management system in order to help protect human health and the ... Electrical Specifications . .... Motor. Model. 2YC63BXD#C. Type. Hermetically sealed swing compressor. Motor ... Control. Expansion valve(electronic type). Nr of Circuits. 1. Refrigerant Oil Type .... The integrated heating capacity and power input, is the ...
1MB taille 158 téléchargements 1177 vues
EEDEN07-720

technical data

Altherma

ERYQ005-007AC EKHBH007AC / EKHBX007AC EKSWW150-300

Altherma ERYQ005-007AC EKHBH007AC / EKHBX007AC EKSWW150-300

Daikin’s unique position as a manufacturer of air conditioning equipment, compressors and refrigerants has led to its close involvement in environmental issues. For several years Daikin has had the intention to become a leader in the provision of products that have limited impact on the environment. This challenge demands the eco design and development of a wide range of products and an energy management system, resulting in energy conservation and a reduction of waste.

ISO14001 assures an effective environmental management system in order to help protect human health and the environment from potential impact of our activities, products and services and to assist in maintaining and improving the quality of the environment.

Daikin Europe N.V. is approved by LRQA for its Quality Management System in accordance with the ISO9001 standard. ISO9001 pertains to quality assurance regarding design, development, manufacturing as well as to services related to the product.

“The present publication is drawn up by way of information only and does not constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of this publication to the best of its knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content and the products and services presented therein. Specifications are subject to change without prior notice. Daikin Europe N.V. explicitly rejects any liability for any direct or indirect damage, In the broadest sense, arising from or related to the use and/or interpretation of this publication. All content is copyrighted by Daikin Europe N.V..”

Naamloze Vennootschap Zandvoordestraat 300 B-8400 Ostend, Belgium www.daikin.eu BTW: BE 0412 120 336 RPR Oostende

EEDEN0 7 - 7 2 0

EEDEN07-720 - 04/2007 Printed in Belgium by Goekint Graphics Copyright © Daikin

Daikin units comply with the European regulations that guarantee the safety of the product.

EEDEN07-720

technical data Altherma

ERYQ005-007AC EKHBH007AC / EKHBX007AC EKSWW150-300

• Chillers • R-410A • ALTHERMA

erA el0 hl1 t4i l-h RAC

Heating only

Heat pump 4

• Altherma • Chillers

• Outdoor units • R-410A • ERYQ

TABLE OF CONTENTS ERYQ

1

Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

2

Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Nominal Capacity and Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3

Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Heating/Cooling capacity tables

4

7 7 9

10

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . . 11 Dimensional drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

11 12

5

Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

6

Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . External connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

7 8

14 15

Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

16

Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

18

• Altherma • Outdoor units

5

• Outdoor units • R-410A • ERYQ

1 i n u a r m o rA o e0 dh1Q t4Y uRl- EA•OR

1



Features Cost effective alternative to a fossil fuel boiler



Easy to install

Low energy bills and low CO2 emissions



Total solution for year round comfort

1

6

• Altherma • Outdoor units

• Outdoor units • R-410A • ERYQ

2

Specifications

2-1 NOMINAL CAPACITY AND NOMINAL INPUT Indoor Units Condition 1

Heating capacity

ERYQ006AC (+ EKHBH)

ERYQ007AC (+ EKHBH)

ERYQ005AC (+ EKHBX)

ERYQ006AC (+ EKHBX)

ERYQ007AC (+ EKHBX)

EKHBH007AC

EKHBH007AC

EKHBH007AC

EKHBX007AC

EKHBX007AC

EKHBX007AC

4.36

4.36

4.36

4.36

4.36

4.36

Minimum

kW

Nominal

kW

5.75

6.84

8.43

5.75

6.84

8.43

Maximum kW

7.45

8.79

9.58

7.45

8.79

9.58

Cooling capacity

Minimum

kW

-

-

-

4.82

4.82

4.82

Nominal

kW

-

-

-

7.20

8.16

8.37

-

-

-

7.20

8.50

8.91

Heating PI

Nominal

kW

1.26

1.58

2.08

1.26

1.58

2.08

Cooling PI

Nominal

kW

-

-

-

2.27

2.78

2.97

COP

Nominal

-

4.56

4.34

4.05

4.56

4.34

4.05

Maximum kW

Condition 2

ERYQ005AC (+ EKHBH)

