis) meet IEC 60068-2-27 (15G, 11ms, 3 Axis, 6 faces, 3 times for each face) UL508 listed, UL60950-1, UL1310 Class 2 Power Recognized, ISA 12.12.01 (Class 1, Division 2, Groups A, B, C and D) EN 60950-1, CB scheme GB4943, GB9254, GB17625.1
CE
EN 61000-6-3, EN 55022 Class B, EN 61000-3-2, EN 61000-3-3, EN 61000-6-2, EN 55024, EN 61000-4-2 Level 4, EN 61000-4-3 Level 3, EN 61000-4-4 Level 4, EN 61000-4-5 L-Level 3, L/N-FG Level 4, EN 61000-4-6 Level 3, EN 61000-4-8 Level 4, EN 61000-4-11, ENV 50204 Level 2, EN 61204-3
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12
2
Switching Power Supply Type SPD 10W DIN rail mounting
Block Diagrams
Pin Assignement and Front Controls Pin No.
Designation
Description
1
V+
Positive output terminal
2
V-
Negative output terminal Ground terminal to minimise High frequency emissions
3 4
N
Input terminals (neutral conductor, no polarity at DC input)
5
L
Input terminals (phase conductor, no polarity at DC input)
ON
Operation indicator LED
LO
DC LOW indicator LED
Vout ADJ.
Trimmer-potentiometer for Vout adjustment
Derating Diagram
Output voltage (%)
100
75
0 -20
3
Temperature
61
71
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12
Typ. Current Limited Curve v
Output voltage (%)
Hiccup Mode 100
75
t Time
Mechanical Drawings
22.50 (0.89)
2 1 V-
V+
2
1
V-
V+
DC Output
LO
LO
ON
ON
90.00 (3.60)
90.00 (3.60)
DC Output
Vout ADJ
Typ. Efficiency Curve
Vout ADJ
EFFICIENCY (%)
22.50 (0.89)
mm (inches)
85 80 75 70 65 60 55 50 45 40 35
230 VAC 115 VAC
10 N L
25
50 Power out (%)
75
100
N L
Installation 3 4 5 114.00 (4.49)
3 4 5
Ventilation and cooling
Connector size range Spring terminal
Screw terminal
Max. torque for terminal Input terminals Output terminals General tolerances mm(in.) 0.00 (0.00) ÷ 30.00 (1.18) 30.00 (1.18) ÷ 120.00 (4.72)
Normal convection All sides 25mm free space for cooling is recommended AWG24-14 (0.2~2mm2) flexible/solid cable, 10mm stripping at cable and recommends use copper conductors only, 60/75°C AWG26-12 (0.2~2.5mm2) flexible/solid cable, connector can withstand torque at max 0,56Nm (5 lbs-in). 4~5 mm stripping at cable and recommends use copper conductors only, 60/75°C 0.56Nm (5.0lb-in) 0.56Nm (5.0lb-in) ±0.30 (0.01) ±0.50 (0.02)
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12
4
Switching Power Supply Type SPD 18W DIN rail mounting • • • • • • • • •
Universal AC input full range Installation on DIN rail 7.5 or 15mm Short circuit protection Overload protection High efficiency LED indicator for DC power ON LED indication for DC low Internal input filter CE, TUV approved and cULus Listed
Product Description
Ordering Key
The Switching power supplies SPD series are specially designed to be used in all automation application where the installation is on a DIN rail
Model Mounting ( D = Din rail ) Output voltage Output power Input Type Optional features
and compact dimensions and performance are a must.
SP D 24 18 1 B
Input type: 1= single phase
Approvals au
art geprü
Description
f t
B
Optional Features Code
y
Class I, Div 2
p
e
T
d
Rheinland Product Safety
e
appro
v
UL 1310
Spring connectors
B
UL 60950-1
Output performances MODEL NO.
SPD05 SPD12 SPD15 SPD24
INPUT VOLTAGE 90~264 90~264 90~264 90~264
VAC VAC VAC VAC
OUTPUT WATTAGE 15 18 18 18
OUTPUT VOLTAGE
Single Output Models WATTS + 5 VDC WATTS +12 VDC WATTS +15 VDC WATTS +24 VDC
OUTPUT CURRENT
EFF. (min.)
EFF. (typ.)
3000 mA 1500 mA 1200 mA 750 mA
73% 75% 75% 75%
75% 77% 77% 77%
Output data Line regulation Load regulation Minimum load Turn on time (full resistive load) Vi nom, Io nom with 7000µF CAP Transient recovery time Ripple and noise Output voltage accuracy Temperature coefficient Hold up time Vi= 115VAC Vi= 230VAC Voltage fall time (I0nom)
1
± 1% ± 2% 0 1000ms 1500ms 2ms 50mVpp ± 1% ± 0.03%/°C 20ms 75ms 150ms max
Rated continuous loading 5V Model 12V Model 15V Model 24V Model Reverse voltage 5V Model 12V Model 15V Model 24V Model Capacitor load Voltage rise time Vi nom Io nom Vi nom, Io nom with 7000µF CAP
3A @ 5VDC/2.6A @ 5.75VDC 1.5A @ 12VDC/1.3A @ 13.8VDC 1.2A @ 15VDC/1.0A @ 17.25VDC 0.75A @ 24VDC/0.6A @28.8VDC VDC 7.5 VDC 18 VDC 22 VDC 35 7000µF 150ms 500ms
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12
Switching Power Supply Type SPD 18W DIN rail mounting
Input data Rated input voltage Voltage range AC DC Rated input current Vi: 115VAC, Io nom Inrush current Vi= 115VAC Vi= 230VAC
100 - 240VAC
Power dissipation 5V Model 12V Model 15V Model 24V Model Frequency range Leakage current Input-Output Input-FG (Vi : 230VAC, Io nom)
90 - 264VAC 120 - 375VDC 335-500mA 10A 18A
5.0W 4.65W 4.25W 4.45W 47- 63Hz 0.25mA 3.5mA
Controls and Protections Overload Input Fuse Overvoltage Protection 1)
110 – 140% T2A/250VAC internal1) 125 – 145%
Output Short Circuit Hiccup mode Internal surge voltage protection Varistor (IEC 61000-4-5)
Fuse not replaceable by user
General data (@ nominal line, full load, 25°C ) Ambient temperature Derating (>61°C to +71°C) Ambient humidity Storage Protection degree Cooling Insulation voltage Input-Output Input-FG Insulation resistance I/O
-20°C to 71°C 2.5%/°C 20 ~ 95%RH -25°C to +85°C IP20 Free air convection 3.000VAC/4242VDC min 1.500VAC/2121VDC min 100M1 min (@ 500VDC)
MTBF
(Bellcore issue 6 @ 40°C, GB)
5V Model 12V Model 15V Model 24V Model
795000 Hours 797000 Hours 796000 Hours 800000 Hours Case material Plastic: PC, UL94-V0 Pollution degree 2 Altitude 2000m Dimensions LxWxD mm(inch) 90(3.60)x22.5(0.89)x114(4.49) Weight 150g
Norms and Standards Vibration resistance
Shock resistance
UL / cUL
TUV CCC
meet IEC 60068-2-6 (Mounting by rail: 10-500Hz, 2G, along X, Y, Z each Axis, 60 min for each Axis) meet IEC 60068-2-27 (15G, 11ms, 3 Axis, 6 faces, 3 times for each face) UL508 listed, UL60950-1, UL1310 Class 2 Power (only 5V, 12V w/o Class 2) Recognized, ISA 12.12.01 (Class 1, Division 2, Groups A, B, C and D) EN 60950-1, CB scheme GB4943, GB9254, GB17625.1
CE
EN 61000-6-3, EN 55022 Class B, EN 61000-3-2, EN 61000-3-3, EN 61000-6-2, EN 55024, EN 61000-4-2 Level 4, EN 61000-4-3 Level 3, EN 61000-4-4 Level 4, EN 61000-4-5 L-N Level 3, L/N-FG Level 4, EN 61000-4-6 Level 3, EN 61000-4-8 Level 4, EN 61000-4-11, ENV 50204 Level 2, EN 61204-3
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12
2
Switching Power Supply Type SPD 18W DIN rail mounting
Block diagrams
Pin Assignement and Front Controls Pin No.
Designation
Description
1
V+
Positive output terminal
2
V-
Negative output terminal Ground this terminal to minimize high-frequency emission
3 4
N
Input terminals (neutral conductor, no polarity at DC input)
5
L
Input terminals (phase conductor, no polarity at DC input)
ON
Operation indicator LED
LO
DC LOW indicator LED
Vout ADJ.
Trimmer-potentiometer for Vout adjustment
Derating Diagram
Output voltage (%)
100
75
0 -20
61
71
Temperature
3
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12
Typ. Current Limited Curve v
Output voltage (%)
Hiccup Mode 100
50
t Time
Mechanical Drawings 22.50 (0.89)
Vout ADJ
1
85 80
V-
V+
75 70
DC Output
90.00 (3.60)
90.00 (3.60)
ON
2
LO ON
Vout ADJ
EFFICIENCY (%)
V+
DC Output LO
Typ. Efficiency Curve
22.50 (0.89)
2 1 V-
mm (inches)
65 60 55 50 45
230 VAC 115 VAC
40 35 N L
3 4 5 114.00 (4.49)
N L
3 4 5
10
25
50 Power out (%)
75
100
Installation Ventilation and cooling
Connector size range Spring terminal
Screw terminal
Max. torque for terminal Input terminals Output terminals General tolerances mm(in.) 0.00 (0.00) ÷ 30.00 (1.18) 30.00 (1.18) ÷ 120.00 (4.72)
Normal convection All sides 25mm free space for cooling is recommended AWG24-14 (0.2~2mm2) flexible/solid cable, 10mm stripping at cable and recommends use copper conductors only, 60/75°C AWG26-12 (0.2~2.5mm2) flexible/solid cable, connector can withstand torque at max 0,56Nm (5 lbs-in). 4~5 mm stripping at cable and recommends use copper conductors only, 60/75°C 0.56Nm (5.0lb-in) 0.56Nm (5.0lb-in) ±0.30 (0.01) ±0.50 (0.02)
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12
4
Switching Power Supply Type SPD 30W DIN rail mounting • • • • • • • • •
Universal AC input full range Installation on DIN rail 7.5 or 15mm Short circuit protection Overload protection Class 2 output High efficiency LED indicator for DC power ON Power Ok output CE, TUV approved and cULus Listed
Product Description
Ordering Key
The Switching power supplies SPD series are specially designed to be used in all automation application where the
Model Mounting ( D = Din rail ) Output voltage Output power Input Type Optional features
installation is on a DIN rail and compact dimensions and performance are a must.
SP D 12 30 1 B
Input type: 1= single phase
Approvals a
Description
f t
B
Optional Features
rt gepr ua ü
Rheinland Product Safety
Class I, Div 2
Spring connectors
d
p
e
T
y
e
appro
v
UL 1310
Code B
UL 60950-1
Output performances MODEL NO.
SPD05 SPD12 SPD24 SPD48
INPUT VOLTAGE 85~264 85~264 85~264 85~264
VAC VAC VAC VAC
OUTPUT WATTAGE 30 30 30 30
OUTPUT VOLTAGE
Single Output Models WATTS + 5 VDC WATTS +12 VDC WATTS +24 VDC WATTS +48 VDC
OUTPUT CURRENT
EFF. (min.)
EFF. (typ.)
