technical data

management system in order to help protect human health and the ... Electrical Specifications . .... Motor. Model. 2YC63BXD#C. Type. Hermetically sealed swing compressor. Motor ... Control. Expansion valve(electronic type). Nr of Circuits. 1. Refrigerant Oil Type .... The integrated heating capacity and power input, is the ...
1MB taille 8 téléchargements 670 vues
EEDE06-9

technical data

Altherma

ERYQ005-007A EKHBH007A / EKHBX007A EKSWW150-300

Altherma ERYQ005-007A EKHBH007A / EKHBX007A EKSWW150-300

ISO14001 assures an effective environmental management system in order to help protect human health and the environment from potential impact of our activities, products and services and to assist in maintaining and improving the quality of the environment.

Daikin units comply with the European regulations that guarantee the safety of the product.

Daikin Europe N.V. is approved by LRQA for its Quality Management System in accordance with the ISO9001 standard. ISO9001 pertains to quality assurance regarding design, development, manufacturing as well as to services related to the product.

Zandvoordestraat 300 B - 8400 Ostend Belgium www.daikineurope.com

EEDE0 6 - 9

EEDE06-9 - 07/2006 Printed in Belgium by Goekint Graphics

“ The present publication is drawn up by way of information only and does not constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of this publication to the best of its knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content and the products and services presented therein. Specifications are subject to change without prior notice. Daikin Europe N.V. explicitly rejects any liability for any direct or indirect damage, In the broadest sense, arising from or related to the use and/or interpretation of this publication. All content is copyrighted by Daikin Europe N.V..”

EEDE06-9

technical data Altherma

ERYQ005-007A EKHBH007A / EKHBX007A EKSWW150-300

• Chillers • R-410A • ALTHERMA

erA el0 hl1 t4i l-h RAC

Cooling only

Heating only

Heat pump 4

• Altherma • Chillers

• Outdoor units • R-410A • ERYQ

TABLE OF CONTENTS ERYQ

1

Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

2

Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Nominal Capacity and Nominal Input

............................... 7

....................................................................... 7

Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3

Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cooling/Heating capacity tables

4

7 9

10

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . . 11 Dimensional drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

11 12

5

Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

6

Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . External connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

7 8

14 15

Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

16

Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

18

• Altherma • Outdoor units

5

• Outdoor units • R-410A • ERYQ

1 i n u a r m o rA o e0 dh1Q t4Y uRl- EA•OR

1



Features Cost effective alternative to a fossil fuel boiler



Easy to install

Low energy bills and low CO2 emissions



Total solution for year round comfort

1

6

• Altherma • Outdoor units

• Outdoor units • R-410A • ERYQ

2

Specifications

2-1 NOMINAL CAPACITY AND NOMINAL INPUT

EKHBH*

Indoor Units Condition 1

Heating capacity

ERYQ007A

ERYQ005A

ERYQ006A

ERYQ007A

EKHBH007A*

EKHBH007A*

EKHBH007A*

EKHBX007A*

EKHBX007A*

EKHBX007A*

4.36

4.36

4.36

4.36

4.36

4.36

kW

Nominal

kW

5.75

6.84

8.43

5.75

6.84

8.43

Maximum kW

7.45

8.79

9.58

7.45

8.79

9.58

Cooling capacity

Minimum

kW

-

-

-

3.67

3.67

3.67

Nominal

kW

-

-

-

5.12

5.86

6.08

-

-

-

5.12

6.13

7.10

Heating PI

Nominal

kW

1.26

1.58

2.08

1.26

1.58

2.08

Cooling PI

Nominal

kW

-

-

-

2.16

2.59

2.75

COP

Nominal

-

4.56

4.34

4.05

4.56

4.34

4.05

EER

Nominal

-

Heating

Minimum

kW

Nominal

kW

5.03

6.10

7.64

5.03

6.10

7.64

Maximum kW

6.68

7.98

8.76

6.68

7.98

8.76

Cooling

-

-

-

2.37

2.26

2.21

3.87

3.87

3.87

3.87

3.87

3.87

Minimum

kW

-

-

-

4.82

4.82

4.82

Nominal

kW

-

-

-

7.20

8.16

8.37

Maximum kW

-

-

-

7.20

8.50

8.91 2.54

Heating PI

Nominal

kW

1.58

1.95

2.54

1.58

1.95

Cooling PI

Nominal

kW

-

-

-

2.16

2.59

2.75

COP

Nominal

-

3.18

3.13

3.00

3.18

3.13

3.00

EER

Nominal

-

-

-

-

3.33

3.15

3.04

ERYQ005A (+ EKHBX)