EER

Nominal

-

Heating

Minimum

kW

Nominal

kW

5.03

6.10

7.64

5.03

6.10

7.64

Maximum kW

6.68

7.98

8.76

6.68

7.98

8.76

Cooling

-

-

-

3.17

2.94

2.82

3.87

3.87

3.87

3.87

3.87

3.87

Minimum

kW

-

-

-

3.67

3.67

3.67

Nominal

kW

-

-

-

5.12

5.86

6.08

Maximum kW

-

-

-

5.12

6.13

7.10 2.54

Heating PI

Nominal

kW

1.58

1.95

2.54

1.58

1.95

Cooling PI

Nominal

kW

-

-

-

2.16

2.59

2.75

COP

Nominal

-

3.18

3.13

3.00

3.18

3.13

3.00

EER

Nominal

-

-

-

-

2.37

2.26

2.21

Notes

1 2

Condition 1: heating Ta DB/WB 7°C/6°C - LWC 35°C ( DT = 5°C ) - cooling Ta 35°C - LWE 7°C Condition 2: heating Ta DB/WB 7°C/6°C - LWC 45°C ( DT = 5°C ) - cooling Ta 35°C - LWE 18°C ( DT = 5°C )

2-2 TECHNICAL SPECIFICATIONS Casing Dimensions

Packing

ERYQ006AC (+ EKHBH)

ERYQ007AC (+ EKHBH)

ERYQ005AC (+ EKHBX)

Colour

Ivory white

Material

Polyester painted galvanised steel

Unit

Packing

Weight

ERYQ005AC (+ EKHBH)

Height

mm

735

Width

mm

825

Depth

mm

300

Height

mm

797

Width

mm

960

Depth

mm

390

Unit

kg

56

Packed Unit

kg

61

Material

ERYQ006AC (+ EKHBX)

ERYQ007AC (+ EKHBX)

EPS Carton

Weight Heat Exchanger

Specifications

Length

kg

5

mm

845

mm

1.8

Nr of Rows Fin Pitch

2

Nr of Stages Tube type Fin

Type

WF fin

Treatment Fan

Anti-corrosion treatment (PE)

Type

Propeller

Quantity

1

Discharge direction Motor

Horizontal

Quantity Output

Compressor

1 W

Quantity Motor

32 Hi-Xa(8)

53 1

Model

2YC63BXD#C

Type Motor Output

Hermetically sealed swing compressor W

• Altherma • Outdoor units

1920

7

• Outdoor units • R-410A • ERYQ

2

1 2

Specifications

2-2 TECHNICAL SPECIFICATIONS Operation Range (1)

Heating Cooling Sanitary water

Sound Level (nominal)

Heating

Min

°CDB

-

10

Max

°CDB

-

43

25

Min

°CDB

-20

Max

°CDB

43

Sound Power

dBA

Sound Power

dBA

60

60

61

60

60

61

48

48

49

48

48

49

-

-

-

62

62

63

-

-

-

48

48

50

R-410A kg

1.7 Expansion valve(electronic type)

Nr of Circuits

1

Type

FVC50K

Charged Volume

l

Flare connection mm

6.35

Type

Flare connection

Diameter (OD) Drain

0.75

Type Diameter (OD)

Gas

mm

15,9

Quantity

1

Type

Piping Length

Socket

Diameter (OD)

mm

Minimum

m

3

Maximum m

30

Additional Refrigerant Charge Installation height difference

ERYQ007AC (+ EKHBX)

-20

Type

Liquid (OD)

ERYQ006AC (+ EKHBX)

°CWB

Control

Piping connections

ERYQ005AC (+ EKHBX)

°CWB

Charge

Refrigerant Oil

ERYQ007AC (+ EKHBH)

Min

Sound dBA Pressure (2) Refrigerant

ERYQ006AC (+ EKHBH)

Max

Sound dBA Pressure (2) Cooling

ERYQ005AC (+ EKHBH)

18

kg/m

0.02 IF > 10m

Maximum m

Max. internunit level difference

15 m

20

Defrost Method

Reverse cycle

Defrost Control

Sensor for outdoor heat exchanger temperature

Capacity Control Method

Inverter controlled

Standard Accessories

Installation manual

Item Quantity

1

Item

Drain plug

Quantity

1

Notes

See operation range drawing The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value depending on the distance and acoustic environment. Refer to sound spectrum drawing for more information.

8

• Altherma • Outdoor units

• Outdoor units • R-410A • ERYQ

2

Specifications

2-3 ELECTRICAL SPECIFICATIONS Power Supply

ERYQ006AC (+ EKHBH)

ERYQ007AC (+ EKHBH)

ERYQ005AC (+ EKHBX)

ERYQ006AC (+ EKHBX)

ERYQ007AC (+ EKHBX)

Name

V1

1

Phase

1~

2

Frequency Voltage Voltage range

Minimum

Hz

50

V

220-240

V

-10%

Maximum V

+10%

Starting Current

Heating

A

11

Cooling

A

11

Maximum running Current

Heating

A

18

Cooling

A

16.25

A

20

Recomended fuses Wiring connections

ERYQ005AC (+ EKHBH)