6000 mA 2500 mA 1250 mA 625 mA
77% 82% 83% 83%
79% 84% 86% 86%
Output Data Line regulation Load regulation Minimum load Turn on time (full resistive load) Vi nom, Io nom Vi nom, Io nom with 3500µF CAP Transient recovery time Ripple and noise Output voltage accuracy Temperature coefficient Hold up timeVi= 115VAC Vi= 230VAC Voltage fall time (I0nom)
1
± 0.5% ± 0.5% 0 1000ms 2000ms 2ms 50mVpp ± 1% ± 0.03%/°C 20ms 30ms 150ms max
Rated continuous loading 5V Model 12V Model 24V Model 48V Model Reverse voltage 5V Model 12V Model 24V Model 48V Model Capacitor load Voltage rise time Vi nom Io nom Vi nom, Io nom with 3500µF CAP
6A @ 5VDC/5.4A @ 5.5VDC 2.5A @ 12VDC/2.1A @ 14VDC 1.25A @ 24VDC/1.05A @ 28VDC 0.625A @ 48VDC/0.54A @ 55VDC 7.5VDC 18VDC 35VDC 63VDC 3500µF 150ms 500ms
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12
Switching Power Supply Type SPD 30W DIN rail mounting
Input Data Rated input voltage Voltage range AC DC Rated input current (Vi : 115VAC, Io nom) Typ. Max. Inrush current Vi= 115VAC Vi= 230VAC
100 - 240VAC 85 - 264VAC 90 - 375VDC 560mA 800mA 20A 40A
Power dissipation (Vi : 230VAC, Io nom) 5V Model 12V Model 24V Model 48V Model Frequency range Leakage current Input-Output Input-FG
8.5W 5.6W 5.5W 4.9W 47- 63Hz 0.25mA 3.5mA
Controls and Protections Overload Input fuse Output short circuit Power ready output (only SPD 24) On threshold Off threshold 1)
110 – 140% T2A/250VAC internal1) Fold forward *19.2-19.4VDC )19.1-19.3VDC
Over voltage protection
VDC
Min. 5V Model 6 12V Model 15 24V Model 30 48V Model 60 Internal surge voltage protection Varistor
Max. 6.8 16.5 33 66
(IEC 61000-4-5)
Fuse not replaceable by user
General Data (@ nominal line, full load, 25°C ) Ambient temperature Derating (>61°C to +71°C) Ambient humidity Storage Protection degree Cooling Pollution degree
-40°C to 71°C 2.5%/°C 20 ~ 90%RH -40°C to +85°C IP20 Free air convection 2
MTBF
(Bellcore issue 6 @ 40°C, GB)
5V Model 12V Model 24V Model 48V Model
551000 Hours 582000 Hours 588000 Hours 609000 Hours Case material Plastic: PC, UL94-V0 Dimensions LxWxD mm(inch) 90(3.6) x 40.5(1.59) x 114(4.49) Weight 270g
Norms and Standards Vibration resistance
Shock resistance
UL / cUL
TUV
CCC
meet IEC 60068-2-6 (Mounting by rail: 10-500Hz, 2G, along X, Y, Z each Axis, 60 min for each Axis) meet IEC 60068-2-27 (15G, 11ms, 3 Axis, 6 faces, 3 times for each face) UL508 listed, UL60950-1, UL1310 Class 2 Power (only 5V, w/o Class 2) Recognized, ISA 12.12.01 (Class 1, Division 2, Groups A, B, C and D) EN 60950-1, CB scheme EN 61558-1, EN 61558-2-17 (meet EN 60204) GB4943, GB9254, GB17625.1
CE
EN 61000-6-3, EN 55022 Class B, EN 61000-3-2, EN 61000-3-3, EN 61000-6-2, EN 55024, EN 61000-4-2 Level 4, EN 61000-4-3 Level 3, EN 61000-4-4 Level 4, EN 61000-4-5 L-Level 3, L/N-FG Level 4, EN 61000-4-6 Level 3, EN 61000-4-8 Level 4, EN 61000-4-11, ENV 50204 Level 2, EN 61204-3
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12
2
Switching Power Supply Type SPD 30W DIN rail mounting
Block Diagrams
Rdy connection RL >700ohm Rdy
L
Fuse
Vo+ Line Filter
Inrush Current Limiter and Rectifier
Switching Device
Vo-
N
-Vout
PWM Controller
a) Relay
Rdy
Rectifier
2.2k 0.5W
OptoIsolation
Reference & Error Amp.
OptoIsolation
Over Voltage Detection
5.1k 0.3w
Vout ADJ
Output Level Detection
-Vout b) 5V signal
DC ON (Green LED) RDY (Open Collector)
Pin Assignement and Front Controls Pin No.
Designation
Description
1
RDY
DC OK output for relay (not connect except 24V model)
2
+
Positive output terminal
3
+
Positive output terminal
4
-
Negative output terminal
5
-
Negative output terminal Ground this terminal to minimize high-frequency emissions
N
Input terminals (neutral conductor, no polarity at DC input)
L
Input terminals (phase conductor, no polarity at DC input)
Vout ADJ
Trimmer-potentiometer for Vout adjustment
DC ON
Operation indicator LED
Derating Diagram
Typ. Efficiency Curve 95 90 85 80 Efficiency (%)
Output voltage (%)
100
75
70 65 60 55 50
230 VAC 115 VAC
45 40
0 -25
61 Temperature (C°)
3
75
71
10
25
50
75
100
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12
Switching Power Supply Type SPD 30W DIN rail mounting
Output Voltage (%)
Typ. Current Limited Curve
100 75 230 VAC 115 VAC
50 25 0 120
130
140
150
160
170
180
190
Output Current (%)
Mechanical Drawings
mm (inches)
Installation
40.50 (1.59)
40.50 (1.59)
543 2 1
543 2 1
- - + + Rdy
- - + + Rdy
Vout ADj
DC ON
90.00 (3.60)
90.00 (3.60)
Ventilation and cooling
N L
Vout ADj
Connector size range Spring terminal
Screw terminal
DC ON
N L
67 8
67 8 114.00 (4.49)
Max. torque for terminal Input terminals Output terminals General tolerances mm(in.) 0.00 (0.00) ÷ 30.00 (1.18) 30.00 (1.18) ÷ 120.00 (4.72)
Normal convection All sides 25mm free space for cooling is recommended AWG24-14 (0.2~2mm2) flexible/solid cable, 10mm stripping at cable and recommends use copper conductors only, 60/75°C AWG26-12 (0.2~2.5mm2) flexible/solid cable, connector can withstand torque at max 0,56Nm (5 lbs-in). 4~5 mm stripping at cable and recommends use copper conductors only, 60/75°C 0.56Nm (5.0lb-in) 0.56Nm (5.0lb-in) ±0.30 (0.01) ±0.50 (0.02)
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12
4
Switching Power Supply Type SPD 60W DIN rail mounting • • • • • • • • •
Universal AC input full range Installation on DIN rail 7.5 or 15mm Short circuit protection Overload protection Class 2 output High efficiency LED indicator for DC power ON Power Ok output CE, TUV approved and cULus Listed
Product Description
Ordering Key
The Switching power supplies SPD series are specially designed to be used in all automation application where the installation is on a DIN rail
Model Mounting ( D = Din rail ) Output voltage Output power Input Type Optional features
and compact dimensions and performance are a must.
SP D 24 60 1 B
Input type: 1= single phase
Approvals au
art geprü
Description
f t
B
Optional Features
Rheinland Product Safety
Spring connectors
d
p
e
T
y
e
appro
Code
v
B
Output Performances Model
Rated output Voltage (VDC)
Output Power (W)
Output Current (A)
SPD05 SPD12 SPD24 SPD48
5 12 24 48
50 60 60 60
10.0 5.0 2.5 1.25
Voltage Trim Range Min. VDC 5 12 24 48
Max. VDC 5.5 14 28 55
DC ON green LED at start up DC LOW red LED after start up Min. VDC Max. VDC 3.5 4.5 9.0 10.8 18 21.6 37 43
Typical Efficiency 79% 86% 89% 89%
Output Data Line regulation Load regulation Minimum load (A) Turn on time (full resistive load) Transient recovery time Ripple and noise Output voltage accuracy Temperature coefficient Hold up time Vi= 115VAC Vi= 230VAC Voltage fall time (I0nom)
1
± 0.5% ± 0.5% 0 1000ms max 2ms 50mVpp ± 1% ± 0.03%/°C 20ms 30ms 150ms max
Rated continuous loading 5V Model 12V Model 24V Model 48V Model Reverse voltage 5V Model 12V Model 24V Model 48V Model Capacitor load Voltage rise time at full resistive load
10A @ 5VDC/9.0A @ 5.5VDC 5A @ 12VDC/4.25A @ 14VDC 2.5A @ 24VDC/2.1A @ 28VDC 1.25A @ 48VDC/1.08A @ 55VDC 7.5VDC 18VDC 35VDC 63VDC 7000µF 150ms max
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12
Switching Power Supply Type SPD 60W DIN rail mounting
Input Data Rated input voltage Voltage range AC DC Rated input current (Vi : 115VAC, Io nom) Typ. Max. Inrush current Vi= 115VAC Vi= 230VAC
100 - 240VAC 85 - 264VAC 90 - 375VDC 1060mA 1500mA 20A 40A
Power dissipation (Vi : 230VAC, Io nom) 5V Model 12V Model 24V Model 48V Model Frequency range Leakage current Input-Output Input-FG
12.5W 9.0W 8.8W 7.8W 47- 63Hz 0.25mA 3.5mA
Controls and Protections Overload Input fuse Output short circuit Power ready output (Rdy) (only SPD 24) On threshold Off threshold 1)
110 – 150% T2A/250VAC internal1) Fold forward Vout > 19,2V ± 2% Vout < 19,1V ± 2%
Over voltage protection
VDC
Min. 5V Model 6.0 12V Model 15 24V Model 30 48V Model 60 Internal surge voltage protection Varistor
Max. 6.8 16.5 33 66
(IEC 61000-4-5)
Fuse not replaceable by user
General Data (@ nominal line, full load, 25°C ) Ambient temperature Derating (>61°C to +71°C) Ambient humidity Storage Protection degree Cooling Insulation voltage Input-Output Input-FG Insulation resistance I/O
-40°C to 71°C 2.5%/°C 20 ~ 95%RH -40°C to +85°C IP20 Free air convection 3.000VAC/4242VDC min 1.500VAC/2121VDC min 100M1 min (@ 500VDC)
MTBF
(Bellcore issue 6 @ 40°C, GB)
5V Model 12V Model 24V Model 48V Model
498000 Hours 504000 Hours 520000 Hours 531000 Hours Case material Plastic: PC, UL94-V0 Pollution degree 2 Altitude 2000m Dimensions LxWxD mm(inch) 90(3.60)x40.5(1.59)x114(4.49) Weight 340g
Norms and Standards Vibration resistance
Shock resistance
UL / cUL
TUV
CCC
meet IEC 60068-2-6 (Mounting by rail: 10-500Hz, 2G, along X, Y, Z each Axis, 60 min for each Axis) meet IEC 60068-2-27 (15G, 11ms, 3 Axis, 6 faces, 3 times for each face) UL508 listed, UL60950-1, UL1310 Class 2 Power (only 5V, 12V w/o Class 2) Recognized, ISA 12.12.01 (Class 1, Division 2, Groups A, B, C and D) EN 60950-1, CB scheme EN 61558-1, EN 61558-2-17 (meet EN 60204) GB4943, GB9254, GB17625.1
CE
EN 61000-6-3, EN 55022 Class B, EN 61000-3-2, EN 61000-3-3, EN 61000-6-2, EN 55024, EN 61000-4-2 Level 4, EN 61000-4-3 Level 3, EN 61000-4-4 Level 4, EN 61000-4-5 L-Level 3, L/N-FG Level 4, EN 61000-4-6 Level 3, EN 61000-4-8 Level 4, EN 61000-4-11, ENV 50204 Level 2, EN 61204-3
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12
2
Switching Power Supply Type SPD 60W DIN rail mounting
Block Diagrams L
Fuse
Vo + Inrush Current Limiter and Rectifier
Line Filter
Switching Device
Rectifier
N
Vo -
PWM Controller Opto Isolation
Reference & Error Amp.
Opto Isolation
Over Voltage Detection
Vout ADj.
Y
Y Y Output Level Detection
DC ON (Green LED) RDY (Open Collector)
Pin Assignement and Front Controls Pin No.