ERYQ006A (+ EKHBX)

ERYQ007A (+ EKHBX)

Notes

2-2

ERYQ006A

Minimum

Maximum kW

Condition 2

EKHBX*

ERYQ005A

1 2

*Condition 1 - cooling Ta 35°C - LWE 7°C - heating Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) * Condition 2 - cooling Ta 35°C - LWE 18°C (DT = 5°C) - heating Ta DB/WB 7°C/6°C - LWC 45°C (DT = 5°C)

TECHNICAL SPECIFICATIONS

Casing Dimensions

Packing

ERYQ006A (+ EKHBH)

ERYQ007A (+ EKHBH)

Colour

Ivory white

Material

Polyester painted galvanised steel

Unit

Packing

Weight

ERYQ005A (+ EKHBH)

Height

mm

797

Width

mm

960

Depth

mm

390

Height

mm

735

Width

mm

825

Depth

mm

300

Unit

kg

56

Packed Unit

kg

61

Material

EPS Carton

Weight Heat Exchanger

Dimensions

Length

kg

5

mm

845

mm

1.8

Nr of Rows Fin Pitch

2

Nr of Stages Tube type Fin

Type

WF fin

Treatment Fan

Anti-corrosion treatment (PE)

Type

Propeller

Quantity Motor

1 Quantity Output

Compressor

1 W

Quantity Motor

32 Hi-Xa(8)

53 1

Model

2YC63BXD#C

Type Motor Output

Hermetically sealed swing compressor W

• Altherma • Outdoor units

1920

7

• Outdoor units • R-410A • ERYQ

2

1 2

2-2

Specifications TECHNICAL SPECIFICATIONS

Operation Range

Heating Cooling Sanitary water

Sound Level (nominal)

Heating

Cooling

Refrigerant

ERYQ005A (+ EKHBH)

-20

°CWB

25

Min

°CDB

7

Max

°CDB

20

Min

°CDB °CDB

-20

Sound Power

dBA

64

64

66

64

64

66

Sound Pressure

dBA

48

48

52

48

48

52

Sound Power

dBA

63

64

66

Sound Pressure

dBA

47

47

53

43

R-410A kg

1 FVC50K

Charged Volume

l Type mm

Type mm

Quantity

15,9 1

Type

Socket

Diameter (OD)

mm

Minimum

m

3

Maximum m

30

Additional Refrigerant Charge

kg/m

Maximum m

Max. internunit level difference

m

18

0.02 IF > 10m 15

20

Defrost Method

Reverse cycle

Defrost Control

Sensor for outdoor heat exchanger temperature

Capacity Control Method

Inverter controlled

Standard Accessories

Installation manual

Item Quantity

1

Item

Drain plug

Quantity

8

6,35 Flare connection

Diameter (OD)

Installation height difference

0.75 Flare connection

Diameter (OD)

Piping Length

1.7 Expansion valve(electronic type)

Type

Drain

ERYQ007A (+ EKHBX)

Max

Nr of Circuits

Gas

ERYQ006A (+ EKHBX)

°CWB

Type

Liquid (OD)

ERYQ005A (+ EKHBX)

Min

Control

Piping connections

ERYQ007A (+ EKHBH)

Max

Charge

Refrigerant Oil

ERYQ006A (+ EKHBH)

1

• Altherma • Outdoor units

• Outdoor units • R-410A • ERYQ

2 2-3

Specifications ELECTRICAL SPECIFICATIONS

Power Supply

ERYQ007A (+ EKHBH)

ERYQ005A (+ EKHBX)

ERYQ006A (+ EKHBX)

ERYQ007A (+ EKHBX)

V1

1

Phase



2

Voltage

Hz

50

V

220-440

Voltage range

Maximum V

Starting Current

Cooling

A

Heating

A

Cooling

A

Heating

A

18

A

20

Maximum running Current

Recomended fuses Wiring connections

ERYQ006A (+ EKHBH)

Name Frequency

Current

ERYQ005A (+ EKHBH)