For Power Supply

Quantity

For connection Quantity with indoor Remark

• Altherma • Outdoor units

3 4 Included earth wiring

9

• Outdoor units • R-410A • ERYQ

3

Capacity tables

3-1

Heating/Cooling capacity tables

HEATING (Peak values)

1

Model

3 005

006

007

LWC Tamb -15 -10 -7 -2 2 7 -15 -10 -7 -2 2 7 -15 -10 -7 -2 2 7

30 HC 3.93 4.65 5.14 6.06 6.89 8.03 4.87 5.67 6.21 7.23 8.14 9.40 5.42 6.27 6.84 7.92 8.9 10.2

35 PI 1.48 1.52 1.54 1.57 1.57 1.57 1.82 1.88 1.91 1.95 1.97 1.98 2.06 2.13 2.17 2.22 2.26 2.28

HC 3.67 4.32 4.77 5.62 6.38 7.45 4.62 5.34 5.83 6.77 7.61 8.79 5.16 5.93 6.46 7.45 8.35 9.58

40 PI 1.59 1.65 1.68 1.72 1.74 1.75 1.94 2.02 2.07 2.13 2.16 2.19 2.19 2.29 2.34 2.41 2.46 2.51

HC 3.47 4.07 4.49 5.28 6.00 7.00 4.43 5.09 5.55 6.42 7.21 8.32 4.97 5.68 6.17 7.10 7.93 9.10

45 PI 1.71 1.79 1.83 1.88 1.91 1.94 2.08 2.18 2.24 2.32 2.37 2.42 2.34 2.46 2.53 2.62 2.69 2.76

HC 3.33 3.89 4.28 5.03 5.72 6.68 4.30 4.92 5.35 6.17 6.92 7.98 4.86 5.51 5.97 6.85 7.65 8.76

50 PI 1.84 1.94 1.99 2.06 2.11 2.15 2.23 2.36 2.42 2.52 2.59 2.66 2.51 2.65 2.73 2.85 2.93 3.02

HC 3.25 3.78 4.15 4.87 5.53 6.47 4.24 4.82 5.23 6.02 6.74 7.78 4.80 5.42 5.86 6.70 7.47 8.56

PI 1.99 2.10 2.16 2.25 2.31 2.37 2.40 2.55 2.63 2.75 2.83 2.92 2.70 2.86 2.95 3.10 3.20 3.31

HEATING (integrated values*)