Designation
Description
1
RDY
DC OK, output for relay (only on SPD 24)
2
+
Positive output terminal
3
+
Positive output terminal
4
-
Negative output terminal
5
-
Negative output terminal
6
GND
Ground terminal to minimise High frequency emissions
7
L
Phase input ( no polarity with DC input )
8
N
Neutral input ( no polarity with DC input )
Pot1
Vout ADJ.
Trimmer for fine output voltage adjustment
L1
DC ON
DC output ready LED
Output Rdy Wiring Diagram
Derating Diagram
RL > 700ohm Rdy
-Vout a ) Relay
Rdy
75
2.2K 0.5W 5.1K 0.3W
-Vout b ) 5V signal
3
Power out (%)
100
0 -40
61
71
Temperature (%)
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12
Switching Power Supply Type SPD 60W DIN rail mounting
Typ. Current Limited Curve SPD 60W - 24V
mm (inches)
Typ. Efficiency Curve
EFFICIENCY (%)
Mechanical Drawings
95 90 85 80 75 70 65 60 55 50 45 40 10
230 VAC 115VAC
25
50 Power out (%)
75
100
Installation Ventilation and cooling
Connector size range Spring terminal
Screw terminal
Max. torque for terminal Input terminals Output terminals General tolerances mm(in.) 0.00 (0.00) ÷ 30.00 (1.18) 30.00 (1.18) ÷ 120.00 (4.72)
Normal convection All sides 25mm free space for cooling is recommended AWG24-14 (0.2~2mm2) flexible/solid cable, 10mm stripping at cable and recommends use copper conductors only, 60/75°C AWG26-12 (0.2~2.5mm2) flexible/solid cable, connector can withstand torque at max 0,56Nm (5 lbs-in). 4~5 mm stripping at cable and recommends use copper conductors only, 60/75°C 0.56Nm (5.0lb-in) 0.56Nm (5.0lb-in) ±0.30 (0.01) ±0.50 (0.02)
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12
4
Alimentatori con tecnologia Switching Tipo SPD100W Montaggio da guida DIN • Installazione su guida DIN 7.5 o 15mm • Protezione da corto circuito • PFC standard • Controllo alimentazione in usciat a 24VCC • Indicatore LED per accensione DC ON • Indicatore LED di spegnimento DC LOW • Standard parallel function • Very compact dimensions • UL, cUL listed and TUV/CE approved • Class I div2 certification (in progress)
Product Description
Ordering Key
This SPD is the most compact 100W power supply on the market. Relay output for “power ready” parallel function and PFC are
Model Mounting ( D = Din rail ) Output voltage Output power Input type
included. Performances are unique with high efficiencies and the possibility of being used up to 70°C with a little derating.
Approvals au
Input type: 1= single phase
art geprü
f t
B
SP D 24 100 1
y
p
e
T
d
Rheinland Product Safety
e
appro
v
Output Performances MODEL NO.
INPUT VOLTAGE
OUTPUT WATTAGE
SPD12100
90~264 VAC
100.8 WATTS
SPD24100
90~264 VAC
SPD48100
90~264 VAC
OUTPUT VOLTAGE
OUTPUT CURRENT
EFF. (min.)
EFF. (typ.)
+12 VDC
8,4 A
82%
84%
100.8 WATTS
+24 VDC
4,2 A
84%
86%
100.8 WATTS
+48 VDC
2,1 A
86%
88%
Single Output Models
Output Data Line regulation Load regulation Non parallel model Parallel model Minimum load Turn on time (full resistive load) Vi nom, Io nom 12V/24V models with 7000µF CAP Vi nom, Io nom 48 V model with 3500µF CAP Transient recovery time Ripple and noise Output voltage accuracy Temperature coefficient Hold up timeVi= 115VAC Vi= 230VAC
1
± 1% ± 1% ± 5% 0
1000ms 2000ms 2ms 50mVpp ± 1% ± 0.03%/°C 15ms 30ms
Voltage fall time (I0nom) Rated continuous loading 12V Model 24V Model 48V Model Reverse voltage 12V Model 24V Model 48V Model Capacitor load 12V/24V models 48V model Voltage rise time Vi nom Io nom Vi nom, Io nom 12V/24V models with 7000µF CAP 48V model with 3500µF CAP
150ms max 8.4A @ 12VDC/6.9A @ 14.5VDC 4.2A @ 24VDC/3.5A @ 28.5VDC 2.1A @ 48VDC/1.8A @ 56VDC 18VDC 35VDC 63VDC 7000µF 3500µF 150ms 500ms 500 ms
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 0811
Switching Power Supply Type SPD 100W DIN rail mounting
Input Data Rated input voltage Voltage range AC DC Rated input current (Vi : 90VAC, Io nom) Typ. Inrush current Vi= 115VAC Vi= 230VAC
100 - 240VAC
Power dissipation 12V Model 24V Model 48V Model Frequency range Leakage current Input-Output Input-FG (Vi : 230VAC, Io nom)
90- 264VAC 120 - 375VDC 2.4A 30A 60A
18.5W 15W 14W 47- 63Hz 0.25mA 3.5mA
Controls and Protections Over voltage protection
Overload 12V model 24V model 48V model Input fuse Output short circuit Power ready output threshold at start up Elettrical isolation Contact rating at 60VDC 1)
14.5V to 17.4V 30.0V to 33.0V 60.0V to 66.0V T3.15A/250VAC internal1) Fold forward
VDC
Min. 12V Model 14.5 24V Model 30 48V Model 60 Internal surge voltage protection Varistor
Max. 17.4 33 66
(IEC 61000-4-5)
≥17.6-19.4VDC 500VDC 0.3A
Fuse not replaceable by user
General Data (@ nominal line, full load, 25°C ) Ambient temperature Derating (>61°C to +71°C) Ambient humidity Storage Protection degree Cooling Pollution degree
-35°C to 71°C 2.5%/°C 22 ~ 95%RH -40°C to +85°C IP20 Free air convection 2
MTBF
(Bellcore issue 6 @ 40°C, GB)
12V Model 24V Model 48V Model
448000 Hours 456000 Hours 490000 Hours Case material Plastic: PC, UL94-V0 Dimensions LxWxD mm(inch) 90(3.6) x 54(2.13) x 114(4.49) Weight 430g
Norms and Standards Vibration resistance
Shock resistance
UL / cUL
TUV
meet IEC 60068-2-6 (Mounting by rail: 10-500Hz, 2G, along X, Y, Z each Axis, 60 min for each Axis) meet IEC 60068-2-27 (15G, 11ms, 3 Axis, 6 faces, 3 times for each face) UL508 listed, UL60950-1, UL1310 Class 2 Power Recognized EN 60950-1, CB scheme EN 61558-1, EN 61558-2-17 (meet EN 60204)
CE
EN 61000-6-3, EN 55022 Class B, EN 61000-3-2, EN 61000-3-3, EN 61000-6-2, EN 55024, EN 61000-4-2 Level 4, EN 61000-4-3 Level 3, EN 61000-4-4 Level 4, EN 61000-4-5 L-N Level 3, L/N-FG Level 4, EN 61000-4-6 Level 3, EN 61000-4-8 Level 4, EN 61000-4-11, ENV 50204 Level 2, EN 61204-3
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 0811
2
Switching Power Supply Type SPD 100W DIN rail mounting
Block Diagrams L
Vo+
Fuse
π
Bridge Rectifier
Filter
Filter
Switching Device
Rectifier Current Detection
N
VoSingle/Paralle Select
PWM Controller OptoIsolation
Reference & Error Amp
OptoIsolation
Over Voltage Detection
Vout ADJ
Output Level Detection
DC ON (Green LED) DC LOW (Red LED) RDY (Relay Contact)
Pin Assignement and Front Controls Pin No.
Designation
Description
1
RDY
A normal open relay contact for DC ON level control Never connect
2 3, 4
V+
Positive output terminal
5, 6
V-
Negative output terminal Ground this terminal to minimize high-frequency emissions
7 8
N
Input terminals (neutral conductor, no polarity at DC input)
9
L
Input terminals (phase conductor, no polarity at DC input)
DC ON
Operation indicator LED
DC LO
DC LOW voltage indicator LED
Vout ADJ
Trimmer-potentiometer for Vout adjustment
Typ. Efficiency Curve
Derating Diagram
90
100
85
Output voltage (%)
Output voltage (%)
80 75 70 65 60 55 50
230 VAC 115 VAC
45
75
40 0
35
-35 10
25
50
75
100
61
71
Temperature (C°)
Temperature (C°)
3
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 0811
Switching Power Supply Type SPD 100W DIN rail mounting
Output Voltage (%)
Typ. Current Limited Curve
100 75 50
230 VAC 115 VAC
25 0 110
120
130
140
150
160
170
180
190
200
210
Output Current (%)
Mechanical Drawings
mm (inches)
Installation Ventilation and cooling
Screw terminals
Normal convection All sides 25mm free space for cooling is recommended 10-24AWG flexible or solid cable 8mm stripping recommend
Max. torque for screws terminals Input terminals 1.008Nm (9.0lb-in) Output terminals 0.616Nm (5.5lb-in) Plug-in connectors 10-24AWG flexible or solid cable 7mm stripping recommend Max. torque for plug-in terminals Input terminals 0.784Nm (7.0lb-in) Output terminals 0.784Nm (7.0lb-in) Recommended circuit breaker 5A / 6A / 10A B, D characteristics Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network.0811
4
Switching Power Supply Type SPD 120W DIN rail mounting t*OTUBMMBUJPOPO%*/3BJMPSNN t4IPSUDJSDVJUQSPUFDUJPO t1'$BWBJMBCMF t)JHIFGGJDJFODZ t1PXFSSFBEZPVUQVU t-&%JOEJDBUPSGPS%$QPXFS0/ t-&%JOEJDBUPSGPS%$MPX t1BSBMMFMWFSTJPOTBWBJMBCMF t$PNQBDUEJNFOTJPOT t6- D6-MJTUFEBOE567$&BQQSPWFE
Product Description
Ordering Key
The Switching power supplies SPD series are specially designed to be used in all automation
Model Mounting (D= Din rail) Output voltage Output power Input Type Optional features
where the application installation is on a DIN rail and compact dimensions and performance are a must.
SP D 24 120 1 BFP
Input type: 1= single phase
Approvals au
art geprü
f
t
B
Optional Features
y
p
e
T
d
Rheinland Product Safety y
e
appro
v
Description
Code
Plug-in connectors
Bxx
With P.F.C.