For Power Supply

Quantity

For connection Quantity with indoor Remark

• Altherma • Outdoor units

+10% 11 11 16.25

3 4 Included earth wiring

9

• Outdoor units • R-410A • ERYQ

1

3

Capacity tables

3-1

Cooling/Heating capacity tables

COOLING

Model

3 005

006

007

Tamb (°C) LWE (°C) 7 11 13 16 20 7 11 13 16 20 7 11 13 16 20

20 CC 6.01 6.81 7.23 7.88 8.80 7.15 8.09 8.57 9.33 10.4 8.24 9.26 9.79 10.6 11.7

25 PI 1.56 1.57 1.57 1.56 1.55 2.05 2.09 2.11 2.13 2.16 2.43 2.49 2.52 2.57 2.63

CC 5.73 6.50 6.90 7.54 8.42 6.84 7.73 8.20 8.92 9.9 7.90 8.87 9.38 10.17 11.3

PI 1.48 1.52 1.54 1.57 1.57 1.57 1.82 1.88 1.91 1.95 1.97 1.98 2.06 2.13 2.17 2.22 2.26 2.28

HC 3.67 4.32 4.77 5.62 6.38 7.45 4.62 5.34 5.83 6.77 7.61 8.79 5.16 5.93 6.46 7.45 8.35 9.58

30 PI 1.75 1.77 1.78 1.78 1.79 2.28 2.34 2.36 2.40 2.44 2.68 2.76 2.80 2.86 2.94

CC 5.43 6.17 6.56 7.17 8.03 6.50 7.34 7.79 8.49 9.48 7.52 8.45 8.93 9.69 10.75

PI 1.59 1.65 1.68 1.72 1.74 1.75 1.94 2.02 2.07 2.13 2.16 2.19 2.19 2.29 2.34 2.41 2.46 2.51

HC 3.47 4.07 4.49 5.28 6.00 7.00 4.43 5.09 5.55 6.42 7.21 8.32 4.97 5.68 6.17 7.10 7.93 9.10

35 PI 1.95 1.98 2.00 2.01 2.03 2.52 2.59 2.63 2.68 2.73 2.94 3.05 3.10 3.17 3.26

CC 5.12 5.83 6.20 6.79 7.63 6.13 6.94 7.36 8.03 8.99 7.10 7.79 8.14 8.68 9.39

PI 1.71 1.79 1.83 1.88 1.91 1.94 2.08 2.18 2.24 2.32 2.37 2.42 2.34 2.46 2.53 2.62 2.69 2.76

HC 3.33 3.89 4.28 5.03 5.72 6.68 4.30 4.92 5.35 6.17 6.92 7.98 4.86 5.51 5.97 6.85 7.65 8.76

40 PI 2.16 2.21 2.23 2.26 2.29 2.77 2.87 2.91 2.97 3.04 3.23 3.31 3.36 3.41 3.48

CC 4.80 5.30 5.56 5.95 6.48 5.35 5.84 6.09 6.46 6.96 5.68 6.12 6.34 6.67 7.09

PI 1.84 1.94 1.99 2.06 2.11 2.15 2.23 2.36 2.42 2.52 2.59 2.66 2.51 2.65 2.73 2.85 2.93 3.02

HC 3.25 3.78 4.15 4.87 5.53 6.47 4.24 4.82 5.23 6.02 6.74 7.78 4.80 5.42 5.86 6.70 7.47 8.56

43 PI 2.39 2.32 2.28 2.22 2.13 2.68 2.62 2.59 2.53 2.44 2.86 2.80 2.77 2.71 2.61

CC 4.59 4.98 5.18 5.46 5.82 4.89 5.21 5.36 5.57 5.82 4.87 5.18 5.33 5.55 5.80

PI 2.53 2.38 2.30 2.18 1.99 2.59 2.43 2.34 2.20 1.99 2.59 2.43 2.35 2.20 1.99

HEATING (Peak values)

Model

005

006

007

LWC Tamb -15 -10 -7 -2 2 7 -15 -10 -7 -2 2 7 -15 -10 -7 -2 2 7

30 HC 3.93 4.65 5.14 6.06 6.89 8.03 4.87 5.67 6.21 7.23 8.14 9.40 5.42 6.27 6.84 7.92 8.9 10.2

35

40

45

50 PI 1.99 2.10 2.16 2.25 2.31 2.37 2.40 2.55 2.63 2.75 2.83 2.92 2.70 2.86 2.95 3.10 3.20 3.31

HEATING (integrated values*)