Model

005

006

007

LWC Tamb -15 -10 -7 -2 2 7 -15 -10 -7 -2 2 7 -15 -10 -7 -2 2 7

30 HC 3.50 4.14 4.52 5.27 5.92 8.03 4.34 5.04 5.46 6.29 7.00 9.40 4.82 5.58 6.02 6.89 7.6 10.2

Tamb (°C) LWE (°C) 7 11 13 16 20 7 11 13 16 20 7 11 13 16 20

CC 6.01 6.81 7.23 7.88 8.80 7.15 8.09 8.57 9.33 10.4 8.24 9.26 9.79 10.6 11.7

35 PI 1.40 1.45 1.45 1.46 1.45 1.57 1.73 1.79 1.80 1.81 1.81 1.98 1.96 2.03 2.04 2.07 2.08 2.28

HC 3.27 3.85 4.20 4.89 5.49 7.45 4.11 4.75 5.13 5.89 6.55 8.79 4.59 5.28 5.69 6.48 7.18 9.58

PI 1.56 1.57 1.57 1.56 1.55 2.05 2.09 2.11 2.13 2.16 2.43 2.49 2.52 2.57 2.63

CC 5.73 6.50 6.90 7.54 8.42 6.84 7.73 8.20 8.92 9.9 7.90 8.87 9.38 10.17 11.3

40 PI 1.51 1.56 1.58 1.60 1.60 1.75 1.85 1.92 1.94 1.98 1.99 2.19 2.08 2.17 2.20 2.25 2.27 2.51

HC 3.09 3.62 3.95 4.59 5.16 7.00 3.94 4.53 4.88 5.59 6.20 8.32 4.43 5.06 5.43 6.17 6.82 9.10

PI 1.75 1.77 1.78 1.78 1.79 2.28 2.34 2.36 2.40 2.44 2.68 2.76 2.80 2.86 2.94

CC 5.43 6.17 6.56 7.17 8.03 6.50 7.34 7.79 8.49 9.48 7.52 8.45 8.93 9.69 10.75

45 PI 1.62 1.70 1.72 1.75 1.76 1.94 1.98 2.07 2.10 2.15 2.18 2.42 2.23 2.34 2.37 2.44 2.47 2.76

HC 2.97 3.46 3.77 4.38 4.92 6.68 3.83 4.38 4.71 5.37 5.96 7.98 4.32 4.91 5.26 5.96 6.58 8.76

PI 1.95 1.98 2.00 2.01 2.03 2.52 2.59 2.63 2.68 2.73 2.94 3.05 3.10 3.17 3.26

CC 5.12 5.83 6.20 6.79 7.63 6.13 6.94 7.36 8.03 8.99 7.10 7.79 8.14 8.68 9.39

50 PI 1.75 1.84 1.87 1.92 1.94 2.15 2.12 2.24 2.28 2.35 2.38 2.66 2.39 2.52 2.57 2.65 2.70 3.02

HC 2.89 3.36 3.65 4.24 4.76 6.47 3.77 4.29 4.60 5.23 5.80 7.78 4.27 4.82 5.15 5.83 6.43 8.56

PI 2.16 2.21 2.23 2.26 2.29 2.77 2.87 2.91 2.97 3.04 3.23 3.31 3.36 3.41 3.48

CC 4.80 5.30 5.56 5.95 6.48 5.35 5.84 6.09 6.46 6.96 5.68 6.12 6.34 6.67 7.09

PI 1.89 2.00 2.03 2.10 2.13 2.37 2.28 2.42 2.47 2.56 2.61 2.92 2.56 2.72 2.78 2.88 2.94 3.31

* The integrated heating capacity and power input, is the average heating capacity and power input during 1 cycle. (from end of defrost till end of the next defrost).

COOLING

Model

005

006

007

20

25

30

35

SYMBOLS HC CC PI LWE LWC Tamb

10

40

43 PI 2.39 2.32 2.28 2.22 2.13 2.68 2.62 2.59 2.53 2.44 2.86 2.80 2.77 2.71 2.61

CC 4.59 4.98 5.18 5.46 5.82 4.89 5.21 5.36 5.57 5.82 4.87 5.18 5.33 5.55 5.80

PI 2.53 2.38 2.30 2.18 1.99 2.59 2.43 2.34 2.20 1.99 2.59 2.43 2.35 2.20 1.99

3TW57552-1

NOTES

: Heating capacity at maximum operating frequency, measured acc. Eurovent 6/C/003-2006 (kW) : Cooling capacity at maximum operating frequency, measured acc. Eurovent 6/C/003-2006 (kW) : Power input (kW) : Leaving Water Evaporator temperature (°C) : Leaving Water Condensor temperature (°C) : Ambient temperature (°C) RH=85%

• Altherma • Outdoor units

1

Heating capacity Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water range Dt = 3∼8°C

2

Cooling capacity Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water range Dt = 3∼8°C

3

Power input Power input is total input according to Eurovent rating standard 6/C/003-2006

• Outdoor units • R-410A • ERYQ

4

Dimensional drawing & centre of gravity

4-1

Dimensional drawing unit (mm)

ERYQ Drain outlet (I.D. J 15.9 hose for connection)

Minimum space for air passage

Wall height on air outlet side = less than 1200

1 4

In case of removing stop valve cover 4 x holes for anchor bolts (M8 or M10)

Name plate Wiring inlet

Brand name label

Outdoor air thermistor

Terminal strip with earth terminal

Liquid stop valve (J6.4 CuT) Service port

Gas stop valve (J15.9 CuT)

3D051658C

• Altherma • Outdoor units

11

• Outdoor units • R-410A • ERYQ

1

4

Dimensional drawing & centre of gravity

4-2

Centre of gravity

ERYQ

4

The position of foundation bolt 4D042258H

12

• Altherma • Outdoor units

• Outdoor units • R-410A • ERYQ

5

Piping diagram

ERYQ-AC

1

Outdoor unit Heat exchanger

5

Outdoor air temperature thermistor

Capillary tube 1

Capillary tube 2 Capillary tube 3

Heat exchanger thermistor

Muffler with filter

Refrigerant flow Cooling Heating

Capillary tube 4

Filter Motor operated valve

Propeller fan

Filter Four way valve on : heating

Muffler with filter

Field piping

Muffler Liquid stop valve

Muffler Field piping Discharge pipe thermistor

Compressor

Accumulator

Gas stop valve with service port

3D052750B

• Altherma • Outdoor units

13

• Outdoor units • R-410A • ERYQ

1

6

Wiring diagram

6-1

Wiring diagram

ERYQ-AC

6 Power supply

To indoor unit

Sheet metal

Indoor

g Field wiring

(outdoor) (discharge) (Condenser) Outdoor Z1C∼Z7C X1M, X2M Y1E V2, V3, V5, V9, V100 SA2 FU1, FU2, FU3: AC1, AC2 U, V, W, X11A, X12A E1, E2 HR1, HR2

14

: Ferrite core : Terminal strip : Electronic expansion valve coil : Varistor : Surge arrester : Fuse

: Connector

MRM10, MRM20 MRC/W R1T∼R3T S2∼S102 LEDA L N SW1 SW4 M1C M1F L1R

: Magnetic relay : Thermistor : Connector : Pilot lamp : Live : Neutral : Forced operation on/off switch SW (SW1) : Local setting SW (SW4) : Compressor motors : Fan motor : Reactor