xFx
With Parallel function
xxP
Output Performances */165 70-5"(&
.0%&-/0
065165 8"55"(&
065165 70-5"(&
065165 $633&/5
&'' NJO
&'' UZQ
4JOHMF0VUQVU.PEFMT 41%
1ø 90~264 VAC
120 WATTS
+12 VDC
10 A
85%
87%
41%
1ø 90~264 VAC
120 WATTS
+24 VDC
5A
87%
94%
Output Data Line regulation Load regulation Minimum load Turn on time (full resistive load) VI nom, Io nom VI nom, Io nom 12V model with 3500 μF CAP VI nom, Io nom 24V models with 7000 μF CAP Transient recovery time Ripple and noise Output voltage accuracy Temperature coefficient Hold up time Vi Voltage fall time (I0nom Vi nom) 1
± 1% ±1% 0A 1000ms 1500ms 1500ms 2ms 100mVpp ±1% ±0.03%/°C 20ms 150ms max
Voltage fall time (I0nom Vi nom) Rated continuous loading 12V Model 24V Model Reverse voltage 12V Model 24V Model Capacitor load Vi nom Io nom 12V model Vi nom Io nom 24V model Voltage rise time Vi nom Io nom Vi nom, Io nom 12V model with 7000μF CAP 24V model with 3500μF CAP
150ms max 10A @ 12VDC/8.2A @ 14.5VDC 5A @ 24VDC/4.2A @ 28.5VDC VDC 18 VDC 35 7000μF 3500μF 500ms 500ms 500ms
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 20/03/14
Switching Power Supply Type SPD 120W DIN rail mounting
Input Data Rated input voltage Voltage range AC 115V selected AC 220V selected DC Rated input current (Vi:90VAC, Io nom) 5ZQ .BY Inrush current Vi= 115VAC
115/230 (auto selected) 90 - 132VAC 180 - 264VCA 210 - 315VDC 0.36A 0.5A
Power dissipation 12V Model 24V Model Frequency range Leakage current Input-Output Input-FG
20W 16W 47-63Hz 0.25mA 3.5mA
10A
Controls and Protections Overload Input fuse Output short circuit Power ready output on threshold &MFDUSJDBMJTPMBUJPO Contact rating at 60VDC
110-145% T2A/600VAC internal1) Hiccup mode ≥17.6-19.4VDC 500VDC 0.3A
Over voltage protection
VDC
.JO 12V Model 14.5 24V Model 30 Internal surge voltage protection Varistor
.BY 17.4 33
(IEC 61000-4-5)
1) Fuse not replaceable by user
General Data (@ nominal line, full load, 25°C) "NCJFOUUFNQFSBUVSF Derating (>61°C to +71°C) "NCJFOUIVNJEJUZ 4UPSBHF Protection degree Cooling Pollution degree
-35°C to +71°C 2.5%/C 20 - 90% RH -40°C to +85°C IP20 Free air convection 2
MTB (Bellcore issue 6 @ 40°C, GB) 12V Model 24V Model Case material Dimensions LxWxD mm(inch) Weight
527000 Hours 559000 Hours Metal 124(4.88) x 64.4(2.53) x 118.8(4.68) 800 g
Norms and Standards 7JCSBUJPOSFTJTUBODF
4IPDLSFTJTUBODF
6-D6-
567
2
meet IEC 60068-2-6 (Mounting by rail: 10-500Hz, 2G, along X, Y, Z each Axis, 60 min for each Axis) meet IEC 60068-2-27 (15G,11ms, 3 Axis, 6 faces, 3 times for each face) UL508 listed, UL60950-1, Recognized, ISA 12.12.01 (Class 1, Division 2, Groups A, B, C and D) EN 60950-1, CB scheme EN 61558-1, EN 61558-217 (meet EN 60204)
CCC $&
GB4943, GB9254, GB17625.1 EN 61000-6-3, EN 55022 Class B, EN 61000-3-2, EN 61000-3-3, EN 61000-6-2, EN 55024, EN 61000-4-2 Level 4, EN 61000-4-3 Level 3, EN 61000-4-4 Level 4, EN 61000-4-5 Level 3, L/N-FG Level 4, EN 61000-4-6 Level 3, EN 61000-4-8 Level 4, EN 61000-4-11, ENV 50204 Level 2, EN 61204-3
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 20/03/2014
Switching Power Supply Type SPD 120W DIN rail mounting
Block Diagram
Vo+
L1 L2
Vo-
L3
Vo ADJ
DC ON (Green LED) DC LOW (Red LED) RDY 1 (Relay contact)
Pin Assignement and Front Controls 1JO/P
Designation
Description
1, 2
V-
Negative output terminal
3, 4
V+
Positive output terminal
5
RDY
A normal open relay contact for DC ON level control
6
RDY
(Never connect except 24V model)
7
Grounf this terminal to minimize high-frequency emissions
8
L1
Input terminals
9
L2
Input terminals
10
L3
Input terminals
%$0/
Operation indicator LED
DC LO
DC LOW voltage indicator LED
Vout ADJ
Trimmer-potentiometer for Vout adjustment
Derating Diagram
Typ. Efficiency Curve
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 20/03/2014
3
Switching Power Supply Type SPD 120 W DIN rail mounting
Typ. Current Limited Curve
Mechanical Drawings mm (inches)
Installation Ventilation and cooling
4DSFXUFSNJOBM
.BYUPSRVFGPSUFSNJOBM Input terminal Output terminal Plug-in terminals
.BYUPSRVFGPS plug-in terminals Input terminal Output terminal
Normal convection All sides 25mm free space for cooling is recommended. 10-24AWG flexible or solid cable 8mm stripping recommend. 1.008Nm (9.0lb-in) 0.616Nm (5.5lb-in) 10-24AWG flexible or solid cable 7mm stripping recommend.
0.784Nm (7.0lb-in) 0.784Nm (7.0lb-in)
(0.27)
4
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 20/03/2014
Switching Power Supply Type SPD 240W DIN rail mounting • • • • • • • • • • •
Universal AC input full range Installation on DIN rail 7.5 or 15mm Short circuit protection PFC as standard High efficiency Power ready output LED indicator for DC power ON LED indicator for DC low Parallel connection feature Compact dimensions UL, cUL listed and TUV/CE approved
Product Description
Ordering Key
The Switching power supplies SPD series are specially designed to be used in all automation application where the installation is on a DIN rail
Model Mounting ( D = Din rail ) Output voltage Output power Input Type Optional features
and compact dimensions and performance are a must.
Approvals au
Input type: 1= single phase
art geprü
f t
B
SP D 24 240 1 B
p
e
T
d
Rheinland Product Safety
y
e
appro
v
Optional Features Description
Class I, Div 2
Code
UL 60950-1
Plug-in connectors
B
Output performances INPUT VOLTAGE
MODEL NO.
OUTPUT WATTAGE
OUTPUT VOLTAGE
OUTPUT CURRENT
EFF. (min.)
EFF. (typ.)
Single Output Models SPD24
115~230 VAC
240 WATTS
+ 24 VDC
10 A
87%
89%
SPD48
115~230 VAC
240 WATTS
+48 VDC
5A
88%
90%
Output data Line regulation Load regulation Vi nom, Single mode Io min, Io nom parallel mode Minimum load Turn on time (full resistive load) Vi nom, Io nom Vi nom, Io nom with 7000µF CAP Transient recovery time Ripple and noise Output voltage accuracy Temperature coefficient
1
± 0.5% ±1 ±5 0 1000ms 1500ms 2ms 100mVpp ± 1% ± 0.03%/°C
Hold up timeVi= 115VAC Vi= 230VAC Voltage fall time (I0nom) Rated continuous loading 24V Model 48V Model Reverse voltage 24V Model 48V Model Capacitor load Voltage rise time Vi nom Io nom Vi nom, Io nom with 7000µF CAP
25ms 30ms 150ms max 10A @ 24VDC/8.4A @ 28.5VDC 5A @ 48VDC/4.2A @ 56VDC 35VDC 63VDC 7000µF 150ms 500ms
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network . 18/04/12
Switching Power Supply Type SPD 240W DIN rail mounting
Input data Rated input voltage Voltage range AC in 115V AC in 230V DC in Rated input current (Vi : 115VAC, Io nom) Typ. Max. Inrush current Vi= 115VAC Vi= 230VAC
115 - 230
Power dissipation 24V Model 48V Model Frequency range Leakage current Input-Output Input-FG (Vi : 230VAC, Io nom)
90 - 132VAC 180 - 264VDC 210 - 375VDC 4.4/1.6mA 5.4/2.2mA
35W 32W 47- 63Hz 0.25mA 3.5mA
30A 60A
Controls and Protections Overload Input fuse Output short circuit Power ready output (only SPD 24) Threshold voltages
1)
120 – 140% T6.3/250VAC internal1) Fold forward
Over voltage protection 125-140% Internal surge voltage protection Varistor (IEC 61000-4-5)
17.6 - 19.4VDC
Fuse not replaceable by user
General Data (@ nominal line, full load, 25°C ) Ambient temperature Derating (>61°C to +71°C) Ambient humidity Storage Protection degree Cooling Pollution degree
-40°C to 71°C 2.5%/°C 20 ~ 90%RH -40°C to +85°C IP20 Free air convection 2
MTBF
(Bellcore issue 6 @ 40°C, GB)
24V Model 48V Model
423000 Hours 437000 Hours Metal
Case material Dimensions LxWxD mm(inch) Screw terminal type 124.5(4.9) x 83.5(3.29) x 123.6(4.87) Detachable connector type 143.5(5.65) x 83.5(3.29) x123.6(4.87) Weight 1380g
Norms and Standards Vibration resistance
Shock resistance
UL / cUL
TUV
CCC
meet IEC 60068-2-6 (Mounting by rail: 10-500Hz, 2G, along X, Y, Z each Axis, 60 min for each Axis) meet IEC 60068-2-27 (15G, 11ms, 3 Axis, 6 faces, 3 times for each face) UL508 listed, UL60950-1, recognized, ISA 12.12.01 (Class1, Division 2, Groups A, B, C and D) EN 60950-1, CB scheme EN 61558-1, EN 61558-2-17 (meet EN 60204) GB4943, GB9254, GB17625.1
CE
EN 61000-6-3, EN 55022 Class B, EN 61000-3-2 ClassD, EN 61000-3-3, EN 61000-6-2, EN 55024, EN 61000-4-2 Level 4, EN 61000-4-3 Level 3, EN 61000-4-4 Level 4, EN 61000-4-5 LLevel 3, L/N-FG Level 4, EN 61000-4-6 Level 3, EN 61000-4-8 Level 4, EN 61000-4-11, ENV 50204 Level 2, EN 61204-3
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12
2
Switching Power Supply Type SPD 240W DIN rail mounting
Block diagrams Vo+
Fuse
L
Inruh Current Limiter, Rectifier and Auto Select 115/230VAC
Filter
Smoothing Circuit
P.F.C Circuit
Switching Device
Rectifier Current Detection
N
VoSingle/Parallel Select
PWM Controller
Y
OptoIsolation
Reference & Error Amp.
OptoIsolation
Over Voltage Detection
Vout ADj
DC ON (Green LED)
Output Level Detection
DC LOW (Red LED) RDY (Relay Contact)
Pin Assignement and Front Controls Pin No.
Designation
Description
1
RDY
A Normal open realay contact for DC ON level control (Never connect except 24V model)
2 3, 4
V+
Positive output terminal
5, 6
V-
Negative output terminal Ground this terminal to minimize high-frquency emission
7 8
L
Input terminals (phase conductor, no polarity at DC input)
9
N
Input terminals (neutral conductor, no polarity at DC input)
DC ON
Operation indicator LED
Vout ADJ
Trimmer-potentiometer for Vout adjustment
S/P
Single/Parallel select switch
Derating Diagram
Typ. Efficiency Curve
89
75
Efficiency (%)
Output voltage (%)
100
88 87 86 85 84 83 82
230 VAC 115 VAC
81 80 0 -25
61
71
10
25
50
75
100
Temperature (C°)
3
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12
Typ. Current Limited Curve
Output Voltage (%)
100 75
230 VAC 115 VAC
50 25 0 100
110
120
130
140
150
160
Output Current (%)
Mechanical Drawings
Installation
mm (inches)
Ventilation and cooling 83.50 (3.29)
83.50 (3.29) Screw connections
Vout ADj DC LO DC ON
L N
143.50 (5.65)
Vout ADj DC LO DC ON
DC OUTPUT - - + + Rdy
124.50 (4.90)
S P
- - + + Rdy
124.50 (4.90)
S P
Normal convection All sides 25mm free space for cooling is recommended 10-24AWG flexible or solid cable 8mm stripping recommend
Max. torque for screws terminals Input terminals 1.008Nm (9.0lb-in) Output terminals 0.616Nm (5.5lb-in) 10-24AWG flexible or solid cable Plug-in connectors 7mm stripping recommend Max. torque for plug-in terminals Input terminals 0.784Nm (7.0lb-in) Output terminals 0.784Nm (7.0lb-in)
L N AC INPUT
7
9
7 116.60 (4.59)
9 7.00 (0.30)
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12
4
Switching Power Supply Type SPD 300W DIN rail mounting • Installation on DIN Rail 7.5 or 15mm • Short circuit protection • Passive PFC • Power ready relay output on 24VDC • LED indicator for DC power ON • LED indicator for DC low • Parallel function by switch • Very compact dimensions • UL, cUL listed and TUV/CE approved • Class I division 2 certification • Selv design
Product Description This SPD is the most compact 300W power supply on the market. Relay output for “power ready” parallel function and PFC are included. Performances are unique with high
Ordering Key
efficiencies and the possibility of being used up to 70°C with a little derating. Thanks to the Class I Div 2 design is suitable for installation in potentially explosive environments.
au
art geprü
1= single phase Nil= screw terminals B= Detachable connectors
f t
B
Model Mounting (D= Din rail) Output voltage Output power Input type Connection Input type: Connection:
Approvals
SP D 24 300 1 B
y
p
e
T
d
Rheinland Product Safety
e
appro
v
Output performances MODEL NO.