Model

005

006

007

LWC Tamb -15 -10 -7 -2 2 7 -15 -10 -7 -2 2 7 -15 -10 -7 -2 2 7

30 HC 3.50 4.14 4.52 5.27 5.92 8.03 4.34 5.04 5.46 6.29 7.00 9.40 4.82 5.58 6.02 6.89 7.6 10.2

35 PI 1.40 1.45 1.45 1.46 1.45 1.57 1.73 1.79 1.80 1.81 1.81 1.98 1.96 2.03 2.04 2.07 2.08 2.28

HC 3.27 3.85 4.20 4.89 5.49 7.45 4.11 4.75 5.13 5.89 6.55 8.79 4.59 5.28 5.69 6.48 7.18 9.58

40 PI 1.51 1.56 1.58 1.60 1.60 1.75 1.85 1.92 1.94 1.98 1.99 2.19 2.08 2.17 2.20 2.25 2.27 2.51

HC 3.09 3.62 3.95 4.59 5.16 7.00 3.94 4.53 4.88 5.59 6.20 8.32 4.43 5.06 5.43 6.17 6.82 9.10

45 PI 1.62 1.70 1.72 1.75 1.76 1.94 1.98 2.07 2.10 2.15 2.18 2.42 2.23 2.34 2.37 2.44 2.47 2.76

HC 2.97 3.46 3.77 4.38 4.92 6.68 3.83 4.38 4.71 5.37 5.96 7.98 4.32 4.91 5.26 5.96 6.58 8.76

SYMBOLS CC HC PI LWE LWC Tamb

10

50 PI 1.75 1.84 1.87 1.92 1.94 2.15 2.12 2.24 2.28 2.35 2.38 2.66 2.39 2.52 2.57 2.65 2.70 3.02

HC 2.89 3.36 3.65 4.24 4.76 6.47 3.77 4.29 4.60 5.23 5.80 7.78 4.27 4.82 5.15 5.83 6.43 8.56

PI 1.89 2.00 2.03 2.10 2.13 2.37 2.28 2.42 2.47 2.56 2.61 2.92 2.56 2.72 2.78 2.88 2.94 3.31

* The integrated heating capacity and power input, is the average heating capacity and power input during 1 cycle. (from end of defrost till end of the next defrost).

4TW56712-1A

NOTES

: Cooling capacity at maximum operating frequency, measured acc. Eurovent 6/C/003-2006 (kW) : Heating capacity at maximum operating frequency, measured acc. Eurovent 6/C/003-2006 (kW) : Power input (kW) : Leaving Water Evaporator temperature (°C) : Leaving Water Condensor temperature (°C) : Ambient temperature (°C) RH=85%

• Altherma • Outdoor units

1

2

3

Cooling capacity Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water range Dt = 3∼8°C Heating capacity Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water range Dt = 3∼8°C Power input Power input is total input according to Eurovent rating standard 6/C/003-2006

• Outdoor units • R-410A • ERYQ

4

Dimensional drawing & centre of gravity

4-1

Dimensional drawing unit (mm)

ERYQ Drain outlet (I.D. J 15.9 hose for connection)

Minimum space for air passage

Wall height on air outlet side = less than 1200

1 4

In case of removing stop valve cover 4 x holes for anchor bolts (M8 or M10)

Name plate Wiring inlet

Brand name label

Outdoor air thermistor

Terminal strip with earth terminal

Liquid stop valve (J6.4 CuT) Service port

Gas stop valve (J15.9 CuT)

3D051658B

• Altherma • Outdoor units

11

• Outdoor units • R-410A • ERYQ

1

4

Dimensional drawing & centre of gravity

4-2

Centre of gravity

ERYQ

4

The position of foundation bolt 4D042258G

12

• Altherma • Outdoor units

• Outdoor units • R-410A • ERYQ

5

Piping diagram

ERYQ

1

Outdoor unit Heat exchanger

5

Outdoor temperature thermistor

Capillary tube 1

Capillary tube 2 Capillary tube 3

Heat exchanger thermistor

Muffler with filter

Refrigerant flow Cooling Heating

Capillary tube 4

Filter Motor operated valve

Propeller fan

Filter Four way valve on : heating

Muffler with filter

Field piping

Muffler Liquid stop valve Muffler

Field piping Discharge pipe thermistor

Compressor

Accumulator

Gas stop valve with service port

3D052750A

• Altherma • Outdoor units

13

• Outdoor units • R-410A • ERYQ

1

6

Wiring diagram

6-1

Wiring diagram

ERYQ

6 Power supply

To indoor unit

Sheet metal

Indoor

g Field wiring

(discharge) (outdoor) (Condenser) Outdoor Z1C∼Z7C X1M, X2M Y1E V2, V3, V5, V9, V100 SA2 FU1, FU2, FU3: AC1, AC2 U, V, W, X11A, X12A E1, E2 HR1, HR2