• Altherma • Outdoor units

Q1L PM1 PCB1,2 Y1R Sheet metal

: Overload protector : Power module : Printed circuit board : Reversing solenoide valve coil : Terminal strip fixed plate

3D052296C

• Outdoor units • R-410A • ERYQ

6

Wiring diagram

6-2

External connection diagram Standard parts

1

Power supply Outdoor unit 3 core

Unit power supply: 230V + earth

For more details please check unit wiring diagram

X1M:L-N-Earth

6

Backup heater power supply (3/6/9kW): 400V or 230V + earth Optional power supply X2M:1-2-3-Earth Booster heater power supply (3kW): 400V or 230V + earth 4 core

3 or4 core

3 core

Optional parts

Field supply X1M:9-10-11-Earth

Sanitary tank 2 way valve

2 core Q3L - Q1T Clixon Thermostat 2 way valve

Only for EKSWWU*V3 Power supply booster heater

5 core

230V or400V Q2L - Clixon booster heater

NO valve: NC valve:

2 core

Thermistor cable Note: min. distance to power cable = 3cm

Room thermostat A3P (optional)

2 core

2 core

R5T - Thermistor water temperature

Signal

4 core

X1M:7-8-Earth

2 way valve M2S (EKHBX Units) for cooling mode

3 way valve M3S (when EKSWW is installed) selection sanitary-floorheating

Indoor unit User interface

3TW56719-6A

• Altherma • Outdoor units

15

• Outdoor units • R-410A • ERYQ

7-1

Sound pressure spectrum

ERYQ005ACV3 Heating

ERYQ006ACV3 Heating Sound pressure level (dB)

7

Sound data

Sound pressure level (dB)

1

7

3TW57557-2

Octave band center frequency (Hz)

3TW57557-2

NOTES 1 2 3 4

Data is valid at free field condition (measured in a semi-anachoic room) dB(A) = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections.

1

Coil Microphone

2 3 4

Location of microphone

Octave band center frequency (Hz)

3TW57557-1

16

Microphone

Location of microphone

Data is valid at free field condition (measured in a semi-anachoic room) dB(A) = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections.

Octave band center frequency (Hz)

NOTES

NOTES

3 4

Coil

Sound pressure level (dB)

Sound pressure level (dB)

3TW57557-2

2

Data is valid at free field condition (measured in a semi-anachoic room) dB(A) = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections.

ERYQ005ACV3 Cooling

ERYQ007ACV3 Heating

1

Octave band center frequency (Hz)

NOTES

1 Coil Microphone

2 3 4

Location of microphone

• Altherma • Outdoor units

Data is valid at free field condition (measured in a semi-anachoic room) dB(A) = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections.

Coil Microphone

Location of microphone

• Outdoor units • R-410A • ERYQ

7

Sound data

7-1

Sound pressure spectrum ERYQ007ACV3 Cooling

3TW57557-1

Octave band center frequency (Hz)

2 3 4

Data is valid at free field condition (measured in a semi-anachoic room) dB(A) = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections.

7

3TW57557-1

NOTES 1

1

Sound pressure level (dB)

Sound pressure level (dB)

ERYQ006ACV3 Cooling

Octave band center frequency (Hz)

NOTES 1 Coil Microphone

2 3 4

Location of microphone

• Altherma • Outdoor units

Data is valid at free field condition (measured in a semi-anachoic room) dB(A) = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections.

Coil Microphone

Location of microphone

17

• Outdoor units • R-410A • ERYQ

8

Operation range

1

Outdoor temp. (°CDB)

8

Heating mode

: Units with optional back up heater

Leaving condenser water temperature (°C)

Cooling mode

Outdoor temp. (°CDB)

Leaving evaporator water temperature (°C)

Outdoor temp. (°CDB)

Sanitary mode

: Booster heater operation only

: Units with optional back up heater or booster heater operation only

Water temperature sanitary tank (°C)

4TW57553-1A

18

• Altherma • Outdoor units

• Indoor units • R-410A • EKHBH / EKHBX

TABLE OF CONTENTS EKHBH / EKHBX

1

Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

2

Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

21

Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

21 22

3

Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

24

4

Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . . 25 Dimensional drawing

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

5

Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

6

Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . External connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

7

27 29

Hydraulic performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Static pressure drop unit