INPUT VOLTAGE
OUTPUT WATTAGE
OUTPUT VOLTAGE
OUTPUT CURRENT
EFF. (min.)
EFF. (typ.)
Single Output Models SPD24300
115~230 VAC
300 WATTS
+ 24 VDC
12.5 A
87%
89%
SPD48300
115~230 VAC
300 WATTS
+ 48 VDC
6.25 A
88%
90%
Output data Line regulation Load regulation Minimum load Single mode Parallel mode Turn on time (full resistive load) Vi nom, Io nom Vi nom, Io nom with 7000µF CAP Transient recovery time Ripple and noise Output voltage accuracy Temperature coefficient
1
± 0.5% ± 1% ± 1% ± 5% 1000ms 1500ms 2ms 100mVpp ± 1% ± 0.03%/°C
Hold up time Vi115/230 VAC Voltage fall time (I0nom) Rated continuous loading 24V Model 48V Model Reverse voltage 24V Model 48V Model Capacitor load Vi nom Io nom Voltage rise time Vi nom Io nom Vi nom, Io nom 12v model with 7000µF CAP
25/30 ms 150ms max 12.5A @ 24VDC/10.5A @ 28.5VDC 6.25A @ 48VDC/5.35A @ 56VDC 35VDC 63VDC 7000µF 150ms 500ms
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12
Switching Power Supply Type SPD 300W DIN rail mounting
Input data Rated input voltage Voltage range AC in 115V selected AC in 230V selected DC in Rated input current (Vi : 90/180VAC, Io nom) Typ. Max. Inrush current Vi= 115/230VAC
115 - 230VAC 90 - 132VAC 180 - 264VAC 210 - 375VDC 6.0A 3.0A
Power dissipation 24V Model 48V Model Frequency range Leakage current Input-Output Input-FG
42W 40W 47- 63Hz 0.25mA 3.5mA
35 - 65A
Controls and Protections Overload Input fuse Output short circuit Power ready output (only 24V model) On threshold Elettrical isolation Contact rating at 60vdc 1)
120-145% T8A/250VAC internal1) Fold forward
Over voltage protection 125 - 140% Internal surge voltage protection Varistor (IEC 61000-4-5)
≥17.6 -19.4VDC 500VDC 0.3A
Fuse not replaceable by user
General data (@ nominal line, full load, 25°C ) Ambient temperature Derating (>56°C to +71°C) Ambient humidity Storage Protection degree Cooling Pollution degree
-30°C to 71°C 2.5%/°C 20 ~ 90%RH -40°C to +85°C IP20 Free air convection 2
MTBF
(Bellcore issue 6 @ 40°C, GB)
24V Model 48V Model
415000 Hours 431000 Hours Case material Metal Dimensions LxWxD mm(inch) 124(4.88) x 83.5(3.29) x 123.6(4.87) Weight 1400g
Norms and Standards Vibration resistance
Shock resistance
UL / cUL
TUV
meet IEC 60068-2-6 (Mounting by rail: 10-500Hz, 2G, along X, Y, Z each Axis, 60 min for each Axis) meet IEC 60068-2-27 (15G, 11ms, 3 Axis, 6 faces, 3 times for each face) UL508 listed, UL60950-1, Recognized, ISA 12.12.01 (Class 1, Division 2, Groups A, B, C and D) EN 60950-1, CB scheme EN 61558-1, EN 61558-2-17 (meet EN 60204)
CE
EN 61000-6-3, EN 55022 Class B, EN 61000-3-2 Class D, EN 61000-3-3, EN 61000-6-2, EN 55024, EN 61000-4-2 Level 4, EN 61000-4-3 Level 3, EN 61000-4-4 Level 4, EN 61000-4-5 L-N Level 3, L/N-FG Level 4, EN 61000-4-6 Level 3, EN 61000-4-8 Level 4, EN 61000-4-11, ENV 50204 Level 2, EN 61204-3
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12
2
Switching Power Supply Type SPD 300W DIN rail mounting
Block Diagrams
Fuse
L
Inrush Current Limiter, Rectifie and Auto Select 115/230VAC
Filter N
Vo+
P. F. C. Circuit
Smoothing Circuit
Switching Device
Rectifier Current Detection
Single/Parallel Select
PWM Controller
Y
Vo-
OptoIsolation
Reference & Error Amp.
OptoIsolation
Over Voltage Detection
Vout ADJ
Output Level Detection
DC ON (Green LED) DC LOW (Red LED) RDY (Relay Contact)
Pin Assignement and Front Controls Pin No.
Designation
Description
1
RDY
A normal open relay contact for DC ON level control (Never connect except 24V model)
2 3, 4
V+
Positive output terminal
5, 6
V-
Negative output terminal Ground this terminal to minimize high-frequency emissions
7 8
L
Input terminals (phase conductor, no polarity at DC input)
9
N
Input terminals (neutral conductor, no polarity at DC input)
DC ON
Operation indicator LED
DC LO
DC LOW voltage indicator LED
Vout ADj
Trimmer-potentiometer for Vout adjustment
S/P
Single / Parallel select switch
Derating Diagram
Typ. Efficiency Curve
100
89
62,5
86 85 84 83 82
230 VAC 115 VAC
81 80 0 -30
3
Efficiency (%)
Output voltage (%)
88 87
Temperature (C°)
56
71
25
50
75
100
Power out (%)
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12
Switching Power Supply Type SPD 300W DIN rail mounting
Output voltage (%)
100
Output Voltage [%]
Typ. Current Limited Curve 100 75 50
230VAC 115VAC
25 0 110
120
130
140
150
75
160 Power Out [%]
170
180
190
200
210
230 VAC 115 VAC
50 25 0 110
100
120
130
140
150
160
Output Current (%)
Mechanical Drawings
Installation
mm (inches)
Ventilation and cooling 83.50 (3.29)
83.50 (3.29)
Rdy
124.50 (4.90)
Vout ADj.
L
DC LO DC ON
N
L
N
AC INPUT
7
9
7
116.60 (4.59)
9
143.50 (5.65)
--
DC LO DC ON
Rdy
124.50 (4.90)
++
Vout ADj.
--
S P
++
S P
Screw terminals
1
6 1
6
Max. torque for screws terminals Input terminals Output terminals Max. torque for detachable connections Input terminals Output terminals Plug-in connectors
Normal convection All sides 25mm free space for cooling is recommended 10-24AWG flexible or solid cable 8mm stripping recommend 1.008Nm (9.0lb-in) 0.616Nm (5.5lb-in)
1.008Nm (9.0lb-in) 0.616Nm (5.5lb-in) 10-24AWG flexible or solid cable 7mm stripping recommend
Max. torque for plug-in terminals Input terminals 0.784Nm (7.0lb-in) Output terminals 0.784Nm (7.0lb-in) Recommended circuit breaker 15A / 16A B, D characteristics
7.00 (0.30)
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/04/12
4
Switching Power Supply Type SPD 480W DIN rail mounting • • • • • • • • •
Universal AC single phase input full range Can also be used as bi-phase 400VAC Installation on DIN rail 7.5 or 15mm PFC as standard High efficiency up to 90% Power ready output Parallel connection feature Compact dimensions CE, TÜV, CCC approved and cULus listed
Product Description
Ordering Key
The Switching power supplies SPD series are specially designed to be used in all automation application where the
Model Mounting (D= Din rail) Output voltage Output power Input Type Optional features
installation is on a DIN rail and compact dimensions and performance are a must.
Approvals au
Input type: 1= single phase
art geprü
f t
B
SP D 24 480 1 B
p
e
T
d
Rheinland Product Safety
y
e
appro
v
Optional Features Description
Code
Plug-in connectors
B
Output performances MODEL NO.
INPUT VOLTAGE
OUTPUT WATTAGE
OUTPUT VOLTAGE
OUTPUT CURRENT
EFF. (min.)
EFF. (typ.)
Single Output Models
1)
SPD24
90~264 VAC
480 WATTS
+ 24 VDC
20 A
86%
89%
SPD48
90~264 VAC
480 WATTS
+48 VDC
10 A
87%
90%
When S/P switch is set to parallel, it is not possible to trim output voltage.
Output data Line regulation Load regulation Single mode Parallel mode Minimum load Turn on time (full resistive load) Vi nom, Io nom Vi nom, Io nom with 7000µF CAP Transient recovery time Ripple and noise Output voltage accuracy Temperature coefficient
1
± 0.5% ± 1% ± 5% 0 1000ms 1500ms 2ms 100mVpp + 1% ± 0.03%/°C
Hold up timeVi= 115/230VAC Voltage fall time (I0nom) Rated continuous loading 24V Model 48V Model Reverse voltage 24V Model 48V Model Capacitor load Voltage rise time Vi nom Io nom Vi nom, Io nom with 7000µF CAP
25-30ms 150ms max 20A @ 24VDC/16.8A @ 28.5VDC 10A @ 48VDC/8.5A @ 56VDC 35VDC 63VDC 7000µF 150ms 500ms
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 11/09/12
Switching Power Supply Type SPD 480W DIN rail mounting
Input data Rated input voltage Voltage range AC DC Rated input current (Vi : 115/230VAC, Io nom) Typ. Max. Inrush current Vi= 115/230VAC Io nom
115 - 230VAC
Power dissipation 24V Model 48V Model Frequency range Leakage current Input-Output Input-FG P.F.C Vi=115/230VAC, Ionom (Vi : 400VAC, Io nom)
90 - 264VAC 120 - 375VDC 4.9/2.5A 7/3.5A
63W 560W 47- 63Hz 0.25mA 3.5mA 0.99/0.97
25/50A
Controls and Protections Overload Input fuse Output short circuit Power ready output (only SPD 24) On threshold elettrical isolation Contact Rating at 60VDC
110 – 1405% T10A/250VAC internal Fold forward
Over voltage protection 125/140% Internal surge voltage protection Varistor (IEC 61000-4-5)
≥17.6-19.4VDC 500VDC 0.3A
General data (@ nominal line, full load, 25°C ) Ambient temperature Derating (>61°C to +71°C) Ambient humidity Storage Protection degree Cooling Pollution degree
-40°C to 71°C 2.5%/°C 20 ~ 95%RH -40°C to +85°C IP20 Free air convection 2
MTBF
(Bellcore issue 6 @ 40°C, GB)
24V Model 48V Model
403000 Hours 416000 Hours Case material Metal Dimensions LxWxD mm (inch) 124.5 (4.9) x 175.5 (6.91) x 123.6 (4.87) Weight 1920g
Norms and Standards Vibration resistance
Shock resistance
UL / cUL
TUV
meet IEC 60068-2-6 (Mounting by rail: 10500Hz, 2G, along X, Y, Z each Axis, 60 min for each Axis). meet IEC 60068-2-27 (15G, 11ms, 3 Axis, 6 faces, 3 times for each face). UL508 listed, UL60950-1 Recognized, ISA 12.12.01 (Class 1, Division 2, Groups A, B, C and D). EN 60950-1, CB scheme EN 61558-1, EN 61558-2-17 (meet EN 60204).
CCC CE
GB4943, GB9254, GB17625.1. EN 61000-6-3, EN 55022 Class B, EN 61000-3-2 Class D, EN 61000-3-3, EN 61000-6-2, EN 55024, EN 61000-4-2 Level 4, EN 61000-4-3 Level 3, EN 61000-4-4 Level 4, EN 61000-4-5 L-N Level 3, L/N-FG Level 4, EN 61000-4-6 Level 3, EN 61000-4-8 Level 4, EN 61000-4-11, ENV 50204 Level 2, EN 61204-3.