14

: Ferrite core : Terminal strip : Electronic expansion valve coil : Varistor : Surge arrester : Fuse

: Connector

MRM10, MRM20 MRC/W R1T∼R3T S2∼S102 LEDA L N SW1 SW4 M1C M1F L1R

: Magnetic relay : Thermistor : Connector : Pilot lamp : Live : Neutral : Forced operation on/off switch SW (SW1) : Local setting SW (SW4) : Compressor motor : Fan motor : Reactor

• Altherma • Outdoor units

Q1L PM1 PCB1,2 Y1R Sheet metal

: Overload protector : Power module : Printed circuit board : Reversing solenoide valve coil : Terminal strip fixed plate

3D052296B

• Outdoor units • R-410A • ERYQ

6

Wiring diagram

6-2

External connection diagram

EKHB-A

1

Standard parts Power supply For more details please check unit wiring diagram

Outdoor unit

6

3 core

Unit power supply: 230V + earth

X1M:L-N-Earth

Backup heater power supply (3/6/9kW): 400V or 230V + earth

Optional power supply

X2M:1-2-3-Earth

Booster heater power supply (3kW): 400V or 230V + earth

3 or 4 core

3 core

Optional parts

4 core

Field supply X1M:9-10-11-Earth

Sanitary tank Room thermostat Power supply booster heater

Q2L - Clixon booster heater

R5T - Thermistor water temperature

4 core 5 core

230V or 400V

A3P (optional)

X1M:7-8-Earth

NO valve:

2 core

NC valve:

2 core

2 core Signal Thermistor cable Note: min. distance to power cable = 3cm

2 way valve M2S (EKHBX Units) for cooling mode

3 way valve M3S (when EKSWW is installed) selection sanitary-floorheating

Indoor unit User interface

3TW56719-6

• Altherma • Outdoor units

15

• Outdoor units • R-410A • ERYQ

7-1

Sound pressure spectrum

ERYQ005ABV3 Cooling

ERYQ006ABV3 Cooling Sound pressure level (dB)

7

Sound data

Sound pressure level (dB)

1

7

3TW56717-1

Octave band center frequency (Hz)

3TW56717-1

NOTES 1 2 3 4

Octave band center frequency (Hz)

NOTES

Data is valid at free field condition (measured in a semi-anachoic room) dB(A) = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections.

1 Coil Microphone

2 3 4

Data is valid at free field condition (measured in a semi-anachoic room) dB(A) = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections.

Coil Microphone

Location of microphone

Location of microphone

ERYQ007ABV3 Cooling Sound pressure level (dB)

Sound pressure level (dB)

ERYQ005ABV3 Heating

3TW56717-1

Octave band center frequency (Hz)

3TW56717-2

NOTES 1 2 3 4

Data is valid at free field condition (measured in a semi-anachoic room) dB(A) = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections.

1

Coil Microphone

2 3 4

Location of microphone

16

Octave band center frequency (Hz)

NOTES

• Altherma • Outdoor units

Data is valid at free field condition (measured in a semi-anachoic room) dB(A) = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections.

Coil Microphone

Location of microphone

• Outdoor units • R-410A • ERYQ

7

Sound data

7-1

Sound pressure spectrum ERYQ007ABV3 Heating

3TW56717-2

Octave band center frequency (Hz)

2 3 4

Data is valid at free field condition (measured in a semi-anachoic room) dB(A) = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections.

7

3TW56717-2

NOTES 1

1

Sound pressure level (dB)

Sound pressure level (dB)

ERYQ006ABV3 Heating

Octave band center frequency (Hz)

NOTES 1

Coil Microphone

2 3 4

Location of microphone

• Altherma • Outdoor units

Data is valid at free field condition (measured in a semi-anachoic room) dB(A) = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections.