• Altherma • Indoor units

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

19

• Indoor units • R-410A • EKHBH / EKHBX

1 H t K i E n u a/ m r rA Ho e0 Bo h1 Hd t4 nKl- E•IAR •

Features Cost effective alternative to a fossil fuel boiler



Easy to install

Low energy bills and low CO2 emissions



Total solution for year round comfort

2 1

20

• Altherma • Indoor units

• Indoor units • R-410A • EKHBH / EKHBX

2 2-1

Specifications TECHNICAL SPECIFICATIONS

Outdoor units Nominal input (Indoor only) Casing Dimensions

Packing

EKHBH007AC + ERYQ007AC

EKHBX007AC + ERYQ005AC

EKHBX007AC + ERYQ006AC

EKHBX007AC + ERYQ007AC

ERYQ005ACV3

ERYQ006ACV3

ERYQ007ACV3

ERYQ005ACV3

ERYQ006ACV3

ERYQ007ACV3

W

230

Colour

RAL9010 Epoxy polyester painted galvanised steel

Packing

mm

1225

mm

660

Depth

mm

Height

mm

895

936

Width

mm

487

487

Depth

461

595

mm

361

kg

55

65

Gross Weight

kg

65

75

Material

Pump

kg

EPS

EPS

Wood

Wood

Carton

Carton

PS (straps)

PS (straps)

10

10

Type

Water cooled

Nr. of speed Heating

kPa

Cooling

kPa

3 46.5

Water side Heat exchanger

Water flow rate Nom.

40.1

Water filter

46.5

40.1

29.0

49.9

45.9

44.7

130

130

Type

Brazed plate

Qty

1

Water volume

l

Water flow rate Min.

l/min

Heating

l/min

Cooling

l/min

0.67 12 16.5

19.6

Volume

l

Max. water pressure

bar

Pre pressure

bar

Diameter perforations

mm

16.5

19.6

24.1

14.7

16.8

17.4

Polyurethane foam 10 3 1 1

Material Piping connections diameter

24.1

-

Insulation material Expansion vessel

29.0

-

Power input

Brass inch

Piping

inch

Safety valve

bar

1"MBSP 1"MBSP 3

Manometer

Yes

Drain valve / Fill valve

Yes

Shut off valve

Yes

Air purge valve

Yes

Refrigerant Circuit

Gas side diameter

Sound Level Operation range

Waterside

Notes

2

Height

Machine weight

Nominal ESP unit

Water circuit

2

Width

Weight Main components

EKHBH007AC + ERYQ006AC

Material

Unit

Weight

EKHBH007AC + ERYQ005AC

mm

15.9

Liquid side diameter

mm

6.35

Sound Pressure

dBA

28

Heating

°C

25 - 50

Cooling

°C

-

5 - 20

The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value, depending on the distance and acoustic environment.

• Altherma • Indoor units

21

• Indoor units • R-410A • EKHBH / EKHBX

2 2-2

Specifications ELECTRICAL SPECIFICATIONS

Electric heater

Type Power Supply

2 Current

2

Phase Frequency Voltage Running Current Zmax Zmax electric heater + booster heater (EKSWW* Models)

Electric heater

Type Power Supply

Current

Phase Frequency Voltage Running Current Zmax Zmax electric heater + booster heater (EKSWW* Models)

Electric heater

Type Power Supply

Current

Phase Frequency Voltage Running Current Zmax Zmax electric heater + booster heater (EKSWW* Models)

Electric heater

Type Power Supply

Current

Phase Frequency Voltage Running Current Zmax Zmax electric heater + booster heater (EKSWW* Models)

22

Hz V A

EKHBH007AC + EKHBH007AC + EKHBH007AC + EKHBX007AC + EKHBX007AC + EKHBX007AC + ERYQ005AC ERYQ006AC ERYQ007AC ERYQ005AC ERYQ006AC ERYQ007AC 3V3 1~ 50 230 13

List Text List Text

Hz V A List Text List Text

Hz V A List Text List Text

Hz V A List Text List Text

• Altherma • Indoor units

No requirements

0.24 + j0.15

6V3 1~ 50 230 26

0.24 + j0.15 0.16 + j0.10

6W1 3N~ 50 400 8.6 No requirements No requirements

6T1 3~ 50 230 15 Out of scope Out of scope

• Indoor units • R-410A • EKHBH / EKHBX

2 2-2

Specifications ELECTRICAL SPECIFICATIONS

Electric heater

Type Power Supply

Current

Phase Frequency Voltage Running Current Zmax Zmax electric heater + booster heater (EKSWW* Models)

Electric heater

Type Power Supply

Current

Phase Frequency Voltage Running Current Zmax Zmax electric heater + booster heater (EKSWW* Models)

Notes

Hz V A

EKHBH007AC + EKHBH007AC + EKHBH007AC + EKHBX007AC + EKHBX007AC + EKHBX007AC + ERYQ005AC ERYQ006AC ERYQ007AC ERYQ005AC ERYQ006AC ERYQ007AC 9W1 3N~ 50 400 13