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 11/09/12
2
Switching Power Supply Type SPD 480W DIN rail mounting
Block diagrams
L1
Fuse1
L2
Fuse2
L3
Fuse3
Vo+
x Filter
Bridge Rectifier
x
π Filter
P.F.C Circuit
Switchong Device
Rectifier Current Detection
x
π Filter Vo+ Single / Parallel Select
PWM Controller
Y
OptoIsolation
Reference & Error Amp. Vout ADj
Over Voltage Detection
OptoIsolation
Continuos / Discontinuos DC ON
M.C.U
DC LOW RDY
Pin Assignement and Front Controls Pin No.
Designation
Description
1, 2
V-
Negative output teminal
3, 4
V+
Positive output terminal
5
RDY
A normal open relay contact for DC ON level control (Never connect except 24V model)
6 7
L
Input terminals (phase conductor, no polarity at DC input)
8
N
Input terminal (neutral conductor, no polarity at DC input) Ground this terminal to minimize high-frequency emissions
9 DC ON
Operation indicator LED
DC LO
DC LOW voltage indicator LED
Vout ADJ
Trimmer-potentiometer for Vout adjustment
S/P
Single / Paralle select switch
Typ. Efficiency Curve
Derating Diagram
90 100 Efficiency (%)
Output voltage (%)
85 75
75 230 VAC 115 VAC
70 65
0 -25
3
80
61 Temperature (C°)
71
10
25
50
75
100
Power Out (%)
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 11/09/12
Switching Power Supply Type SPD 480W DIN rail mounting
Output Voltage (%)
Typ. Current Limited Curve
100 75
230 VAC 115 VAC
50 25 0 100
110
120
140
150
160
Output Current (%)
Mechanical Drawings
mm (inches)
Installation Ventilation and cooling
Connector
Input Connector
Normal convection All sides 25mm free space for cooling is recommended. Size range AWG 24-10 (0.2~4mm²) flexible/solid cable. can withstand torque at maximum 9 pound-inches.
Output Connector
Max. torque for screws terminals Input terminals Output terminals
can withstand torque at maximum 5.5 poundinches. 8 mm strip ping at cable end recom mends, use copper conductors only, 60/75°C.
0.784Nm (7.0lb-in) 0.784Nm (7.0lb-in)
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 11/09/12
4
Switching Power Supply Type SPD 100W Bi-Phase DIN rail mounting · Installation on DIN Rail 7.5 or 15mm · Short circuit protection · Input single phase 340 to 575VAC · Passive PFC · Power ready output on 24VDC · LED indicator for DC power ON · LED indicator for DC low · Standard parallel function · Very compact dimensions · UL, cUL listed and TUV/CE approved · Class I div2 certification (in progress)
Product Description
Ordering Key
This particular SPD is the most compact 100W power supply on the market. Relay output for “power ready” parallel function and PFC are included. Performances are unique with high efficiencies
Model Mounting ( D = Din rail ) Output voltage Output power Input type
and the possibility of being used up to 70°C with a little derating. Furthermore it can be powered with 2 phases of a 3 phase grid system due to its high voltage input.
SP D 24 100 2
Input type: 2= single phase high voltage (bi-phase)
Approvals au B
art geprü
f
Rheinland P r o d u c t
S a f e t y
yp e
v appro
Output Performances Model SPD12100 SPD24100 SPD48100
Rated output Voltage (VDC) 12 24 48
Output Power (W) 100.8 100.8 100.8
Voltage Trim Range DC ON LED (VDC) Output 0.8 Io nom Threshold at startup Current (A) Min. VDC Max. VDC Min. Max. 8.4 11.4 14.5 10 11.2 4.2 22.5 28.5 17.6 19.4 2.1 47.0 56.0 37.0 43.0
DC LO LED (VDC) Threshold after startup Min. Max. 10 11.2 17.6 19.4 37.0 43.0
Typical Efficiency 86% 87% 89%
Output Data Output voltage accuracy Line regulation Load regulation Non parallel model Parallel model Temp. coefficient Ripple and noise Vi nom, Io nom, BW=20MHz Rated continuous Loading
-0 +1% max (factory adjusted) ± 1% ± 1% ± 5% ± 0.03% / °C 50mV 8.4A @ 12VDC / 6.9A @14.5VDC 4.2A @ 24VDC / 3.5A @ 28.5VDC 2.1A @ 48VDC / 1.8A @ 56VDC 150ms
Fall Time Transient recovery time 2ms Vi nom , Io= 0.5 x Inom Turn On Time Vi nom, I o nom 1.0s Vi nom, I o nom with Capacitor load 1.5s
1
Rise Time Vi nom, I o nom V i nom, Io nom with Capacitor load Capacitor Load 12V, 24V versions 48V version Reverse Voltage Immunity 12V 24V 48V Hold up Time Vi nom Io max Minimum load Vi nom Parallel Operation 0.1 Io min~0.9 Io max
150ms 500ms 7000µF 3500µF 18V 35V 63V 20ms 0% 2 units max.
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. - 0940
Switching Power Supply Type SPD 100W Bi-phase DIN rail mounting
Input Data Rated input voltage Voltage range AC in DC in Rated input current Power dissipation 12V 24V 48V
400/500VAC
Frequency range 47 - 63Hz Internal Voltage Surge Protection Varistor
340 - 575VAC 480 - 820VDC 0.48A / 0.75A
(acc. to IEC61000-4-5)
Leakage Current Input / Output Input / FG Inrush current P.F.C.
15.0W 13.0W 10.5W
0.25mA 3.5mA 10A 0.55
Controls and Protections Input Fuse Output Short Circuit Rated Overload Protection Over voltage protection (auto recovery) 12V model 24V model 48V model
2A/600VAC internal1) current limit
Input Voltage Surge Protection Varistor Power ready (only SPD241002) Threshold at start up Min. 17.6VDC - Max.19.4VDC
115 - 135%
(contact closed)
Contact rating at 60VDC Insulation
14.5V to 17.4V 30.0V to 33.0V 60.0V to 66.0V
0.3A 500VDC
Fuse not replaceable by user
General Data (@ nominal line, full load, 25°C ) Ambient temperature Derating (>61°C to +71°C) Ambient humidity Storage Pollution degree Protection degree Cooling Switching frequency
-25°C to 71°C 2.5% / °C 20 to 95%RH -25°C to +85°C 2 IP20 Free air convection 45kHz
MTBF (Bellcore Issue 6@40°C), GB 12V model 622.000h 24V model 661.000h 48V model 672.000h Altitude during operation 3.000m Case material Plastic Dimensions L x W x D 90 x 54 x 114mm Weight 500g
Approvals and EMC Insulation voltage Input / Output Input / FG Insulation resistance
CE
EN 61000-6-3, EN 55022 Class B, EN 61000-3-2, EN 61000-3-3 EN 61000-6-2, EN 55024, EN 61000-4-2 Level 4, EN 61000-4-3 Level 3 EN 61000-4-4 Level 4, EN 61000-4-5 L-N Level 3, L / N-FG Level 4 EN 61000-4-6 Level 3, EN 61000-4-8 Level 4, EN 61000-4-11 ENV 50204 Level 2, EN 61204-3
3.000VAC / 4242VDC 1500VAC / 2121VDC 100M∧ min acc. to IEC 60068-2-27
Shock resistance
(15G, 11ms, 3 Axis, 6 Faces, 3 times for each Face)
acc. to IEC 60068-2-6
Vibration resistance
(Mounting by rail: 10-500 Hz, 2G, along X, Y, Z each Axis, 60 min for each Axis)
UL / cUL
UL 508 Listed UL 60950-1, Recognized ISA 12.12.01 (Class I, Division 2, Groups A, B, C and D in progress) EN 60950-1, CB scheme EN 61558-1, EN 61558-2-17 (acc.to EN 60204)
TUV
0940 S
ifi ti
bj t t
h
ith t
ti
Pi t
j t
l F
i lf t
d/
t
i ti
l
kt
l
t
k
2
Switching Power Supply Type SPD 100W Bi-phase DIN rail mounting
Block Diagrams
L1
Fuse1
Vo +
X
N ( L2)
Bridge Rectifier
Filter
Filter
P.F.C Circuit
Switching
Device
Rectifier
Current Detection
X
PWM Controller Y
Vo -
Opto Isolation
Reference & Error Amp.
Opto Isolation
Over Voltage Detection
Single / Parallel Select Vout ADJ.
Output Level Detection
DC ON ( Green LED) DC LOW ( Red LED) RDY 1) ( Relay Contact)
1) only for SPD241002
Pin Assignment and Front Controls Pin No.
Designation
1 2 3 4 5 6 7 8 9
RDY RDY V+ V+ VVGND N or L2 L1
NO relay contact for DC OK (only SPD241002) NO relay contact for DC OK (only SPD241002) Positive output terminal Positive output terminal Negative output terminal Negative output terminal Ground terminal to minimise High frequency emissions Neutral or phase 2 (no polarity with DC input) Phase 1 (no polarity with DC input)
L1 L2 POT1 SW1
DC ON DC LO Vout ADJ. S/P
DC output ready LED DC low indicator LED Trimmer for fine output voltage adjustment Single / Parallel select switch
Description
Typ. Current Limited Curve SPD241002 / 400VAC
SPD241002 / 500VAC
Hiccup mode
Hiccup mode
100
Output Voltage (%)
Output Voltage (%)
100
75
50
25
0
50
25
0 110
120
130
140
150
Power Out (%)
3
75
160
170
110
120
130
140
150
160
170
Power Out (%)
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. - 0940
Switching Power Supply Type SPD 100W Bi-phase DIN rail mounting
Derating Diagram
100 90 80 70 60 50 40 30 20 10 0
95 90 85 80
Power out (%)
Efficiency [%]
Typ. Efficiency Curve
75 70 65 60 55 50 45 40 10
500 Vac 400 Vac
25
50
75
-25/ -13
100
Power Out [%]
-20/ -4
-15/ -5
-10/ 14
+55/ +60/ +65/ +70/ +75/ +80/ 131 140 149 158 167 176
Temperature °C / °F
Mechanical Drawings
mm (inches)
54.00 [2.13]
SW1
+71/ 159.8
114 [4.49]
654321
Rdy
POT1
S/P Vout A D J. DC LO DC O N
90.0 [3.6]
L2
L1
7
N
L
8
9
Installation Ventilation and cooling
Screw terminals
Normal convection All sides 25mm free space for cooling is recommended 10-24AWG flexible or solid cable 8mm stripping recommend
Max. torque for screws terminals Input terminals 1.008Nm (9.0lb-in) Output terminals 0.616Nm (5.5lb-in) Plug-in connectors 10-24AWG flexible or solid cable 7mm stripping recommend Max. torque for plug-in terminals Input terminals 0.784Nm (7.0lb-in) Output terminals 0.784Nm (7.0lb-in) Recommended circuit breaker 3A / 5A / 6A B, D characteristics
0940 - Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network.
4
Switching Power Supply Type SPD 120W 3 phases DIN rail mounting · · · · · · · ·
Universal AC 3 phases input full range Can also be used as single phase 480VAC Installation on DIN rail 7.5 or 15mm PFC as standard High efficiency up to 88% Power ready output Compact dimensions UL, cUL listed and TUV/CE
Product Description
Ordering Key
The Switching power supplies SPD series are specially designed to be used in all automation application where the
Model Mounting ( D = Din rail ) Output voltage Output power Input Type
installation is on a DIN rail and compact dimensions and performance are a must.