Coil Microphone

Location of microphone

17

• Outdoor units • R-410A • ERYQ

8

Operation range

1

Outdoor temp. (°CDB)

Cooling mode

8

Leaving evaporator water temperature (°C)

Heating mode

Outdoor temp. (°CDB)

Leaving condenser water temperature (°C)

Sanitary mode

Outdoor temp. (°CDB)

: Booster heater operation only

Leaving condenser water temperature (°C)

4TW56713-1A

18

• Altherma • Outdoor units

• Indoor units • R-410A • EKHBH / EKHBX

TABLE OF CONTENTS EKHBH / EKHBX

1

Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

2

Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

21

Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

21 23

3

Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

24

4

Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . . 25 Dimensional drawing

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

5

Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

6

Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . External connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

7

27 29

Hydraulic performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Static pressure drop unit

• Altherma • Indoor units

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

19

• Indoor units • R-410A • EKHBH / EKHBX

1 H t K i E n u a/ m r rA Ho e0 Bo h1 Hd t4 nKl- E•IAR •

Features Cost effective alternative to a fossil fuel boiler



Easy to install

Low energy bills and low CO2 emissions



Total solution for year round comfort

2 1

20

• Altherma • Indoor units

• Indoor units • R-410A • EKHBH / EKHBX

2 2-1

Specifications TECHNICAL SPECIFICATIONS

Outdoor units Nominal input (Indoor only) Casing Dimensions

Packing

EKHBH007A (+ERYQ006A)

EKHBH007A (+ERYQ007A)

ERYQ005A

ERYQ006A

ERYQ007A

W

EKHBX007A (+ERYQ005A)

EKHBX007A (+ERYQ006A)

EKHBX007A (+ERYQ007A)

ERYQ005A

ERYQ006A

ERYQ007A

230

Colour

RAL9010

Material

Polyester painted galvanised steel

Packing

Unit

Weight

EKHBH007A (+ERYQ005A)

Height

mm

2 2

1225

Width

mm

660

Depth

mm

595

Height

mm

895

936

Width

mm

487

487

Depth

mm

361

461

Unit

kg

55

65

Packed Unit

kg

65

75

Material

EPS Wood Carton PS(straps)

Weight

kg

Main components

Pump

Type

Pump

Nominal ESP unit

Cooling Heating

kPa

Main components

Pump

Power input

W

Water side Heat exchanger

Type

10 Water cooled

Nr. of speed

3

kPa 46.5

40.1

29.0

46.5

40.1

29.0

1

Water volume

l

Water flow rate Min.

l/min

0.67 12

Cooling

l/min

Heating

l/min

Main components

Water side Heat exchanger

Insulation material

Expansion vessel

Volume

l

10

Max. water pressure

bar

3

Pre pressure

bar

1

Diameter perforations

mm

1

inch

1"MBSP

Piping

inch

1"MBSP

Safety valve

bar

3

16.5

Material Piping connections diameter

44.4

Brazed plate

Qty

Water flow rate Nom.

Water circuit

46.5

130

Water side Heat exchanger

Water filter

49.9

19.6

24.2

14.7

16.5

17.6

16.5

19.6

24.2

Polyurethane foam

Brass

Manometer

Yes

Drain valve / Fill valve

Yes

Shut off valve

Yes

Air purge valve

Yes

• Altherma • Indoor units

21

• Indoor units • R-410A • EKHBH / EKHBX

2 2-1

2 2

Specifications TECHNICAL SPECIFICATIONS

EKHBH007A (+ERYQ005A)

EKHBH007A (+ERYQ006A)

EKHBH007A (+ERYQ007A)

EKHBX007A (+ERYQ005A)

Refrigerant Circuit

Gas side diameter

mm

15,9

Liquid side diameter

mm

(2)

Sound Level

Sound Pressure

Operation range

Waterside

Notes

dBA

27

Cooling

°C

7 ˜ 20

Heating

°C

EKHBX007A (+ERYQ007A)

30 ˜ 55 The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value, depending on the distance and acoustic environment. ERYQ = 6.35 mm EKHB = 9.52 mm (flare connection)

22

EKHBX007A (+ERYQ006A)

• Altherma • Indoor units

• Indoor units • R-410A • EKHBH / EKHBX

2 2-2 Electric heater

Specifications ELECTRICAL SPECIFICATIONS Type Power Supply

Current Electric heater

Power Supply

Current Electric heater

Current Electric heater

Power Supply

Current

EKHBX007A (+ERYQ006A)

EKHBX007A (+ERYQ007A)

1 50

2

Voltage

V

230

2

Running Current

A

13 6V3

Phase

1

Frequency

Hz

50

Voltage

V

230

Running Current

A

26 6W1

Phase

3N

Frequency

Hz

50

Voltage

V

400

Running Current

A

8.6 6T1

Phase

3

Frequency

Hz

50

Voltage

V

230

Running Current

A

15 9W1

Phase

3N

Frequency

Hz

50

Voltage

V

400

Running Current

A

13

Type Power Supply

EKHBX007A (+ERYQ005A)