List Text List Text

2 2

No requirements No requirements

9T1 3~ 50 230 23

Hz V A List Text List Text

Out of scope Out of scope

Optional electric heater has 2 capacity steps except for the 3V3 model which has only 1 capacity step. For 6W1 and 9W1 models, neutral line only required for optional booster heater power supply Model without optional back up heater is powered via outdoor unit

• Altherma • Indoor units

23

24

Back up heater 6kW 1∼230 V

Back up heater 6kW 3∼400 V + N

Back up heater 6kW 3∼230 V

Back up heater 9kW 3∼400 V + N

Back up heater 9kW 3∼230 V

6V3

6W1

6T1

9W1

9T1

• Altherma • Indoor units

Sanitary warm water tank 200 l 230 V

Sanitary warm water tank 300 l 230 V

Sanitary warm water tank 200 l 400 V

Sanitary warm water tank 300 l 400 V

Sanitary warm water tank 150 l 230 V

Sanitary warm water tank 200 l 230 V

Sanitary warm water tank 300 l 230 V

Wall bracket for EKSWW150V3

Option kit forUK EKSWWU150∼300V3

EKSWW200V3

EKSWW300V3

EKSWW200Z2

EKSWW300Z2

EKSWWU150V3

EKSWWU200V3

EKSWWU300V3

EKWBSWW150

EKUSWW

⎯ ⎯ ⎯ ⎯

⎯ ⎯ ⎯ ⎯





V

V V

V

V





V

V

V

V

V

V

V



V



V

EKHBH007AC6V3 EKHBX007AC6V3

Note: An EKHB (H/X) 007AC* indoor unit can only be connected to an outdoor unit ERYQ005∼007AC*

Sanitary warm water tank 150 l 230 V

EKSWW150V3

Available kits

Back up heater 3kW 1∼230 V

3V3

Available options

EKHBH007AC3V3 EKHBX007AC3V3

V

V

V

V

V

V

V

V







V





EKHBH007AC6W1 EKHBX007AC6W1

V

V

V





V

V

V





V







EKHBH007AC6T1 EKHBX007AC6T1

Number

V

V

V

V

V

V

V

V



V









EKHBH007AC9W1 EKHBX007AC9W1

V

V

V





V

V

V

V











EKHBH007AC9T1 EKHBX007AC9T1

3TW57559-5

Kit

Kit

Kit

Kit

Kit

Kit

Kit

Kit

Kit

Kit

Factory mounted

Factory mounted

Factory mounted

Factory mounted

Factory mounted

Factory mounted

Availability

3

Heating only model Reversible model

Description

2

Reference

Optional equipment for EKHB(H/X)007AC*

• Indoor units • R-410A • EKHBH / EKHBX

Options

3

• Indoor units • R-410A • EKHBH / EKHBX

4

Dimensional drawing & centre of gravity

4-1

Dimensional drawing

EKHBH-AC

2 4

Service door

Setup 1 Setup 2

A ≥ 200 ≥ 350

B ≥ 400 ≥ 200

1’’ female BSP

(Closed) 361 (Open) 553

1’’ male BSP

Min. 150

Min. 200

Centre of gravity j 1 Pump + switch for speed setting j 2 Remocon j 3 Water IN conection 1’’ M BSP j 4 Water OUT connection 1’’ M BSP j 5 Power supply intake (+ sanitary warm water tank) j 6 Drain / fill valve j 7 Air purge j 8 Expansion vessel + nipple j 9 Blow off valve j 10 Pressure gauge j 11 Water filter j 12 Suction pipe connection J15.9 flare connection j 13 Liquid pipe connection J6.35 flare connection j 14 Shut off valves (delivered with unit) j 15 Thermistor connection (+ sanitary warm water tank) j 16 Holes for fixation j 17 Blow off drain / drain of drainpan j 18 Switchbox connection terminals j 19 Wallbracket

Min. 100

Minimum space for service & ventilation

3TW57554-1A

EKHBX-AC

Minimum space for service & ventilation

1’’ female BSP

(Closed) 461 (Open) 653

1’’ male BSP

Dimensions wallbracket

Min. 150

Min. 200

Centre of gravity j 1 Pump + switch for speed setting j 2 Remocon j 3 Water IN conection 1’’ M BSP j 4 Water OUT connection 1’’ M BSP j 5 Power supply intake (+ sanitary warm water tank) j 6 Drain / fill valve j 7 Air purge j 8 Expansion vessel + nipple j 9 Blow off valve j 10 Pressure gauge j 11 Water filter j 12 Suction pipe connection J15.9 flare connection j 13 Liquid pipe connection J6.35 flare connection j 14 Shut off valves (delivered with unit) j 15 Thermistor connection (+ sanitary warm water tank) j 16 Holes for fixation j 17 Blow off drain / drain of drainpan j 18 Switchbox connection terminals j 19 Wallbracket