Approvals
Input type:
SP D 24 120 3
3 = three phase (or single phase 400/500VAC 3))
aua r t g e p r ü f B
Rheinland P r o d u c t
S a f e t y
yp e
v appro
Output performances
1)
Model
Rated output Voltage (VDC)
Output Power (W)
SPD12 SPD24
12 24
120 120
Output Voltage Trim Range Current (A)1) Min. VDC Max. VDC 10 (7.5) 11.4 14.5 5 (3.75) 22.5 28.5
DC OK Thereshold at startup (VDC) Min. Max. 10.0 11.2 17.6 19.4
DC low LED Thereshold after startup(VDC) Min. Max. 10.0 11.2 17.6 19.4
Typical Efficiency 87% 88%
When powered with three phases input; with biphase input value is in the brackets.
Output data Line regulation Load regulation Ouput Voltage accuracy Ripple and Noise
± 1% ± 1% from 0 to +1% (factory adjusted) 100mV
Temperature Coefficient Hold up time Vi = 230VAC Minimum load Parallel Operation
+0.02% / °C 20ms 0% NO
Frequency range Inrush current P.F.C. Vi= 500VAC, Io nom.
47- 63 Hz 10A 0.6
Input data Rated input voltage Voltage range AC in DC in Rated input current (380/500) 3)
1
400/500VAC 340 - 575VAC 3) 480 - 820VDC 0.5A / 0.35A
Biphase or triphase input (biphase can be: L1 L2, L2 L3 or L1 L3. Note: when used as biphase, the maximum output power is 75% of rated power.
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. - 0841
Switching Power Supply Type SPD 120W 3 phases DIN rail mounting
Controls and Protections Input Fuse 1.0A/600VAC internal/phase4) Overvoltage ProtectionSPD12 14.5 – 17.4VDC SPD24 30 – 33VDC Output Short Circuit Current limit Continous Rated Overload Protection 115 - 135% 4)
Power ready output (only SPD 24) 17.6 - 19.4VDC Threshold voltages 0.3A Contact rating at 60VDC 500VDC insulation Overtemperature 100 - 110°C (shutdown with auto-restart when temperature is back to normal)
Not replaceable by user.
General data (@ nominal line, full load, 25°C ) Ambient temperature Derating (>61°C to +71°C) Ambient humidity Storage temperature Dimensions L x W x D Screw terminal type
-25°C to 71°C 2.5%/°C 20 - 95%RH -25°C to +85°C
Cooling MTBF (MIL-HDBK-217F) Case material Weight Protection degree
Free air convection n.a. Metal (powder painted aluminium) 800g / 28.22oz IP20
123.6 x 74.3 x 112 mm 4.87 x 2.93 x 4.41 inches
Approvals and EMC Insulation voltage I/O Insulation resistance I/O @ 500VDC UL / cUL
3.000VAC
CE
EN61000-6-3 EN55022 class B EN61000-3-2 EN61000-3-3 EN61000-6-2 EN55024
100M∧ UL508 listed, UL60950-1, Recognized EN60950-1
TUV
Block diagrams L1
Fuse1
L2
Fuse2
L3
Vo+
X Filter
Bridge Rectifier
X
Fuse3
Filter
P.F.C. Circuit
Switching Device
Rectifier Current Detection
X
VoSingle/Parallel Select
PWM
Y
Controller
OptoIsolation
Reference & Error Amp.
Opto-
OverVoltage
Isolation
Detection
Vout Adj.
Output
DCON (Green LED)
Level Detection
DCLOW (Red LED) RDY 1) (Relay Contact)
Note: 1) For 24V Model only
0841 - Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network.
2
Switching Power Supply Type SPD 120W 3 phases DIN rail mounting
Pin assignement and front controls Pin No.
Designation
1 2 3 4 5 6 7 8 9 10
V+ V+ VVGND L1 L2 L3 RDY RDY DC ON DC LO Vout ADJ.
Description Positive output terminal Positive output terminal Negative output terminal Negative output terminal Ground terminal to minimise High frequency emissions Input terminals Input terminals Input terminals A normal open relay contact for DC ON level control A normal open relay contact for DC ON level control DC output ready LED DC low indicator LED Trimmer for fine output voltage adjustment
Installation
Derating Diagram
Ventilation and cooling
Normal convection All sides 25mm free space for cooling is recommended 10-24AWG flexible or solid cable 8mm stripping recommend
Screw connections
Max. torque for screws terminals Input terminals 1.008Nm (9.0lb-in) Output terminals 0.616Nm (5.5lb-in)
Power out (%) 100 90 80 75 70 60 50 40 30 20 10 0 -25/ -13
-20/ -4
-15/ -5
-10/ 14
+50/ +55/ +60/ +65/ +70/ +75/ 122 131 140 149 158
Temperature °C / °F
+61/ 141.8
+71/ 159.8
Mechanical Drawings mm/inches 112.0 74.3
106.6
9 10 1
6.8
4
123.6
++
L1 L2 L3
5 8
3
Specifications are subject to change without notice Pictures are just an example For special features and/or customization please ask to our sales network - 0841
167
Switching Power Supply Type SPD 240W 3 phases DIN rail mounting · · · · · · · ·
Universal AC 3 phases input full range Installation on DIN rail 7.5 or 15mm PFC as standard High efficiency up to 90% Power ready output Parallel connection feature Compact dimensions UL, cUL listed and TUV/CE
Product Description
Ordering Key
The Switching power supplies SPD series are specially designed to be used in all automation application where the
Model Mounting ( D = Din rail ) Output voltage Output power Input Type
installation is on a DIN rail and compact dimensions and performance are a must.
Approvals
Input type:
SP D 24 240 3
3 = three phase (or single phase 400/500VAC 3))
aua r t g e p r ü f B
Rheinland P r o d u c t
yp
e
S a f e t y
v appro
Output performances
1) 2)
Model
Rated output Voltage (VDC)
Output Power (W)
SPD24 SPD48
24 48
240 240
Output Voltage Trim Current Range 2) 1) (A) Min. VDC Max. VDC 10 (7.5) 22.5 28.5 5 (3.75) 47.0 56.0
DC OK Thereshold at startup (VDC) Min. Max. 17.6 19.4 37.0 43.0
DC low LED Thereshold after startup(VDC) Min. Max. 17.6 19.4 37.0 43.0
Typical Efficiency 89% 90%
When powered with three phases input; with biphase input value is in the brackets. When S/P switch is set to parallel, it is not possible to trim output voltage.
Output data Line regulation Load regulation Parallel mode Non parallel mode Ouput Voltage accuracy Ripple and Noise
± 1% ± 5% ± 1% from 0 to +1% (factory adjusted) 100mV
Temperature Coefficient Hold up time Vi = 230VAC Minimum load Parallel Operation (only with S/P switch on “P” position)
+0.02% / °C 20ms 0% 2 units max.
Frequency range Inrush current P.F.C. (Vi= 500VAC, Io nom.)
47- 63 Hz 10A 0.6
Input data Rated input voltage Voltage range AC in DC in Rated input current (380/500) 3)
1
400/500VAC 340 - 575VAC 3) 480 - 820VDC 0.85A / 0.7A
Biphase or triphase input (biphase can be: L1 L2, L2 L3 or L1 L3. Note: when used as biphase, the maximum output power is 75% of rated power.
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. - 0819
Switching Power Supply Type SPD 240W 3 phases DIN rail mounting
Controls and Protections Input Fuse 2.0A/600VAC internal/phase4) Overvoltage ProtectionSPD24 30 – 33VDC SPD48 60 – 68VDC Output Short Circuit Current limit Continous Rated Overload Protection 115 - 135% 4)
Power ready output (only SPD 24) Threshold voltages 17.6 - 19.4VDC Contact rating at 60VDC 0.3A insulation 500VDC Overtemperature 100 - 110°C (shutdown with auto-restart when temperature is back to normal)
Not replaceable by user.
General data (@ nominal line, full load, 25°C ) Ambient temperature Derating (>61°C to +71°C) Ambient humidity Storage temperature Dimensions L x W x D Screw terminal type
-25°C to 71°C 2.5%/°C 20 - 95%RH -25°C to +85°C
Cooling MTBF (MIL-HDBK-217F) Case material Weight Protection degree
Free air convection n.a. Metal (powder painted aluminium) 1.1Kg / 38,80oz IP20
123.6 x 89.0 x 110.7 mm 4.87 x 3.50 x 4.36 inches
Approvals and EMC Insulation voltage I/O Insulation resistance I/O @ 500VDC UL / cUL
CE
3.000VAC
EN61000-6-3 EN55022 class B EN61000-3-2 EN61000-3-3 EN61000-6-2 EN55024
100M& UL508 listed, UL60950-1, Recognized EN60950-1
TUV
Block diagrams L1
Fuse1
L2
Fuse2
L3
Fuse3
Vo+
X Filter
Bridge Rectifier
X
Filter
P.F.C. Circuit
Switching Device
Rectifier Current Detection
X
Vo Single/Parallel
PWM
Y
Controller
Select Opto Isolation
Reference & Error Amp.
Opto -
OverVoltage
Vout Adj.
Isolation
Detection Output
DCON (Green LED)
Level Detection
DCLOW (Red LED) RDY 1) (Relay Contact)
Note: 1) For 24V Model only
0819 - Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network.
2
Switching Power Supply Type SPD 240W 3 phases DIN rail mounting
Pin assignement and front controls Pin No.
Designation
1 2 3 4 5 6 7 8 9 10
V+ V+ VVGND L1 L2 L3 RDY RDY DC ON DC LO Vout ADJ. S/P
Description Positive output terminal Positive output terminal Negative output terminal Negative output terminal Ground terminal to minimise High frequency emissions Input terminals Input terminals Input terminals A normal open relay contact for DC ON level control A normal open relay contact for DC ON level control DC output ready LED DC low indicator LED Trimmer for fine output voltage adjustment Single / Parallel select switch
Installation
Derating Diagram
Ventilation and cooling
Normal convection All sides 25mm free space for cooling is recommended 10-24AWG flexible or solid cable 8mm stripping recommend
Screw connections Max. torque for screws terminals Input terminals Output terminals
1.008Nm (9.0lb-in) 0.616Nm (5.5lb-in)
Power out (%) 100 90 80 75 70 60 50 40 30 20 10 0 -25/ -13
-20/ -4
-15/ -5
-10/ 14
+50/ +55/ +60/ +65/ +70/ +75/ 122 131 140 149 158
Temperature °C / °F
+61/ 141.8
167
+71/ 159.8
Mechanical Drawings mm/inches 110.7 105.3
L1 L2 L3
5
3
8
++
1 89.0
112.0
123.6
9 10
Rdy
4
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. - 0819
Switching Power Supply Type SPD 480W 3 phases DIN rail mounting · · · · · · · · ·
Universal AC 3 phases input full range Can also be used as single phase 480VAC Installation on DIN rail 7.5 or 15mm PFC as standard High efficiency up to 91% Power ready output Parallel connection feature Compact dimensions UL, cUL listed and TUV/CE
Product Description
Ordering Key
The Switching power supplies SPD series are specially designed to be used in all automation application where the
Model Mounting ( D = Din rail ) Output voltage Output power Input Type
installation is on a DIN rail and compact dimensions and performance are a must.
Approvals
Input type:
SP D 24 480 3
3 = three phase (or single phase 400/500VAC 3))
aua r t g e p r ü f B
Rheinland P r o d u c t
yp
e
S a f e t y
v appro
Output performances Model
Rated output Voltage (VDC)
Output Power (W)
SPD24 SPD48 1) 2)
Output Voltage Trim Current Range 1) 1) (A) Min. VDC Max. VDC 20 (15) 22.5 28.5 10 (7.5) 47.0 56.0
DC OK Thereshold at startup (VDC) Min. Max. 17.6 19.4 37.0 43.0
DC low LED Thereshold after startup(VDC) Min. Max. 17.6 19.4 37.0 43.0
Typical Efficiency 90% 91%
When powered with three phases input; with biphase input value is in the brackets. When S/P switch is set to parallel, it is not possible to trim output voltage.