Hz

Type

Current Electric heater

Phase

Type Power Supply

EKHBH007A (+ERYQ007A)

Frequency

Type Power Supply

EKHBH007A (+ERYQ006A)

3V3

Type

Current Electric heater

EKHBH007A (+ERYQ005A)

9T1 Phase

3

Frequency

Hz

50

Voltage

V

230

Running Current

A

23

• Altherma • Indoor units

23

24

Back up heater 6kW 1∼230 V

Back up heater 6kW 3∼400 V + N

Back up heater 6kW 3∼230 V

Back up heater 9kW 3∼400 V + N

Back up heater 9kW 3∼230 V

6V3

6W1

6T1

9W1

9T1

Sanitary warm water tank 150 l 230 V

Sanitary warm water tank 200 l 230 V

Sanitary warm water tank 300 l 230 V

Sanitary warm water tank 200 l 400 V

Sanitary warm water tank 300 l 400 V

Wall bracket for EKSWW150V3

EKSWW150V3

EKSWW200V3

EKSWW300V3

EKSWW200Z2

EKSWW300Z2

EKWBSWW150

Available kits

Back up heater 3kW 1∼230 V

3V3

⎯ ⎯ ⎯ ⎯

⎯ ⎯ ⎯ ⎯

• Altherma • Indoor units V ⎯ ⎯

⎯ ⎯

V

V

V

V

V



V



V

EKHBH007A6V3 EKHBX007A6V3

V

V

V

V

V







V





EKHBH007A6W1 EKHBX007A6W1





V

V

V





V







EKHBH007A6T1 EKHBX007A6T1

V

V

V

V

V



V









EKHBH007A9W1 EKHBX007A9W1





V

V

V

V











EKHBH007A9T1 EKHBX007A9T1

3

Available options

EKHBH007A3V3 EKHBX007A3V3

Number

3TW56719-5

Kit

Kit

Kit

Kit

Kit

Kit

Factory mounted

Factory mounted

Factory mounted

Factory mounted

Factory mounted

Factory mounted

Availability

3

Heating only model Reversible model

Description

2

Reference

Optional equipment for EKHB(H/X)007*

• Indoor units • R-410A • EKHBH / EKHBX

Options

• Indoor units • R-410A • EKHBH / EKHBX

4

Dimensional drawing & centre of gravity

4-1

Dimensional drawing

EKHBH-A

2 4

Service door

Setup 1 Setup 2

A ≥ 200 ≥ 350

B ≥ 400 ≥ 200

1’’ female BSP

(Closed) 361 (Open) 553

1’’ male BSP

Min. 400

Min. 200

Center of gravity j 1 Pump + switch for speed setting j 2 Remocon j 3 Water IN conection 1’’ M BSP j 4 Water OUT connection 1’’ M BSP j 5 Power supply intake (+ sanitary warm water tank) j 6 Drain / fill valve j 7 Air purge j 8 Expansion vessel + nipple j 9 Blow off valve j 10 Pressure gauge j 11 Water filter j 12 Suction pipe connection J15.9 flare connection j 13 Liquid pipe connection J9.52 flare connection j 14 Shut off valves (delivered with unit) j 15 Thermistor connection (+ sanitary warm water tank) j 16 Holes for fixation j 17 Blow off drain j 18 Switchbox connection terminals j 19 Wallbracket

Min. 100

Minimum space for service & ventilation

3TW56714-1A

EKHBX-A

Minimum space for service & ventilation

1’’ female BSP

(Closed) 461 (Open) 653

1’’ male BSP

Dimensions wallbracket

Min. 400

Min. 200

Center of gravity j 1 Pump + switch for speed setting j 2 Remocon j 3 Water IN conection 1’’ M BSP j 4 Water OUT connection 1’’ M BSP j 5 Power supply intake (+ sanitary warm water tank) j 6 Drain / fill valve j 7 Air purge j 8 Expansion vessel + nipple j 9 Blow off valve j 10 Pressure gauge j 11 Water filter j 12 Suction pipe connection J15.9 flare connection j 13 Liquid pipe connection J9.52 flare connection j 14 Shut off valves (delivered with unit) j 15 Thermistor connection (+ sanitary warm water tank) j 16 Holes for fixation j 17 Blow off drain / drain of drainpan j 18 Switchbox connection terminals j 19 Wallbracket