Min. 125

Service door

Setup 1 Setup 2

A ≥ 200 ≥ 350

B ≥ 400 ≥ 200

3TW57564-1A

• Altherma • Indoor units

25

• Indoor units • R-410A • EKHBH / EKHBX

5

Piping diagram

EKHB -AC

Water side

R4T R3T R2T R1T

2

Inlet water thermistor Refrigerant liquid side thermistor Outlet water backup heater thermistor Outlet water heat-exchanger thermistor

Field installation Filter Inlet Shut off valve

5 Refrigerant side

Safety valve Drain valve

Pressure gauge

Drain

Expansion vessel Cooling (EKHBX) Heating (EKHBX + EKHBH)

Option backup heater Drain valve

Field installation

Air purge

Flowswitch

Pump

Outlet Shut off valve

Overview Electric heater body Evaporator Condensor

Outdoor unit

Refr. out Refr. in

Water inlet Refrigerant side

Water side

Refr. in Water outlet Refr. out

O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe PSpinned pipe

26

• Altherma • Indoor units

3TW56715-1

• Indoor units • R-410A • EKHBH / EKHBX

6

Wiring diagram

6-1

Wiring diagram

EKHB007AC3V3 Power supply 230V 1N∼50Hz

Outdoor unit

Sanitary tank

>> See note 2 > See note 2
See note 2 > See note 2 typcial 2-persons usage pattern. Medium Daily demand up to 325 l -> typical 3 to 4 persons usage pattern. High Daily demand up to 550 l -> 4 to 6 persons usage pattern.

(2) Heat-up time: Definition: Heat-up time The time required to reheat the sanitary tank to 55°C after tapping a certain volume of hot water at 40°C. note: changing the field settings (see installation manual) can influence the heat-up time.

Tank 150L 200L 300L

Heat-up time for 150 L (bath) 60 60 50

Setpoint temp. (°C) 55 55 55

Heat-up time for 50 L (shower) 45 40 30

Conditions for testing: Ta = 7°CDB / 6°CWB, Troom = 20°C, Tstart = 10°C, outdoor unit type: ERYQ007

(3) Efficiency of sanitary hot water production: In the ALTHERMA by Daikin system both the heat-pump and the electric booster heater supply the energy to produce sanitary hot water. The higher the portion of energy supplied by the heat-pump, the more energy efficient the system is. Lowering the setpoint temperature increases the portion of energy supplied by the heat-pump and thus the efficiency of the system.

Heat-pump portion

Definition: Heat-pump portion Percentage of energy supplied by the heat-pump in the total energy need for sanitary hot water.

Setpoint temp. (°C) Conditions:

Real life condition Outdoor temperature Room temperature Outdoor unit type Tank type Field settings

Simulation of a daily usage based upon ′medium′ usage pattern. 7°CDB / 6°CWB 20°CDB ERYQ007 200l Default field settings (see installation manual).

4TW56719-3

34

• Altherma • Sanitary Hot Water

• Sanitary Hot Water • R-410A • EKSWW

4

Dimensional drawing & centre of gravity

4-1

Dimensional drawing

EKSWW j 1 Water mains in female 3/4’’ BSP j 2 Water mains out female 3/4’’ BSP j 3 Thermistor connection female 1/2’’ BSP j 4 Flow (from hydrobox) female 3/4’’ BSP j 5 Return (to hydrobox) female 3/4’’ BSP j 6 Switchbox j 7 Clixon j 8 Connection female 3/4’’ BSP j 9 Power entrance

3 4 Required service space around the tank

3TW56714-4A

• Altherma • Sanitary Hot Water

35

• Sanitary Hot Water • R-410A • EKSWW

5

Wiring diagram

5-1

External connection diagram Standard parts

Power supply Outdoor unit 3 core

Unit power supply: 230V + earth

For more details please check unit wiring diagram

X1M:L-N-Earth

Backup heater power supply (3/6/9kW): 400V or 230V + earth Optional power supply

Optional parts

3 core

5

4 core

3 or4 core

3

X2M:1-2-3-Earth Booster heater power supply (3kW): 400V or 230V + earth

Field supply X1M:9-10-11-Earth

Sanitary tank 2 way valve

2 core Q3L - Q1T Clixon Thermostat 2 way valve

Only for EKSWWU*V3 Power supply booster heater

5 core

4 core

230V or400V Q2L - Clixon booster heater

NO valve: NC valve:

2 core

Thermistor cable Note: min. distance to power cable = 3cm

2 core

2 core

R5T - Thermistor water temperature

Signal

Room thermostat A3P (optional)

X1M:7-8-Earth

2 way valve M2S (EKHBX Units) for cooling mode

3 way valve M3S (when EKSWW is installed) selection sanitary-floorheating

Indoor unit User interface

3TW56719-6A

36