Output data Line regulation Load regulation Non parallel mode Parallel mode Ouput Voltage accuracy Ripple and Noise
± 1% ± 1% ± 5% from 0 to +1% (factory adjusted) 100mV
Temperature Coefficient Hold up time Vi = 230Vac Minimum load Parallel Operation (only with S/P switch on “P” position)
+0.02% / °C 20ms 0% 2 units max.
Frequency range Inrush current P.F.C. Vi= 500VAC, Io nom.
47- 63 Hz 15A 0.7
Input data Rated input voltage Voltage range AC in DC in Rated input current (380/500) 3)
1
400/500VAC 340 - 575VAC 3) 480 - 820VDC 1.4A / 1.0A
Biphase or triphase input (biphase can be: L1 L2, L2 L3 or L1 L3. Note: when used as biphase, the maximum output power is 75% of rated power.
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. - 0819
Switching Power Supply Type SPD 480W 3 phases DIN rail mounting
Controls and Protections Input Fuse 3.15A/250VAC internal/phase4) Overvoltage ProtectionSPD24 30 – 33VDC SPD48 60 – 68VDC Output Short Circuit Continous Current limit Discontinous Delay 3s shut-down, after 30s Auto-restart 115 - 135% Rated Overload Protection
Power ready output (only SPD 24) Threshold voltages 17.6 - 19.4VDC Contact rating at 60Vdc 0.3A insulation 500VDC Overtemperature 100 - 110°C (shutdown with auto-restart when temperature is back to normal)
Not replaceable by user.
General data (@ nominal line, full load, 25°C ) Ambient temperature Derating (>61°C to +71°C) Ambient humidity Storage Dimensions L x W x D Screw terminal type
-25°C to 71°C 2.5%/°C 20 - 95%RH -25°C to +95°C
Cooling MTBF (MIL-HDBK-217F) Case material Weight Protection degree
Free air convection n.a. Metal (powder painted aluminium) 1750g / 61.73oz IP20
124 x 150 x 118 mm 1.88 x 5.91 x 4.65 inches
Approvals and EMC Insulation voltage I/O Insulation resistance I/O @ 500VDC UL / cUL
CE
3.000VAC
EN61000-6-3 EN55022 class B EN61000-3-2 EN61000-3-3 EN61000-6-2 EN55024
100M& UL508 listed, UL60950-1, Recognized EN60950-1
TUV
Block diagrams
L1
Fuse1
L2
Fuse2
L3
Fuse3
Vo +
X Filt e r
Br idge Rectifier
X
Filt e r
P.F.C Circuit
Sw it ching D e v i ce
Rect ifier
Filter
C ur r ent
X
Vo -
D etection PW M C o nt r o lle r
Y
Si n gl e / Par al l e l O pto I so l at i o n
Se l e ct
Refer ence & Er r or A m p.
O pto -
V o u t A D J.
O ver Voltage D etection
I so l at i o n
C ontinuous / D iscontinuous M .C .U
0819 S
ifi ti
bj t t
h
ith t
ti
Pi t
j t
l F
i lf t
d/
t
i ti
DC ON D C LO W RD Y
l
kt
l
t
k
2
Switching Power Supply Type SPD 480W 3 phases DIN rail mounting
Pin assignement and front controls Pin No.
Designation
1 2 3 4 5 6 7 8 9 10
+ + GND L1 L2 L3 RDY RDY DC ON DC LO Vout ADJ. S/P C/D
Description Positive output terminal Positive output terminal Negative output terminal Negative output terminal Ground terminal to minimise High frequency emissions Input terminals Input terminals Input terminals A normal open relay contact for DC ON level control A normal open relay contact for DC ON level control DC output ready LED DC low indicator LED Trimmer for fine output voltage adjustment Single / parallel selection switch Continous / Discontinous
Installation
Derating Diagram
Ventilation and cooling
Normal convection All sides 25mm free space for cooling is recommended 10-24AWG flexible or solid cable 8mm stripping recommend
Screw connections Max. torque for screws terminals Input terminals Output terminals
1.008Nm (9.0lb-in) 0.616Nm (5.5lb-in)
Power out (%) 100 90 80 75 70 60 50 40 30 20 10 0 -25/ -13
-20/ -4
-15/ -5
-10/ 14
+50/ +55/ +60/ +65/ +70/ +75/ 122 131 140 149 158
Temperature °C / °F
+61/ 141.8
167
+71/ 159.8
Mechanical Drawings mm/inches 10 9 P 111.3 (4.38) 150 (5.91)
6.9 (0.27)
RDY
106.6 (4.2)
S/P
RDY
123.6 (4.87)
C/D
++
L1 L2 L3
5
3
8
1
4
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. - 0819
Switching Power Supply Type SPD 960W 3 phases DIN rail mounting · · · · · · · · ·
Universal AC 3 phases input full range Can also be used as bi-phase 960VAC Installation on DIN rail 7.5 or 15mm PFC as standard High efficiency up to 93% Power ready output Parallel connection feature (except “L” version) Compact dimensions UL, cUL listed and TUV/CE
Product Description
Ordering Key
The Switching power supplies SPD XX9603 series are suitable for those applications where high DC power is required. Besides
Model Mounting (D= Din rail) Output voltage Output power Input Type Option Input type:
the PFC as standard, it also features the parallel connection with active current sharing on the high end versions.
Approvals
Option:
aua r t g e p r ü f B
SP D 24 960 3 L
3 = three phase (or single phase 400/500VAC 3)) Nil = standard version L = without active current sharing feature
Rheinland P r o d u c t
S a f e t y
yp e
v appro
Output performances MODEL NO.
INPUT VOLTAGE
OUTPUT WATTAGE
SPD24
3ø 340~575 VAC
960 WATTS
SPD24...L
3ø 340~575 VAC
SPD48
3ø 340~575 VAC
OUTPUT VOLTAGE
OUTPUT CURRENT
EFF. (min.)
EFF. (typ.)
+ 24 VDC
40 A
90%
92%
960 WATTS
+ 24 VDC
40 A
90%
92%
960 WATTS
+ 48 VDC
20 A
91%
93%
Single Output Models
Output data Line regulation Load regulation Single mode Parallel mode Minimum load Turn on time (full resistive load) Vi nom, Io nom Vi nom, Io nom with 7000µF CAP Transient recovery time Ripple and noise Output voltage accuracy Temperature coefficient
1
± 0.5% ± 1% ± 5% 0 1000ms 1500ms 2ms 80mVpp + 1% ± 0.03%/°C
Hold up time Vi nom ,Io nom Voltage fall time (I0nom) Rated continuous loading 24V Model 48V Model Reverse voltage 24V Model 48V Model Capacitor load Voltage rise time Vi nom Io nom Vi nom, Io nom with 7000µF CAP
15ms 150ms max 40A @ 24VDC/33.8A @ 28.5VDC 20A @ 48VDC/17A @ 56VDC 35VDC 63VDC 7000µF 150ms 500ms
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 0811
Switching Power Supply Type SPD 960W 3 phases DIN rail mounting
Input data Rated input voltage Voltage range AC DC Rated input current (Vi: 340VAC, Io nom) Typ. Inrush current Vi nom, Io nom 24V/48V models Cold start 24L model
400 - 500VAC 340 - 575VAC 480 - 820VDC 2.4A
Power dissipation Vi: 400 VAC, Io nom 24V Model 48V Model Frequency range Leakage current Input-Output Input-FG
98W 55W 47- 63Hz 0.25mA 3.5mA
30 - 35A 50 - 60A
Controls and Protections Overload Input fuse Output short circuit Power ready output (only 24V model) On threshold Elettrical isolation
120-140% T5A/500VAC internal/phase Hiccup mode ε17.6 -19.4VDC 500VDC
Contact rating at 60vdc Over voltage protection
0.3A
VDC Min. Max. 24V Model 30 33 48V Model 60 68 Internal surge voltage protection Varistor (IEC 61000-4-5)
General data (@ nominal line, full load, 25°C ) Ambient temperature Derating (>61°C to +71°C) Ambient humidity Storage Protection degree Cooling Pollution degree
-40°C to 71°C 3.5%/°C 20 ~ 90%RH -40°C to +85°C IP20 Free air convection 2
MTBF
(Bellcore issue 6 @ 40°C, GB)
24V Model 24L Model 48V Model
352000 Hours 381000 Hours 390000 Metal Case material Dimensions LxWxD mm(inch) 126.2(4.97)x275.8(10.86)x118.8(4.68) Weight 3400g
Norms and Standards Vibration resistance
Shock resistance
UL / cUL
TUV
meet IEC 60068-2-6 (Mounting by rail: 10-500Hz, 2G, along X, Y, Z each Axis, 60 min for each Axis) meet IEC 60068-2-27 (15G, 11ms, 3 Axis, 6 faces, 3 times for each face) UL508 listed, UL60950-1, Recognized, ISA 12.12.01 (Class 1, Division 2, Groups A, B, C and D) EN 60950-1, CB scheme EN 61558-1, EN 61558-2-17 (meet EN 60204)
CCC CE
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 0811
GB4943, GB9254, GB17625.1 EN 61000-6-3, EN 55022 Class B, EN 61000-3-2, EN 61000-3-3, EN 61000-6-2, EN 55024, EN 61000-4-2 Level 4, EN 61000-4-3 Level 3, EN 61000-4-4 Level 4, EN 61000-4-5 L-N Level 3, L/N-FG Level 4, EN 61000-4-6 Level 3, EN 61000-4-8 Level 4, EN 61000-4-11, ENV 50204 Level 2, EN 61204-3
2
Switching Power Supply Type SPD 960W 3 phases DIN rail mounting
Block diagrams
L1
Fuse 1
L2
Fuse 2
Filter
L3
Vo+
Filter
Bridge Rectifier
P.F.C Circuit
Filter
Switching Device
Rectifier
Fuse 3
PWm Controller
Current Detection
Vo-
Reference & Error Amp. Vout ADj.
Bias Power
Parallel Controller
Output Level Detection
Pin Assignement and Front Controls Pin No.
Designation
Description
1, 2
V-
Negative output teminal
3, 4
V+
Positive output terminal
5
G
Parallel GND PIN for current share
6
P
Parallel PIN for current share
7
RDY
A normal open relay contact for DC ON level control
8
(Never connect except 24V model)
9
L3
Input terminals
10
L2
Input terminals
11
L1
Input terminal
12
3
Ground this terminal to minimize high-frequency emission DC ON
Operation indicator LED
DC LO
DC LOW voltage indicator LED
Vout ADj
Trimmer-potentiometer for Vout adjustment
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 0811
Parallel
DC ON (Green LED) DC LOW (Red LED) RDy 1) (Relay Contact)
Parallel Connection
Derating Diagram
Typ. Efficiency Curve 95
100
EFFICIENCY (%)
Power out (%)
90 65
85 80 75 70
0 -40
61
71
10
25
Output Current (%)
50 Power out (%)
75
100
Typ. Current Limited Curve 125
Output Voltage (%)
100
75
50
Hiccup mode
entering hiccup mode after 5~10 sec of output overload
Continuos
25
0 20
40
60
80
100 120 135 Output Current (%)
150
170
190
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 0811
4
Mechanical Drawings mm/inches
Installation Ventilation and cooling
275.80 (10.86)
126.20 (4.97)
Conductors sections From Pin1 to Pin4
L1 L2 L3
DC DC LO ON
Rdy
Vout ADj
12 11 10 9
87654
32
From Pin9 to Pin12
10-24AWG (0.2-4mm2) flexible or solid cable 8mm stripping recommend 6-20AWG (0.5-10mm2) flexible or solid cable 8mm stripping recommend 10-24AWG (0.2-4mm2) flexible or solid cable 8mm stripping recommend
Max. torque for screws terminals From Pin1 to Pin4 1.008Nm (9.0lb-in) From Pin5 to Pin8 1.763Nm (15.6lb-in) From Pin9 to Pin12 0.616Nm (5.5lb-in)
Vout ADj
111.90 (4.41)
1
From Pin5 to Pin8
Normal convection All sides 25mm free space for cooling is recommended
6.90 (0.27)
106.50 (4.20)
6
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 0811