Min. 125

Service door

Setup 1 Setup 2

A ≥ 200 ≥ 350

B ≥ 400 ≥ 200

• Altherma • Indoor units

3TW56724-1A

25

• Indoor units • R-410A • EKHBH / EKHBX

5

Piping diagram

EKHB-A

Water side

R4T R3T R2T R1T

2

Inlet water thermistor Refrigerant liquid side thermistor Outlet water backup heater thermistor Outlet water heat-exchanger thermistor

Field installation Filter Inlet Shut off valve

5 Refrigerant side

Safety valve Drain valve

Pressure gauge

Drain

Expansion vessel Cooling (EKHBX) Heating (EKHBX + EKHBH)

Option backup heater Drain valve

Field installation

Air purge

Flowswitch

Pump

Outlet Shut off valve

Overview Electric heater body Evaporator Condensor

Outdoor unit

Refr. out Refr. in

Water inlet Refrigerant side

Water side

Refr. in Water outlet Refr. out

O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe PSpinned pipe

26

• Altherma • Indoor units

3TW56715-1

• Indoor units • R-410A • EKHBH / EKHBX

6

Wiring diagram

6-1

Wiring diagram

EKHBH/X-A3V3 Power supply

Outdoor unit

Sanitary tank

>> See note 2 > See note 2 > See note 2
See note 2 typcial 2-persons usage pattern. Medium Daily demand up to 325 l -> typical 3 to 4 persons usage pattern. High Daily demand up to 550 l -> 4 to 6 persons usage pattern.

(2) Heat-up time: Definition: Heat-up time The time required to reheat the sanitary tank to 55°C after tapping a certain volume of hot water at 40°C. note: changing the field settings (see installation manual) can influence the heat-up time. Tank 150L 200L 300L

Setpoint temp. (°C) 55 55 55

Heat-up time for Heat-up time for 50 150 L (bath) L (shower) 60 45 60 40 50 30

Conditions for testing: Ta = 7°CDB / 6°CWB, Troom = 20°C, Tstart = 10°C, outdoor unit type: ERYQ007

(3) Efficiency of sanitary hot water production: In the ALTHERMA by Daikin system both the heat-pump and the electric booster heater supply the energy to produce sanitary hot water. The higher the portion of energy supplied by the heat-pump, the more energy efficient the system is. Lowering the setpoint temperature increases the portion of energy supplied by the heat-pump and thus the efficiency of the system.

Heat-pump portion

Definition: Heat-pump portion Percentage of energy supplied by the heat-pump in the total energy need for sanitary hot water.

Setpoint temp. (°C) Conditions:

Real life condition Outdoor temperature Room temperature Outdoor unit type Tank type Field settings

Simulation of a daily usage based upon ′medium′ usage pattern. 7°CDB / 6°CWB 20°CDB ERYQ007 200l Default field settings (see installation manual).

4TW56719-3

34

• Altherma • Sanitary Hot Water

• Sanitary Hot Water • R-410A • EKSWW

4

Dimensional drawing & centre of gravity

4-1

Dimensional drawing

EKSWW j 1 Water mains in female 3/4’’ BSP j 2 Water mains out female 3/4’’ BSP j 3 Thermistor connection female 1/2’’ BSP j 4 Flow (from hydrobox) female 3/4’’ BSP j 5 Return (to hydrobox) female 3/4’’ BSP j 6 Switchbox j 7 Clixon j 8 Connection female 3/4’’ BSP

3 4

3TW56714-4

• Altherma • Sanitary Hot Water

35

• Sanitary Hot Water • R-410A • EKSWW

5

Wiring diagram

5-1

External connection diagram

EKHB-A Standard parts Power supply For more details please check unit wiring diagram

Outdoor unit 3 core

Unit power supply: 230V + earth

X1M:L-N-Earth

Backup heater power supply (3/6/9kW): 400V or 230V + earth

3 5

Optional power supply

X2M:1-2-3-Earth

Booster heater power supply (3kW): 400V or 230V + earth

3 or 4 core

3 core

Optional parts

4 core

Field supply X1M:9-10-11-Earth

Sanitary tank Room thermostat Power supply booster heater

Q2L - Clixon booster heater

R5T - Thermistor water temperature

4 core 5 core

A3P (optional)

X1M:7-8-Earth

230V or 400V

NO valve:

2 core

NC valve:

2 core

2 core Signal Thermistor cable Note: min. distance to power cable = 3cm

2 way valve M2S (EKHBX Units) for cooling mode

3 way valve M3S (when EKSWW is installed) selection sanitary-floorheating

Indoor unit User interface

3TW56719-6

36

• Altherma • Sanitary Hot Water